Plan Review Details - Permit 10080678
Plan Review Stops For Permit 10080678
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-09-13 Cont ID  
Sent By dwise Date 2010-09-13 Time 16:16 Rev Time 0.00
Received By dwise Date 2010-09-13 Time 16:16 Sent To  
Notes
2010-09-13 16:18:40OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE
 NUMBER PX3182

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-08-25 Cont ID  
Sent By jleahy Date 2010-08-25 Time 09:23 Rev Time 0.00
Received By jleahy Date 2010-08-25 Time 09:23 Sent To  
Notes
2010-08-25 09:26:17RISER DIAGRAM SHOWS #3 WIRE TO ATM NEED TO SHOW SIZE OF
 BRANCH CIRCUIT PROTECTION AND WHAT SIZE
 WIRE TO SECOND ATM
  
 ALSO NEED TO SUBMIT PANEL SCHEDULE AND SHOW SIZE OF
 WIRE FROM METER TO ATM PANEL AND WHAT SIZE MAIN IN
 PANEL.
  
 SUBMIT FAULT CURRENT CALC AIC RATING OF MAINS AND BC
 BREAKERS.
  
 JAKE LEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-17 Cont ID  
Sent By shill Date 2011-11-17 Time 14:45 Rev Time  
Received By shill Date   Time   Sent To  
Notes
2011-11-17 14:45:1911/17/11 CLOSED "I" STOP FOR REPORTING PURPOSES
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***