Plan Review Details - Permit 10080689
Plan Review Stops For Permit 10080689
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-09-01 Cont ID  
Sent By jgomez Date 2010-09-01 Time 14:47 Rev Time 0.00
Received By jgomez Date 2010-09-01 Time 14:47 Sent To PC
Notes
2010-09-01 15:08:06BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- ROOFING EQUIPMENT REMOVAL REQUIRES SEPARATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-08-25 Cont ID  
Sent By jgomez Date 2010-08-25 Time 15:04 Rev Time 0.00
Received By jgomez Date 2010-08-25 Time 14:27 Sent To  
Notes
2010-08-25 15:57:47RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- ENGINEER TO REVISE WIND DESIGN CRITERIA AND
 PRESSURES. ACCORDING TO THE 2009 REVISIONS SEC.
 1609.4.3 THIS BUILDING IS LOCATED ON EXPOSURE "C" NOT
 "B". REVISE AS REQUIRED.
  
 2- ANY ROOFING EQUIPMENT REMOVAL REQUIRES SEPARATE
 PERMIT.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-25 Cont ID  
Sent By jgomez Date 2010-08-25 Time 14:27 Rev Time 0.00
Received By jgomez Date 2010-08-25 Time 14:27 Sent To  
Notes
***NONE***