Plan Review Details - Permit 10080780
| Plan Review Stops For Permit 10080780 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2010-10-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-10-07 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-10-07 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2010-10-07 10:35:09 | RIZA N. ALTAN PERFORMED UPLIFT TEST AND CERTIFIED THAT | | | ROOF MEETS THE CALCULATED DESIGN PRESSURES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2010-08-31 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-08-31 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-08-31 |
Time |
08:06 |
Sent To |
|
|
| Notes |
| 2010-08-31 08:58:23 | BUILDING REVIEW FOURTH CHECKLIST. | | | | | | 1- ROOF OVER USING GAF MATERIALS CAN'T BE DONE ON THIS | | | BUILDING. THERE ARE TWO NOTICE OF ACCEPTANCES FOR GAF | | | RECOVERY DECKS. THEY ARE NOA 08-0221.08 AND 08-0221.11. | | | NONE OF THE APPROVED ASSEMBLIES LISTED ON THESE NOA'S | | | CAN'T BE USED IN THIS BUILDING BECAUSE THEY ARE LIMITED | | | BY GENERAL LIMITATION #9. THIS LIMITATION DOESN'T ALLOW | | | NAIL ENHANCING TO INCREASE THE DESIGN PRESSURES OF THE | | | ASSEMBLY. SEE GENERAL LIMITATION #9 ON LAST PAGE OF | | | NOA'S. THE DESIGN PRESSURES LISTED ON THE APPROVED | | | ASSEMBLIES ARE TOO LOW TO MEET THE DESIGN PRESSURES | | | REQUIRED BY SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE. | | | THEREFORE, PROPOSED INSTALLATION IS NOT ALLOWED. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2010-08-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-08-30 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-08-30 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2010-08-30 16:45:34 | BUILDING REVIEW THIRD CHECKLIST. | | | | | | 1- NOTICE OF ACCEPTANCE NOA 09-0224.01 SUBMITTED IS FOR | | | A NEW ROOF OR RE-ROOF APPLICATION. NEED TO PROVIDE | | | PRODUCT APPROVAL FOR ROOF OVER APPLICATION AND SPECIFY | | | SPECIFIC APPROVED ASSEMBLY TO BE INSTALLED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF | | | 2007 FLORIDA RESIDENTIAL CODE. ALSO, CHECK THE GENERAL | | | LIMITATIONS FOR ANY REQUIRED INFORMATION REQUIRED TO BE | | | SUBMITTED. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2010-08-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-08-30 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-08-30 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2010-08-30 15:32:10 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW SECOND | | | CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | | 9B-72 FOR SPECIFIC ROOF OVER ASSEMBLY TO BE INSTALLED. | | | NEED TO CHECK APPROVED ASSEMBLY LIMITATIONS TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF | | | 2007 FLORIDA RESIDENTIAL CODE. | | | INFORMATION SUBMITTED ARE JUST THE MANUFACTURER | | | SPECIFICATION FOR ADHESIVE. THIS IS NOT A PRODUCT | | | APPROVAL. | | | | | | 2- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. | | | SEC. 108.3 CITY AMENDMENTS TO FBC. OWES $330.73 FOR | | | PERMIT FEE BALANCE AND UPDATED VALUATION. | | | | | | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED | | | BY SEC. 713.13 FLORIDA STATUTE. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2010-08-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-08-30 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-08-30 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2010-08-30 11:58:54 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- CLARIFY IF TYPE OF ROOF REPAIR. IS THIS A RE-ROOF OR | | | ROOF OVER. | | | | | | 2- A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS | | | FOR NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | 09-0820.09 SUBMITTED. | | | | | | B) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS | | | TO TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009 | | | FBC REVISIONS, THIS BUILDING IS LOCATED ON EXPOSURE | | | "C". | | | | | | 3- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. | | | SEC. 108.3 CITY AMENDMENTS TO FBC. OWES $330.73 FOR | | | PERMIT FEE BALANCE AND UPDATED VALUATION. | | | | | | 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED | | | BY SEC. 713.13 FLORIDA STATUTE. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2010-10-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-10-07 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-10-07 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2010-10-07 10:36:30 | RECEIVED TEST PACKAGE FROM DOUG WISE AND OWNER TODAY. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-09-02 |
Time |
14:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-08-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-08-30 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-08-30 |
Time |
11:35 |
Sent To |
|
|
| Notes |
|
|
|