Plan Review Details - Permit 10080630
Plan Review Stops For Permit 10080630
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-09-21 Cont ID  
Sent By wjolin Date 2010-09-21 Time 14:45 Rev Time 0.00
Received By wjolin Date 2010-09-21 Time 13:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-09-07 Cont ID  
Sent By wjolin Date 2010-09-07 Time 12:01 Rev Time 0.00
Received By wjolin Date 2010-09-07 Time 11:49 Sent To M
Notes
2010-09-07 12:01:51*****REVIEW COMMENTS - FIRE*****
  
 1) PROVIDE HYDRAULIC CALCULATIONS.
  
 2) PROVIDE CORRECT ORIFICE SIZE IN LEGEND FOR
 SPRINKLERS WITH K-FACTOR LESS THAN 5.6.
  
 3) TWO SIDEWALL SPRINKLERS NEAR BALCONY HAVE SPRAY
 OBSTRUCTED BY SOFFITS.
  
 4) LIGHT FIXTURE LOCATIONS NOT PROVIDED; HOWEVER, THE
 MINIMUM DISTANCE BETWEEN LIGHT FIXTURES AND RESIDENTIAL
 SIDEWALL SPRINKLERS IS 8'-0". VERIFY SPRAY IS NOT
 OBSTRUCTED.
  
 5) IS THE EXISTING BALCONY PROTECTED BY SPRINKLERS?
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-09-20 Cont ID  
Sent By rregueir Date 2010-09-20 Time 16:17 Rev Time 0.00
Received By rregueir Date 2010-09-20 Time 16:17 Sent To  
Notes
2010-09-20 16:17:54FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-13 Cont ID  
Sent By hmoser Date 2010-09-13 Time 14:35 Rev Time 0.00
Received By hmoser Date 2010-08-23 Time 16:25 Sent To  
Notes
2010-08-23 16:25:35TO FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-09-13 Cont ID  
Sent By hmoser Date 2010-09-13 Time 14:33 Rev Time 0.00
Received By hmoser Date 2010-09-13 Time 14:33 Sent To  
Notes
***NONE***