Plan Review Details - Permit 10080852
Plan Review Stops For Permit 10080852
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-10-14 Cont ID  
Sent By jgomez Date 2010-10-14 Time 08:58 Rev Time 0.00
Received By jgomez Date 2010-10-13 Time 14:23 Sent To PC
Notes
2010-10-14 09:04:03BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE ENERGY CALCULATIONS:
 A) REVISE WINDOW INFORMATION TO MATCH PLANS.
 B) REVISE EXTERIOR WALL INSULATION R VALUE TO MATCH
 PLANS. OR REVISE PLANS TO MATCH THE ENERGY
 CALCULATIONS.
 C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
 D) REVISE THE ROOF TYPE SHOWN ON SHEET 2 OF 5 TO MATCH
 PLANS.
 E) REVISE TYPE OF DOOR TO MATCH SHOWN ON SHEET 3 OF 5
 TO MATCH PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-09-29 Cont ID  
Sent By jgomez Date 2010-09-29 Time 14:01 Rev Time 0.00
Received By jgomez Date 2010-09-29 Time 13:08 Sent To  
Notes
2010-09-29 14:26:26RESIDENTIAL (R3) RENOVATION/ALTERATION BUILDING REVIEW
 CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF CHAPTER 11 OF 2007 FLORIDA RESIDENTIAL CODE.
 ***NOTE: PLEASE MAKE SURE CORRECT UPDATED FORM IS USED.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
  
 A) OVAL WINDOWS AS SHOWN ON PLANS.
  
 B) FRENCH DOOR WITH TRANSOM ABOVE AS SHOWN ON PLANS FOR
 ENTRY DOORS.
  
 C) NEW COMPOSITE SHUTTERS. AND PROVIDE COMPLETE
 INSTALLATION SCHEDULE.
  
 D) GARAGE DOOR. NOA 05-0912.11 SUBMITTED DOESN'T MEET
 THE DESIGN PRESSURES THAT WERE CALCULATED BY THE
 ENGINEER OF RECORD. AND, THIS NOA IS FOR AN 18'-0" WIDE
 DOOR. NEED TO PROVIDE PRODUCT APPROVAL THAT MEETS THE
 CALCULATED DESIGN PRESSURES AND WITH THE SIZE SPECIFIED
 ON PLANS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-10-07 Cont ID  
Sent By jleahy Date 2010-10-07 Time 10:23 Rev Time 0.00
Received By jleahy Date 2010-10-07 Time 10:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-09-30 Cont ID  
Sent By jleahy Date 2010-09-30 Time 15:19 Rev Time 0.00
Received By jleahy Date 2010-09-30 Time 15:19 Sent To  
Notes
2010-09-30 15:22:48NEED TO HAVE PANEL SCHEDULE.
  
 PANEL IN GARAGE CAN NOT BE IN A STORAGE CLOSET
  
 REMODELED BEDROOM TO THE RIGHT OF THE FRONT DOOR SHALL
 SHOW ALL OUTLETS AND SWITCHES FOR COMPLIANCE WITH THE
 CODE
  
 JAKE LEAHY
 644-7291

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-14 Cont ID  
Sent By jgomez Date 2010-10-14 Time 12:10 Rev Time 0.00
Received By jgomez Date 2010-10-06 Time 10:56 Sent To  
Notes
2010-10-06 11:00:07R-7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-30 Cont ID  
Sent By rmcdouga Date 2010-09-30 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2010-09-01 Time 10:08 Sent To  
Notes
2010-09-01 10:08:19SENT TO R-7.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2010-10-13 Cont ID  
Sent By jgomez Date 2010-10-13 Time 16:52 Rev Time 0.00
Received By jgomez Date 2010-10-13 Time 16:52 Sent To  
Notes
2010-10-13 16:55:30TALKED TO CHRISTOPHER BICKFORD (OWNER). AGREED THAT A/C
 CONTRACTOR WILL SUBMIT OWN PLANS AND EQUIPMENT SIZING
 CALCULATIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-09-29 Cont ID  
Sent By jgomez Date 2010-09-29 Time 13:15 Rev Time 0.00
Received By jgomez Date 2010-09-29 Time 13:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-10-14 Cont ID  
Sent By jgomez Date 2010-10-14 Time 12:10 Rev Time 0.00
Received By jgomez Date 2010-10-14 Time 12:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-09-29 Cont ID  
Sent By jgomez Date 2010-09-29 Time 13:16 Rev Time 0.00
Received By jgomez Date 2010-09-29 Time 13:16 Sent To  
Notes
2010-09-29 13:31:41RESIDENTIAL (R3) RENOVATION/ALTERATION PLUMBING REVIEW
 CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE PLUMBING RISER DIAGRAM WITH COMPLETE
 INFORMATION AS REQUIRED BY SEC. 106.3.5.4 OF CITY
 AMENDMENTS TO FBC. PLUMBING RISER DIAGRAM SUBMITTED ON
 SHEET P1 IS MISSING THE PLUMBING FIXTURES DRAINAGE PIPE
 SIZES AND LOCATION OF CLEANOUTS AS REQUIRED BY SEC.
 P3005 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 1 Status P Date 2010-09-13 Cont ID  
Sent By astelly Date 2010-09-13 Time 16:46 Rev Time 0.00
Received By astelly Date 2010-09-13 Time 16:46 Sent To  
Notes
***NONE***