Plan Review Details - Permit 10080815
Plan Review Stops For Permit 10080815
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-09-27 Cont ID  
Sent By jgomez Date 2010-09-27 Time 16:46 Rev Time 0.00
Received By jgomez Date 2010-09-27 Time 16:46 Sent To PC
Notes
2010-09-27 16:47:35BUILDING REVISION CHECKLIST:
  
 1- MISSING ALL THE INFORMATION REQUESTED ON PROVISO
 DATED 7/20/09. SEE COPY OF PROVISO COMMENTS BELOW:
  
  
 BUILDING REVIEW APPROVED WITH PROVISO: (PROVIDE
 INFORMATION FOR REVIEW PRIOR TO INSPECTION):
  
 1- PROVIDE 2 COPIES OF PRODUCT APPROVALS (RULE 9B-72)
 FOR: A) SHINGLES. B) SINGLE HUNG WINDOWS. C) ALL
 EXTERIOR DOORS. D) ALL SIMPSON STRUCTURAL CONNECTORS.
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO
 FBC.
 3- REVISE AND RE-SUBMIT ENERGY CALCULATIONS: REVISE
 BUILDING ORIENTATION SHOWN ON SHEET 3 SINCE
 CALCULATIONS ARE NOT DONE AS WORST CASE SCENARIO TO
 MATCH ACTUAL BUILDING ORIENTATION. SEE SURVEY.
 **NOTE: OWNER/AGENT TO SIGN AND DATE FORM.
 4- PROVIDE INFORMATION ON JOB SITE SHOWING COMPLIANCE
 WITH THE U-FACTOR AND SHGC FACTOR SHOWN ON THE ENERGY
 CALCULATIONS.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-27 Cont ID  
Sent By jgomez Date 2010-09-27 Time 16:49 Rev Time 0.00
Received By jgomez Date 2010-09-21 Time 09:23 Sent To  
Notes
2010-09-21 09:24:02TO JG DESK
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-09-27 Cont ID  
Sent By jgomez Date 2010-09-27 Time 16:51 Rev Time 0.00
Received By jgomez Date 2010-09-27 Time 16:51 Sent To  
Notes
***NONE***