Plan Review Details - Permit 10080780
Plan Review Stops For Permit 10080780
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2010-10-07 Cont ID  
Sent By jgomez Date 2010-10-07 Time 10:33 Rev Time 0.00
Received By jgomez Date 2010-10-07 Time 10:33 Sent To  
Notes
2010-10-07 10:35:09RIZA N. ALTAN PERFORMED UPLIFT TEST AND CERTIFIED THAT
 ROOF MEETS THE CALCULATED DESIGN PRESSURES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2010-08-31 Cont ID  
Sent By jgomez Date 2010-08-31 Time 08:52 Rev Time 0.00
Received By jgomez Date 2010-08-31 Time 08:06 Sent To  
Notes
2010-08-31 08:58:23BUILDING REVIEW FOURTH CHECKLIST.
  
 1- ROOF OVER USING GAF MATERIALS CAN'T BE DONE ON THIS
 BUILDING. THERE ARE TWO NOTICE OF ACCEPTANCES FOR GAF
 RECOVERY DECKS. THEY ARE NOA 08-0221.08 AND 08-0221.11.
 NONE OF THE APPROVED ASSEMBLIES LISTED ON THESE NOA'S
 CAN'T BE USED IN THIS BUILDING BECAUSE THEY ARE LIMITED
 BY GENERAL LIMITATION #9. THIS LIMITATION DOESN'T ALLOW
 NAIL ENHANCING TO INCREASE THE DESIGN PRESSURES OF THE
 ASSEMBLY. SEE GENERAL LIMITATION #9 ON LAST PAGE OF
 NOA'S. THE DESIGN PRESSURES LISTED ON THE APPROVED
 ASSEMBLIES ARE TOO LOW TO MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE.
 THEREFORE, PROPOSED INSTALLATION IS NOT ALLOWED.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2010-08-30 Cont ID  
Sent By jgomez Date 2010-08-30 Time 16:40 Rev Time 0.00
Received By jgomez Date 2010-08-30 Time 16:40 Sent To  
Notes
2010-08-30 16:45:34BUILDING REVIEW THIRD CHECKLIST.
  
 1- NOTICE OF ACCEPTANCE NOA 09-0224.01 SUBMITTED IS FOR
 A NEW ROOF OR RE-ROOF APPLICATION. NEED TO PROVIDE
 PRODUCT APPROVAL FOR ROOF OVER APPLICATION AND SPECIFY
 SPECIFIC APPROVED ASSEMBLY TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF
 2007 FLORIDA RESIDENTIAL CODE. ALSO, CHECK THE GENERAL
 LIMITATIONS FOR ANY REQUIRED INFORMATION REQUIRED TO BE
 SUBMITTED.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-08-30 Cont ID  
Sent By jgomez Date 2010-08-30 Time 15:26 Rev Time 0.00
Received By jgomez Date 2010-08-30 Time 15:26 Sent To  
Notes
2010-08-30 15:32:10RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR SPECIFIC ROOF OVER ASSEMBLY TO BE INSTALLED.
 NEED TO CHECK APPROVED ASSEMBLY LIMITATIONS TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF
 2007 FLORIDA RESIDENTIAL CODE.
 INFORMATION SUBMITTED ARE JUST THE MANUFACTURER
 SPECIFICATION FOR ADHESIVE. THIS IS NOT A PRODUCT
 APPROVAL.
  
 2- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 SEC. 108.3 CITY AMENDMENTS TO FBC. OWES $330.73 FOR
 PERMIT FEE BALANCE AND UPDATED VALUATION.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-08-30 Cont ID  
Sent By jgomez Date 2010-08-30 Time 11:50 Rev Time 0.00
Received By jgomez Date 2010-08-30 Time 11:35 Sent To  
Notes
2010-08-30 11:58:54RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- CLARIFY IF TYPE OF ROOF REPAIR. IS THIS A RE-ROOF OR
 ROOF OVER.
  
 2- A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS
 FOR NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 09-0820.09 SUBMITTED.
  
 B) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 TO TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009
 FBC REVISIONS, THIS BUILDING IS LOCATED ON EXPOSURE
 "C".
  
 3- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 SEC. 108.3 CITY AMENDMENTS TO FBC. OWES $330.73 FOR
 PERMIT FEE BALANCE AND UPDATED VALUATION.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-10-07 Cont ID  
Sent By jgomez Date 2010-10-07 Time 10:35 Rev Time 0.00
Received By jgomez Date 2010-10-07 Time 10:35 Sent To  
Notes
2010-10-07 10:36:30RECEIVED TEST PACKAGE FROM DOUG WISE AND OWNER TODAY.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2010-09-02 Time 14:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-30 Cont ID  
Sent By jgomez Date 2010-08-30 Time 11:35 Rev Time 0.00
Received By jgomez Date 2010-08-30 Time 11:35 Sent To  
Notes
***NONE***