Plan Review Details - Permit 10080423
Plan Review Stops For Permit 10080423
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-09-09 Cont ID  
Sent By jwitmer Date 2010-09-09 Time 13:08 Rev Time 0.20
Received By jwitmer Date 2010-09-09 Time 12:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-08-19 Cont ID  
Sent By jleahy Date 2010-08-19 Time 07:45 Rev Time 0.00
Received By jleahy Date 2010-08-19 Time 07:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-09-21 Cont ID  
Sent By wjolin Date 2010-09-21 Time 10:55 Rev Time 0.00
Received By wjolin Date 2010-09-17 Time 14:17 Sent To  
Notes
2010-09-21 10:55:043415 SOUTH DIXIE HIGHWAY
 REVISION TRACKING #10080423
 MASTER PERMIT #08100686
  
 10/28/10 CLARIFICATION RECEIVED FROM ARCHITECT.
 DISREGARD ORIGINAL REVIEW COMMENT BELOW. CHANGED REVIEW
 FROM FAILED STATUS TO PASSED STATUS. WJ
  
 REVIEW COMMENTS - FIRE:
 SHEETS A4 & A19: SLIDING POCKET DOORS ARE REQUIRED TO
 BE POWER OPERATED PER SECTION 7.2.1.14(6) OF THE
 FLORIDA FIRE PREVENTION CODE (NFPA 101, 2006 EDITION
 WITH FLORIDA AMENDMENTS).
  
 WESLEY JOLIN
 FIRE AND LIFE SAFETY PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-21 Cont ID  
Sent By wjolin Date 2010-09-21 Time 10:55 Rev Time 0.00
Received By wjolin Date 2010-08-17 Time 13:38 Sent To  
Notes
2010-08-17 13:45:10C--23