Plan Review Details - Permit 10080787
Plan Review Stops For Permit 10080787
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-12-20 Cont ID  
Sent By shill Date 2010-12-20 Time 16:59 Rev Time 0.00
Received By shill Date 2010-12-20 Time 16:59 Sent To  
Notes
2010-12-20 17:01:53****PROVISO****
 ***PROVIDE AT INSPECTION***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FROM FIRST CORRECTION LIST: EITHER PROVIDE A WINDOW
 SCHEDULE OR REVISE THE FLOOR PLAN TO SHOW THE WINDOW
 SIZES, FBC1609.
  
 DOCUMENT SUBMITTED SHOWS WINDOW SIZE FOR OPENINGS 4, 1,
 AND 2. EITHER REVISE THE FLOOR PLAN OR PROVIDE A WINDOW
 SCHEDULE TO SHOW WINDOW SIZES FOR OPENINGS 3, 5, 6, 7.
  
 PER CONTRACTOR, ALL WINDOWS ARE SMALLER THAN MAX SIZE
 ALLOWED PER PRODUCT APPROVAL. REVISED FLOOR PLAN TO BE
 PROVIDED AT INSPECTION.
  
 2. ENGINEERING SHOW A MULLION, LOCATION UNCLEAR BASED
 ON DOCUMENTS PROVIDED. INCLUDE IN THE WINDOW SCHEDULE
 (OR REVISED FLOOR PLAN).
  
 PER CONTRACTOR, LOCATION WILL BE INDICATED ON FLOOR
 PLAN AND PROVIDED AT INSPECTION.
  
 3. ENGINEER IS TO REVISE ENGINEERING TO INCLUDE THE
 FOLLOWING INFORMATION:
 LOCATION SPECIFIC TO THE UNIT REGARDING PROPOSED
 INSSTALLATION
 THIRD PAGE OF ENGINEERING REFERS TO ADJUSTMENT FACTOR
 FOR 15' HEIGHT, REVISE OR PROVIDE EXPLANATION (ISN'T
 THIS A 4 STORY BUILDING?)
  
 PER ENGINEER, DISREGARD 3RD PAGE (NOTES FOR FILE ONLY,
 NOT INTENDED FOR PLAN REVIEW. DESIGN PRESSURES WERE
 CALCULATED CORRECTLY USING CORRECT BUILDING HEIGHT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-10-01 Cont ID  
Sent By shill Date 2010-10-01 Time 11:33 Rev Time 0.00
Received By shill Date 2010-10-01 Time 11:32 Sent To  
Notes
2010-10-01 11:37:29****PROVISO****
 ****REVISION REQUIRED****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FROM FIRST CORRECTION LIST: EITHER PROVIDE A WINDOW
 SCHEDULE OR REVISE THE FLOOR PLAN TO SHOW THE WINDOW
 SIZES, FBC1609.
  
 DOCUMENT SUBMITTED SHOWS WINDOW SIZE FOR OPENINGS 4, 1,
 AND 2. EITHER REVISE THE FLOOR PLAN OR PROVIDE A WINDOW
 SCHEDULE TO SHOW WINDOW SIZES FOR OPENINGS 3, 5, 6, 7.
  
 2. ENGINEERING SHOW A MULLION, LOCATION UNCLEAR BASED
 ON DOCUMENTS PROVIDED. INCLUDE IN THE WINDOW SCHEDULE
 (OR REVISED FLOOR PLAN).
  
 3. ENGINEER IS TO REVISE ENGINEERING TO INCLUDE THE
 FOLLOWING INFORMATION:
 LOCATION SPECIFIC TO THE UNIT REGARDING PROPOSED
 INSSTALLATION
 THIRD PAGE OF ENGINEERING REFERS TO ADJUSTMENT FACTOR
 FOR 15' HEIGHT, REVISE OR PROVIDE EXPLANATION (ISN'T
 THIS A 4 STORY BUILDING?)
  
  
  
 3. WITH THE REVISION, PROVIDE A COPY OF THE CONTRACT
 FOR THIS JOB.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-09-08 Cont ID  
Sent By shill Date 2010-09-08 Time 08:18 Rev Time 0.00
Received By shill Date 2010-09-08 Time 08:18 Sent To  
Notes
2010-09-08 08:29:30****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE PRODUCT APPROVALS SUBMITTED ARE ALREADY STAMPED
 FOR ANOTHER JOB (PERMIT NUMBER STAMP, DATE STAMP).
 PROVIDE CLEAN PRODUCT APPROVALS, SEE
 WWW.FLORIDABUILDING.ORG OR WWW.MIAMIDADE.GOV, FBC106.
  
 2. EITHER PROVIDE A WINDOW SCHEDULE OR REVISE THE FLOOR
 PLAN TO SHOW THE WINDOW SIZES, FBC1609.
  
 2. THE QUALIFIER IS REQUIRED TO SIGN THE PERMIT
 APPLICATION. PLEASE PRINT THE ENTIRE NAME OF THE
 INDIVIDUAL SIGNING THE DOCUMENT. THE PERMIT APPLICATION
 WAS SIGNED BY "DP MCMULLEN AS PRESIDENT" SO DOES NOT
 APPEAR TO BE SIGNED BY THE QUALIFIER DANNY MCMULLEN.
 THIS COMPANY DOES NOT HAVE ANY AUTHORIZED AGENTS ON
 FILE WITH THE CITY OF WEST PALM BEACH.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-09-27 Cont ID  
Sent By jgomez Date 2010-09-27 Time 10:18 Rev Time 0.00
Received By jgomez Date 2010-09-27 Time 10:18 Sent To  
Notes
2010-09-27 10:19:03SENT TO S. HILL'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-08 Cont ID  
Sent By shill Date 2010-09-08 Time 08:35 Rev Time 0.00
Received By shill Date 2010-08-31 Time 12:19 Sent To  
Notes
2010-08-31 12:20:39UNDER 5 K BUILDING