Plan Review Details - Permit 10080745
| Plan Review Stops For Permit 10080745 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2010-09-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-09-01 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-09-01 |
Time |
13:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2010-08-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-08-30 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-08-30 |
Time |
12:25 |
Sent To |
|
|
| Notes |
| 2010-08-30 12:31:24 | PALM BEACH ATLANTIC UNIVERSITY | | | 500 FERN STREET | | | PERMIT NUMBER 10080745 | | | | | | 1. NO FIRE ALARM SIGNALING APPLIANCES LOCATED IN | | | DRESSING ROOM, DESIGN ROOM, AREA OPPOSITE OF WORK | | | CENTER, OR COSTUME SHOP STORAGE. | | | | | | 2. NO SEQUENCE OF OPERATION INFORMATION PROVIDED WITH | | | DRAWINGS. | | | | | | 3. PLANS DO NOT INDICATE WHAT THE VOICE EVACUATION | | | PORTION OF THE FIRE ALARM SYSTEM WILL STATE. | | | | | | 4. NO SMOKE DETECTORS, HEAT DETECTORS, OR DUCT | | | DETECTORS DISPLAYED ON THE PLANS. | | | | | | 5. NO NOTES PROVIDED FOR THE DRAWINGS. | | | | | | 6. NO SMOKE DETECTOR DISPLAYED ABOVE FIRE ALARM CONTROL | | | PANEL. | | | | | | 7. NO INFORMATION PROVIDED REGARDING COMMUNICATION | | | METHODS FOR FIRE ALARM CONTROL PANEL. | | | | | | 8. FOUR SIGNALS ARE REQUIRED FOR THE FIRE ALARM SYSTEM | | | TO TRANSMIT. THEY ARE GENERAL FIRE ALARM, SUPERVISORY, | | | TROUBLE AND WATERFLOW. | | | | | | 9. THE FIRE ALARM SYSTEM SHALL BE EITHER UL OR FM | | | APPROVED FOR MONITORING FOR CENTRAL STATION SERVICE. | | | | | | ON AUGUST 30, 2010, THIS WRITER MET WITH KEN WEBB TO | | | DISCUSS THESE DEFICIENCIES. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-09-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-09-01 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-08-26 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2010-08-26 10:50:30 | ****************EXPEDITED******************* | | 2010-08-26 10:49:54 | PUT ON MIKE CARSILLO'S DESK |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |