Plan Review Details - Permit 10080635
Plan Review Stops For Permit 10080635
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date   Time 10:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-10-01 Cont ID  
Sent By jwitmer Date 2010-10-01 Time 10:47 Rev Time 0.33
Received By jwitmer Date 2010-10-01 Time 10:47 Sent To  
Notes
2010-10-01 10:57:45BUILDING PLAN REVIEW
 PERMIT: 10080635
 ADD: 8085 IRONHORSE BLVD
 CONT: GLOBE TEC CONSTRUCTION
  
 TEL: (954)214-3759
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS FAIL TO PROVIDE HOW THE GENERATOR WILL COMPLY
 WITH FBC-B 1604.4 EVERY STRUCTURE SHALL BE DESIGNED TO
 RESIST OVERTURNING EFFECTS CAUSED BY TTHE LATERAL
 FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR
 WIND. SHEET E-5 NOTE 5.
  
 2) SHEET E-5 INDICATES A DOUBLE WALL STEEL BASE TANK,
 PLEASE PROVIDE MANUFACTURERS SPEC ON THIS TANK.
  
 BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 REVIEW
 ACTION: DENIED

Review Stop E ELECTRICAL
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-09-30 Cont ID  
Sent By mcarsill Date 2010-09-30 Time 13:23 Rev Time 0.00
Received By mcarsill Date 2010-09-30 Time 13:20 Sent To  
Notes
2010-09-30 13:23:388085 IRONHORSE BOULEVARD
 PERMIT NUMBER 10080635
  
  
 ON SEPTEMBER 30, 2010, THIS WRITER SPOKE TO JONATHAN
 BRAMLEY, DIRECTOR OF ENGINEERING SERVICES. WE DISCUSSED
 THE PLANS AND IT APPEARS THAT ONE SET OF PLANS EXIST
 FOR TWO LOCATIONS.
  
 PREVIOUS PLAN REVIEW COMMENTS APPEAR TO BE ADDRESSED ON
 THE PLANS.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-09 Cont ID  
Sent By shill Date 2010-12-09 Time 16:31 Rev Time 0.00
Received By shill Date 2010-09-22 Time 07:51 Sent To  
Notes
2010-09-22 07:52:18C--8

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-10-26 Cont ID  
Sent By hmoser Date 2010-10-26 Time 16:11 Rev Time 0.00
Received By hmoser Date 2010-10-26 Time 16:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-10-26 Cont ID  
Sent By astelly Date 2010-10-26 Time 13:23 Rev Time 0.00
Received By astelly Date 2010-10-26 Time 13:23 Sent To  
Notes
2010-10-26 13:27:22AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 SCREENING FOR THE GENERATOR MUST BE PROVIDED THAT IS
 COMPATIBLE WITH THE SURROUNDING ARCHITECTURE. PLEASE
 SUBMIT PLAMS AND ELEVATIONS FOR THE REQUIRED SCREENING.
  
 PLEASE SUBMIT A SURVEY OF THE PROPERTY WITH THE
 LOCATION OF THE MECHANICAL EQUIPMENT CLEARY INDICATED.
 THE SITE PLAN SUGGEST THAT MECHANICAL EQUIPMENT MAY BE
 ENCROACHING ONTO THE NEIGHBORING PROPERTY.