Plan Review Details - Permit 10080761
| Plan Review Stops For Permit 10080761 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2010-09-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-09-07 |
Time |
17:18 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2010-09-07 |
Time |
17:01 |
Sent To |
|
|
| Notes |
| 2010-09-07 17:49:12 | BUILDING PLAN REVIEW | | | PERMIT: 10080761 | | | ADD: 222 LAKEVIEW AVE SUITE# 1400 | | | CONT: HOLT LEE | | | TEL: (954)270-1894 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | BUILDING PROVISO: | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | 1) SHEET A1.1 & A1.2 PLEASE INDICATE COMPLIANCE WITH | | | FBC-B 707.14.1 ELEVATOR LOBBIES AND THE REQUIREMENT | | | THAT ELEVATOR LOBBIES SHALL HAVE AT LEAST ONE MEANS OF | | | EGRESS COMPLYING WITH CHAPTER 10 AND OTHER PROVISIONS | | | WITHIN THIS CODE. | | | | | | JIM WITMER C. B. O. | | | COMMERCIAL COMBINATION PLAN REVIEW | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE | | | CUSTOMER SERVICE SURVEY AT: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2010-09-13 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2010-09-13 |
Time |
19:25 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2010-09-13 |
Time |
19:25 |
Sent To |
|
|
| Notes |
| 2010-09-13 19:25:44 | OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE | | | NUMBER PX3182 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2010-12-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-12-28 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-12-28 |
Time |
13:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2010-12-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-12-06 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-12-06 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2010-12-06 15:00:46 | 222 LAKEVIEW AVENUE, SUITE 1400 | | | MASTER PERMIT NUMBER 10080761 | | | REVISION TRACKING NUMBER 10110436 | | | "REVISED CEILING LAYOUT INCLUDING LIGHTING AND AC | | | DIFFUSERS" | | | | | | | | | 1. CARD READERS ARE DISPLAYED IN BOTH STAIRWELLS. CARD | | | READERS ARE NOT ALLOWED TO BE INSTALLED IN STAIRWELLS. | | | PLEASE SEE NFPA 101 THE LIFE SAFETY CODE SECTION | | | 7.1.3.2.1 (6) OF WHAT EQUIPMENT IS ALLOWED TO BE | | | CONTAINED WITHIN AN EXIT ENCLOSURE. IN ADDITION NFPA | | | 101 THE LIFE SAFETY CODE 7.2.1.5.7.1 SPEAKS TO STAIR | | | ENCLOSURE DOORS. ALSO 7.2.1.5.7 DISCUSSES STAIR | | | ENCLOSURES. | | | | | | 2. IF CARD READERS ARE INSTALLED AT THE ELEVATOR | | | LOBBIES HOW DOES A TRANSIENT VISITOR TO THE SPACE EXIT | | | THIS AREA WITHOUT AN ACCESS CARD. ACCESS TO BOTH EXITS | | | ARE MADE INACCESSIBLE AND WHEN THE FIRE ALARM SYSTEM | | | ACTIVATES IS IT THE ENTIRE BUILDING OR THE FLOOR OF | | | INCIDENT, FLOOR ABOVE AND FLOOR BELOW. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2010-09-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-09-10 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-09-10 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2010-09-10 13:21:23 | 222 LAKEVIEW AVENUE, SUITE 1400 | | | PERMIT NUMBER 10080761 | | | | | | 1. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM | | | SYSTEM REMODELING. | | | | | | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER SYSTEM REMODELING. | | | | | | 3. TACTILE SIGNAGE REQUIRED AT EXIT DOORS. | | | | | | 4. NEW FIRE DAMPERS ARE TO BE DROP TESTED TO ENSURE | | | PROPER FUNCTION. | | | | | | 5. INSTALLATIONS OF SOFFITS SHALL NOT INTERFERE WITH | | | ANY OPERATION OF ANY FIRE SPRINKLER HEADS. | | | | | | | | | APPROVED PROVISO | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2010-09-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-08-30 |
Time |
13:04 |
Sent To |
|
|
| Notes |
| 2010-08-30 13:04:43 | *****************EXPEDITED****************** | | | C--8 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2010-09-21 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2010-09-21 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2010-09-21 |
Time |
13:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2010-09-16 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2010-09-16 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2010-09-14 |
Time |
13:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2010-08-31 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2010-08-31 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2010-08-31 |
Time |
15:49 |
Sent To |
|
|
| Notes |
|
|
|