Plan Review Details - Permit 10080606
Plan Review Stops For Permit 10080606
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-08-30 Cont ID  
Sent By jwitmer Date 2010-08-30 Time 11:42 Rev Time 0.77
Received By jwitmer Date 2010-08-30 Time 11:42 Sent To  
Notes
2010-08-30 12:12:42BUILDING PLAN REVIEW
 PERMIT: 10080606
 ADD: 5100 S DIXIE HWY
 CONT: TBD
 CONTACT: IGLESIA "JESUCRIST VIVE" INC.
 TEL: (561)932-4164
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS * WEST PALM BEACH AMENDMENTS
 EXIST FL BLD CODE= 2007 EXISTING FLORIDA BUILDING CODE
 W/ 2009 SUPPLEMENETS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 901.3 CHANGE OF OCCUPANCY CLASSIFICATION. WHERE THE
 OCCUPANCY CLASSIFICATION OF A BUILDING CHANGES, THE
 PROVISIONS OF SECTIONS 902 THROUGH 912 SHALL APPLY.
 THIS INCLUDES A CHANGE OF OCCUPANCY CLASSIFICATION
 WITHIN A GROUP AS WELL AS A CHANGE OF OCCUPANCY
 CLASSIFICATION FROM ONE GROUP TO A DIFFERENT GROUP.
  
 901.3.1 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 912 SHALL APPLY.
  
 901.4 CERTIFICATE OF OCCUPANCY REQUIRED. A CERTIFICATE
 OF OCCUPANCY SHALL BE ISSUED WHERE A CHANGE OF
 OCCUPANCY OCCURS THAT RESULTS IN BEING CLASSIFIED AS A
 DIFFERENT OCCUPANCY CLASSIFICATION AS DETERMINED BY THE
 FLORIDA BUILDING CODE, BUILDING .
  
 2) PLEASE PROVIDE WHAT TYPES OF OCCUPANCIES ARE LOCATED
 ON BOTH SIDES OF THIS A-3 ASSEMBLY OCCUPANCY. EXIST BLD
 CODE 912.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH
 SEPARATION. WHERE A PORTION OF AN EXISTING BUILDING
 THAT IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION AND
 THAT PORTION IS SEPARATED FROM THE REMAINDER OF THE
 BUILDING WITH FIRE BARRIERS HAVING A FIRE-RESISTANCE
 RATING AS REQUIRED IN THE FLORIDA BUILDING CODE FOR THE
 SEPARATE OCCUPANCY, THAT PORTION SHALL COMPLY WITH ALL
 THE REQUIREMENTS OF CHAPTER 8 FOR THE NEW OCCUPANCY
 CLASSIFICATION AND WITH THE REQUIREMENTS OF THIS
 CHAPTER. FBC-B TABLE 508.3 REQUIRES A 2HR SEPERATION
 BETWEEN AN A-3 ASSEMBLY AND EITHER A BUSINESS OR
 MERCANTILE OCCUPANCY.
  
 3) 912.1.2 FIRE PROTECTION AND INTERIOR FINISH. THE
 PROVISIONS OF SECTIONS 912.2 AND 912.3 FOR FIRE
 PROTECTION AND INTERIOR FINISH, RESPECTIVELY, SHALL
 APPLY TO ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION.
  
 4) 106.3.5.MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS
 106.3.5.1.1:
 (2) OCCUPANCY GROUP
 (3) MINIMUM TYPE OF CONSTRUCTION
 (4) FIRE- RESISTANT SEPERATIONS
 (5) DOES THIS BUILDING HAVE FIRE SPRINKLERS?
 EARLY WARNING SMOKE EVACUATION SYSTEM?
 (7)OCCUPANCY LOAD/ EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANT LOAD
 GROSS NEET
 MEANS OF EGRESS
 EGRESS EMERGENCY LIGHTING AND EXIT SIGNAGE
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-09-07 Cont ID  
Sent By wjolin Date 2010-09-07 Time 15:06 Rev Time 0.00
Received By wjolin Date 2010-09-07 Time 14:39 Sent To  
Notes
2010-09-07 15:06:37*****REVIEW COMMENTS - FIRE*****
  
 1) DETERMINE THE OCCUPANT LOAD BASED UPON THE FLORIDA
 FIRE PREVENTION CODE (2007 EDITION).
  
 2) PROVIDE EMERGENCY LIGHTING.
  
 3) PROVIDE FIRE EXTINGUISHERS.
  
 4) PROVIDE EXIT SIGNS.
  
 5) PROVIDE FIRE RATED SEPARATION BETWEEN ASSEMBLY
 OCCUPANCY AND ADJACENT TENANT SPACES.
  
 6) PROVIDE SEATING DIAGRAM.
  
 7) PROVIDE INFORMATION ON EXISTING DOORS (IE, LOCKS,
 CLOSERS, CONSTRUCTION MATERIAL ETC.)
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-22 Cont ID  
Sent By lmartine Date 2010-09-07 Time 12:24 Rev Time 0.00
Received By lmartine Date 2010-08-24 Time 10:22 Sent To  
Notes
2010-08-24 10:22:45B11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-09-01 Cont ID  
Sent By lwagner Date 2010-09-01 Time 09:33 Rev Time 0.00
Received By lwagner Date 2010-09-01 Time 09:15 Sent To  
Notes
2010-09-01 09:32:44FBC PLUMBING 2007
 REVIEW # 1
 DENIED:
  
 FBC PLUMBING 2007 403.1 MINIMUN FIXTURES - A-3
 OCCUPANCY REQUIRES SEPERATE FACILITIES FOR MEN AND
 WOMEN
 1. MENS ADA RESTROOM - 1 WC PER 150, 1 LAVITORY PER 200
 2. WOMENS ADA RESTROOM - 1 WC PER 75 , 1 LAVITORY PER
 200
 3. 1 DRINKING FOUNTAIN IS REQUIRED PER 1,000 PERSONS.
 4. 1 SERVICE SINK IS REQUIRED.
  
 FBC PLUMBING 2007 607.1 HOT WATER IS REQUIRED FOR
 SERVICE SINKS.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2010-08-30 Cont ID  
Sent By astelly Date 2010-08-30 Time 14:35 Rev Time 0.00
Received By astelly Date 2010-08-30 Time 14:35 Sent To  
Notes
***NONE***