| 2010-09-02 12:23:16 | BUILDING PLAN REVIEW |
| | PERMIT: 10060348/ REVISION# 10080514 |
| | ADD: 7611 WASHINGTON RD |
| | CONT: O/B PATICIA TILFORD |
| | TEL: (561)312-0848 |
| | |
| | FL BLD CODE= 2007 FLORIDA RESIDENTIAL BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | 1) SCOPE OF WORK HAS INCREASED PLEASE INDICATE THE |
| | INCRREASE OF VALUE OF WORK, THIS IS TO BE FAIR MARKET |
| | VALUE AS IF A CONTRACTOR IS COMPLETING THE WORK. |
| | 1A) THE CUTTING OF EXISTING SLAB AND ADDING FOUNDATION |
| | AND REBAR. |
| | 1B) REMOVAL OF EXISTING FLAT ROOF SYSTEM AND DRYWALL |
| | CEILINGS AND THE NEW TRUSSES, ROOF SHEATHING. |
| | 1C) NEW PERMIT REQUIRED FOR NEW ROOFING SYSTEM. |
| | SEPERATE REVIEW, AND ASSOCIATED FEES. |
| | |
| | W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| | ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| | AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| | A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| | APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) DISCCREPANCY IN PLANS, THE RIGHT ELEVATION INDICATES |
| | THE EXISTING ROOF TO BE SHINGLES BUT THE W-1 WALL |
| | SECTION INDICATES THE USE OF FLAT CONCRETE TILE. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. PLEASE NOTE AN |
| | ADDITIONAL ROOFING PERMIT WILL BE REQUIRED WITH |
| | SEPERATE REVIEW AND FEES. PLEASE PROVIDE TWO COPIES OF |
| | THE PRODUCT APPROVAL FOR THE TYPE OF SYSTEM TO BE |
| | INSTALLED ON YOUR ROOFING. IF THE EXISTING ROOF IS |
| | GOING TO HAVE CONCRETE ROOF TILES INSTALLED ON THE |
| | EXISTING ROOF FRAMING A ENGINEER WILL NEED TO EVALUATE |
| | THE ROOFING SYSTEM TO SEE IF THE ROOF FRAMING WILL TAKE |
| | THE ADDITIONAL DEAD LOAD OF THE ROOF TILE. |
| | |
| | 3) DISCREPANCY IN PLANS, LOWER LEFT CORNER OF PLANS THE |
| | FRONT ELEVATION INDICATES THE GABLE END TO HAVE A 2'-0" |
| | OVERHANG ON THE GABLE END WHERE AS THE ROOF FRAMING |
| | DETAIL |
| | INDICATES A W-1 WALL SECTION, THIS WOULD CREATE A HIP |
| | AND NOT A GABLE END. THE ROOF FRAMING PLAN ALSO APPEARS |
| | TO HAVE A 1'-0" OVER HANG. IF THE FRONT ELEVATION IS |
| | CORRECT WITH THE 2'-0" OVERHANG ON THTE GABLE END WOULD |
| | THE PLAN NOT REQUIRE A DROPPED GABLE FOR THE PROPOSED |
| | 2'-0" OVERHANG? 106.1.2 ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 4) PLANS WILL NOW REQUIRE A TERMITE SOIL PRETREAT SINCE |
| | THE CONCRETE SLAB IS BEING CUT AND NEW FOUNDATION IS |
| | BEING ADDED. FBC-RESIDENTIALR320.1 & TABLE R301.2(6). |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |