Plan Review Details - Permit 10080415
Plan Review Stops For Permit 10080415
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-11-01 Cont ID  
Sent By jwitmer Date 2010-11-01 Time 15:27 Rev Time 0.77
Received By jwitmer Date 2010-11-01 Time 15:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-09-09 Cont ID  
Sent By jwitmer Date 2010-09-09 Time 14:45 Rev Time 0.00
Received By jwitmer Date 2010-09-09 Time 14:00 Sent To  
Notes
2010-09-09 14:55:35BUILDING PLAN REVIEW
 PERMIT: 10080415
 ADD: 3913 HEATH CIR S
 CONT: O/B HARRIS, TRACY
 TEL: (561)315-0142
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
 2007 RESIDENTIAL/ 2009 SUPPLEMENTS
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE THE WIND DESIGN CRITERIA:1609.6.2
 WIND DESIGN PROCEDURES
 1.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 1.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4. CONSIDERED AN ???C??? EXPOSURE.
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 2) MISSING INFORMATION ON EITHER RIDGE BOARD & GUSSET
 PLATES. R802.2.1 FRAMING DETAILS. RAFTERS SHALL BE
 FRAMED TO RIDGE BOARD OR TO EACH OTHER WITH A GUSSET
 PLATE AS A TIE. RIDGE BOARD SHALL BE AT LEAST 1-INCH
 (25 MM) NOMINAL THICKNESS AND NOT LESS IN DEPTH THAN
 THE CUT END OF THE RAFTER. WHERE THE ROOF PITCH IS LESS
 THAN THREE UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (25-PERCENT SLOPE), STRUCTURAL MEMBERS THAT SUPPORT
 RAFTERS AND CEILING JOISTS, SUCH AS RIDGE BEAMS, HIPS
 AND VALLEYS, SHALL BE DESIGNED AS BEAMS.
  
 3) R802.2.1.1 CEILING JOIST AND RAFTER CONNECTIONS.
 CEILING JOISTS AND RAFTERS SHALL BE NAILED TO EACH
 OTHER IN ACCORDANCE WITH TABLES R602.2(1) AND
 R802.2.3(9) AND THE ASSEMBLY SHALL BE NAILED TO THE TOP
 WALL PLATE IN ACCORDANCE WITH TABLE R602.2(1). CEILING
 JOISTS SHALL BE CONTINUOUS OR SECURELY JOINED WHERE
 THEY MEET OVER INTERIOR PARTITIONS AND NAILED TO
 ADJACENT RAFTERS TO PROVIDE A CONTINUOUS TIE ACROSS THE
 BUILDING WHEN SUCH JOISTS ARE PARALLEL TO THE RAFTERS.
  
 WHERE CEILING JOISTS ARE NOT CONNECTED TO THE RAFTERS
 AT THE TOP WALL PLATE, JOISTS CONNECTED HIGHER IN THE
 ATTIC SHALL BE INSTALLED AS RAFTER TIES, OR RAFTER TIES
 SHALL BE INSTALLED TO PROVIDE A CONTINUOUS TIE. WHERE
 CEILING JOISTS ARE NOT PARALLEL TO RAFTERS, RAFTER TIES
 SHALL BE INSTALLED. RAFTER TIES SHALL BE A MINIMUM OF
 2-INCH BY 4-INCH (51 MM BY 102 MM) (NOMINAL), INSTALLED
 IN ACCORDANCE WITH THE CONNECTION REQUIREMENTS IN TABLE
 R802.2.3(9), OR CONNECTIONS OF EQUIVALENT CAPACITIES
 SHALL BE PROVIDED. WHERE CEILING JOISTS OR RAFTER TIES
 ARE NOT PROVIDED, THE RIDGE FORMED BY THESE RAFTERS
 SHALL BE SUPPORTED BY A WALL OR GIRDER DESIGNED IN
 ACCORDANCE WITH ACCEPTED ENGINEERING PRACTICE.
  
 COLLAR TIES OR RIDGE STRAPS TO RESIST WIND UPLIFT SHALL
 BE CONNECTED IN THE UPPER THIRD OF THE ATTIC SPACE IN
 ACCORDANCE WITH TABLE R602.2(1).
  
 COLLAR TIES SHALL BE A MINIMUM OF 1 INCH BY 4 INCH (25
 MM BY 102 MM) (NOMINAL), SPACED NOT MORE THAN 4 FEET
 (1219 MM) ON CENTER.
  
 4) ROOF SHINGLES AND UNDERLAYMENT. R905.2.2 SLOPE.
 ASPHALT SHINGLES SHALL ONLY BE USED ON ROOF SLOPES OF
 TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) OR
 GREATER. FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12
 UNITS HORIZONTAL (2:12) UP TO FOUR UNITS VERTICAL IN 12
 UNITS HORIZONTAL (4:12), TWO LAYERS OF UNDERLAYMENT
 COMPLYING WITH ASTM D226, TYPE I OR TYPE II, ASTM D
 4869, TYPE I OR TYPE II OR ASTM D6757 ARE REQUIRED IN
 ACCORDANCE WITH SECTION R905.2.7.
  
 5) PLEASE PROVIDE PRODUCT APPROVAL FOR ASPHALT
 SHINGLES. R905.2.4.1.
  
 6) PLEASE PROVIDE COMPLIANCE WITH R704.1 IN ORDER TO
 PROVIDE FOR INSPECTION FOR TERMITE INFESTATION,
 CLEARANCE BETWEEN EXTERIOR WALL COVERINGS AND FINAL
 EARTH GRADE ON THE EXTERIOR OF A BUILDING SHALL NOT BE
 LESS THAN 6 INCHES (152 MM).
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-27 Cont ID  
Sent By lmartine Date 2010-10-27 Time 13:20 Rev Time 0.00
Received By lmartine Date 2010-10-27 Time 13:20 Sent To  
Notes
2010-10-27 13:21:30IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-09 Cont ID  
Sent By jwitmer Date 2010-09-09 Time 14:55 Rev Time 0.00
Received By jwitmer Date 2010-08-17 Time 13:49 Sent To  
Notes
2010-08-17 13:49:22IN ZONING BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2010-10-29 Cont ID  
Sent By astelly Date 2010-10-29 Time 12:12 Rev Time 0.00
Received By astelly Date 2010-10-29 Time 12:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-08-25 Cont ID  
Sent By astelly Date 2010-08-25 Time 12:01 Rev Time 0.00
Received By astelly Date 2010-08-25 Time 12:01 Sent To B
Notes
2010-08-26 17:18:03AMY STELLY
 PLANNING AND ZONING
 822-1442
  
 THE LOCATION OF THE SHED DOES NOT MEET THE REQUIRED
 MINIMUM 5-FOOT SETBACK FROM THE SIDE PROPERTY LINE.