Plan Review Details - Permit 10080864
Plan Review Stops For Permit 10080864
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-10-01 Cont ID  
Sent By rmcdouga Date 2010-10-01 Time 11:23 Rev Time 0.00
Received By rmcdouga Date 2010-10-01 Time 11:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-09-07 Cont ID  
Sent By rmcdouga Date 2010-09-07 Time 15:48 Rev Time 0.00
Received By rmcdouga Date 2010-09-07 Time 15:48 Sent To  
Notes
2010-09-07 16:01:08DENIED BY BUILDING
  
 1) THE DESIGN PRESSURES ON THE PRODUCT APPROVAL (+37.0,
 -40.0) ARE TOO LOW FOR A TWO STORY STRUCTURE LOCATED IN
 EXPOSURE C OF A 140 MPH WIND ZONE. IN ACCORDANCE WITH
 2007 FBC TABLES R301.2(4) AND R301.2(3), IF THE MEAN
 ROOF HEIGHT OF THE STRUCTURE IS 25 FEET THE REQUIRED
 PRESSURES ARE +40.1 AND -44.7.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-09-29 Cont ID  
Sent By jwitmer Date 2010-09-29 Time 10:39 Rev Time 0.00
Received By jwitmer Date 2010-09-29 Time 10:39 Sent To  
Notes
2010-09-29 10:40:35INCOMING SENT TO R MC DOUGALS DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-01 Cont ID  
Sent By rmcdouga Date 2010-10-01 Time 11:23 Rev Time 0.00
Received By rmcdouga Date 2010-09-01 Time 09:03 Sent To  
Notes
2010-09-01 09:04:22SENT TO PLUMBING UNDER $5000 BOX.