Plan Review Details - Permit 10080864
| Plan Review Stops For Permit 10080864 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2010-10-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-10-01 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-10-01 |
Time |
11:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2010-09-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-09-07 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-09-07 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2010-09-07 16:01:08 | DENIED BY BUILDING | | | | | | 1) THE DESIGN PRESSURES ON THE PRODUCT APPROVAL (+37.0, | | | -40.0) ARE TOO LOW FOR A TWO STORY STRUCTURE LOCATED IN | | | EXPOSURE C OF A 140 MPH WIND ZONE. IN ACCORDANCE WITH | | | 2007 FBC TABLES R301.2(4) AND R301.2(3), IF THE MEAN | | | ROOF HEIGHT OF THE STRUCTURE IS 25 FEET THE REQUIRED | | | PRESSURES ARE +40.1 AND -44.7. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2010-09-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-09-29 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2010-09-29 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2010-09-29 10:40:35 | INCOMING SENT TO R MC DOUGALS DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-10-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-10-01 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-09-01 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2010-09-01 09:04:22 | SENT TO PLUMBING UNDER $5000 BOX. |
|
|
|