Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-09-07 Cont ID  
Sent By jwitmer Date 2010-09-07 Time 18:30 Rev Time 0.33
Received By jwitmer Date 2010-09-07 Time 18:10 Sent To  
Notes
2010-09-07 18:41:39BUILDING PLAN REVIEW
 PERMIT: 10080783
 ADD: 5700 GEORGIA AVE
 CONT: ADVANCED AIR & PLUMBING
 TEL: (561)722-1846
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISO:
 1) 2HOUR FIRE RATED WALL REQUIRES A 1 1/2 HR OPENING
 PROTECTIVES PER FBC-B TABLE 715.4 AND 715.4.7 DOOR
 CLOSING. FIRE DOORS SHALL BE SELF- OR AUTOMATIC CLOSING
 IN ACCORDANCE WITH THIS SECTION.
  
 2)FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-09-07 Cont ID  
Sent By wjolin Date 2010-09-07 Time 13:56 Rev Time 0.00
Received By wjolin Date 2010-09-07 Time 12:43 Sent To  
Notes
2010-09-07 13:56:15*****APPROVED WITH COMMENTS*****
  
 1) ADD THE FLORIDA FIRE PREVENTION CODE (FFPC) 2007
 EDITION TO THE CODE LIST.
  
 2) PROVIDE DOOR CLOSERS ON FIRE RATED DOORS PER SECTION
 8.3.3.3 OF FFPC NFPA 101, 2006 EDITION.
  
 3) NEW FIRE-RATED WALLS SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING WITH THE WORDING, "FIRE
 BARRIER - PROTECT ALL OPENINGS." SUCH LETTERING SHALL
 BE 4-INCHES TALL, HALF-INCH WIDE, AND NOT MORE THAN 15
 FEET ON CENTER PER SECTION 8.3.2.4 OF FFPC NFPA 101,
 2006 EDITION.
  
 4) SEVERAL "PLAN NOTES" ARE NOT RELEVANT TO THIS
 PROJECT (STAIRS, GARAGES, EGRESS WINDOWS ETC.).
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-07 Cont ID  
Sent By jwitmer Date 2010-09-07 Time 18:41 Rev Time 0.00
Received By jwitmer Date 2010-08-31 Time 11:49 Sent To  
Notes
2010-08-31 12:04:39B--7

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-09-07 Cont ID  
Sent By jwitmer Date 2010-09-07 Time 18:45 Rev Time 0.20
Received By jwitmer Date 2010-09-07 Time 18:32 Sent To  
Notes
***NONE***