Plan Review Details - Permit 10080204
Plan Review Stops For Permit 10080204
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-01-20 Cont ID  
Sent By jwitmer Date 2011-01-20 Time 12:51 Rev Time 1.07
Received By jwitmer Date 2011-01-20 Time 12:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-08-18 Cont ID  
Sent By jwitmer Date 2010-08-18 Time 07:58 Rev Time 0.77
Received By jwitmer Date 2010-08-18 Time 07:58 Sent To  
Notes
2010-08-18 08:14:11BUILDING PLAN REVIEW
 PERMIT:10080204
 ADD: 1100 45TH ST
 CONT:489 EXEMPT103 EXC# 3 / STATE OF FLORIDA DEPART
 JUVENILE JUSTICE
 TEL: (954)4448550
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED ARE CONSIDERED AN ENGINEERED SYSTEM
 BUT UNDER FLORIDA RULE 9B-72(31)(G) THESE TYPE SYSTEMS
 OR STRUCTURES REQUIRE AN APPROVED PRODUCT APPROVAL
 EITHER FROM THE STATE, MIAMI-DADE NOA OR OTHER APPROVED
 TESTING AGENCY.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG PLEASE
 REVIEW UNDER CATEGORY STRUCTURAL COMPONENTS THERE ARE
 19 PAGES WITH A MINIMUM OF 5 STATE APPROVALS FOR
 EXTERIOR COOLER -FREEZERS.
  
 2) TO SUBMIT THIS SYSTEM FOR A LOCAL APPROVAL THE SAME
 TEN CRITERIA AS THE STATE WILL BE REQUIRED AND ARE
 ATTACHED TO THE COMMENTS. NOTE A THIRD PARTY QUALITY
 ASSURANCE PROGRAM HAS TO BE IN PLACE SEE REQUIREMENT#
 7.
  
 3) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-08-30 Cont ID  
Sent By shill Date 2010-08-30 Time 17:18 Rev Time 0.00
Received By shill Date 2010-08-30 Time 17:18 Sent To  
Notes
2010-08-30 17:30:33********NOT ENOUGHT ELECTRICAL INFOMATION
 SUMITED**********
 1) NEED EXISTING BUILDING ELECTRIC SERVICE RISER
 DIAGRAM
 2) NEED LOAD CALCUATIONS FOR NEW REF. EQUIPMENT LOAD
 ONTO EXISTING ELECT. SERVICE
 3)ELECTRIC DIAGRAM SHOWING ALL CONDUIT AND WIRE SIZES
 FOR WIRING OF NEW EQUIPMENT
 JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE NUMBER
 PX3182
 CELL PHONE MUMBER 561- 718- 3230

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-01-12 Cont ID  
Sent By ddaniels Date 2011-01-12 Time 13:05 Rev Time 0.00
Received By ddaniels Date 2011-01-12 Time 13:05 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-09-07 Cont ID  
Sent By mcarsill Date 2010-09-07 Time 11:21 Rev Time 0.00
Received By mcarsill Date 2010-09-07 Time 11:20 Sent To  
Notes
2010-09-07 11:20:58PLANS WERE REVIEWED ON 8/19/10.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-11 Cont ID  
Sent By jgomez Date 2011-01-11 Time 08:53 Rev Time 0.00
Received By jgomez Date 2011-01-11 Time 08:48 Sent To  
Notes
2011-01-11 08:53:36SENT TO B6.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-09-09 Time   Rev Time 0.00
Received By shill Date 2010-08-10 Time 17:23 Sent To  
Notes
2010-08-10 17:23:54B 14
  

Review Stop L LANDSCAPING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2011-01-28 Cont ID  
Sent By rkussner Date 2011-01-28 Time 14:01 Rev Time 0.00
Received By rkussner Date 2011-01-28 Time 14:00 Sent To  
Notes
2011-01-28 14:10:38***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PURSUANT TO SECTION 94-444 (B), OUTDOOR
 INCINERATORS, GARBAGE OR TRASH RECEPTACLES, FUEL OIL OR
 PROPANE TANKS, STORAGE RACKS AND OTHER MECHANICAL
 EQUIPMENT SHALL NOT BE PERMITTED UNLESS APPROPRIATE
 SCREENING IS PROVIDED. SCREENING SHALL BE CONSTRUCTED
 OF BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE
 MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL. WALLS
 SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT
 TWO-FOOT INTERVALS.
  
 2. PURSUANT TO SECTION 94-445 (4) (G) (3) (II), IN
 AREAS THAT TO BE PLANTED IN A CULTIVATED LANDSCAPE,
 IRRIGATION SYSTEMS SHALL BE DESIGNED TO HAVE 120
 PERCENT COVERAGE.
  
 3. PLEASE APPLY FOR SEPARATE LANDSCAPE, FENCE AND
 IRRIGATION PERMITS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-09-09 Cont ID  
Sent By rregueir Date 2010-09-09 Time 14:41 Rev Time 0.00
Received By rregueir Date 2010-09-09 Time 14:40 Sent To  
Notes
2010-09-09 14:41:21MECHANICAL SCOPE NOT PART OF THIS REVIEW. SEPARATE
 PLANS AND PERMIT REQUIRED FOR MECHANICAL WORK.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2011-01-28 Cont ID  
Sent By lfranco Date 2011-01-28 Time 12:25 Rev Time 0.00
Received By lfranco Date 2011-01-28 Time 10:57 Sent To L
Notes
2011-01-28 12:38:26PLANNING AND ZONING: **** FAILED ****
  
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. AN APPROVED EASEMENT CONSENT FORM FROM THE CITY OF
 WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES (4TH
 FLOOR, CITY HALL) IS REQUIRED FOR ALL PROPOSED
 FENCES/WALLS.
  
 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED
 MECHANICAL/FREEZER EQUIPMENT TO ALL PROPERTY LINES.
 PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK.
  
  
 4. THE SITE PLAN SHALL INCLUDE THE FOLLOWING:
  
 A. PROVIDE ELEVATIONS WITH DIMENSIONS INCLUDING TOTAL
 HEIGHT OF FREEZE AND ASSOCIATED EQUIPMENT. PROVIDE A
 FLOOR PLAN OF SCREENING AND LANDSCAPING DETAIL. INCLUDE
 WALL/FENCE HEIGHT, ETC.,
  
 PROVIDE DETAIL OF ALL ENCLOSURES WITH LANDSCAPING ON
 THE SITE PLAN/FLOOR PLANS. CURBING WILL BE REQUIRED TO
 PROTECT THE LANDSCAPING.
  
 PURSUANT TO SECTION 94-444(B) OPEN SPACE STANDARDS:
  
 THE FREEZER EQUIPMENT SHALL NOT BE PERMITTED UNLESS
 APPROPRIATE SCREENING IS PROVIDED. SCREENING SHALL BE
 CONSTRUCTED OF BRICK, DECORATIVE CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY, DURABLE WOOD AND
 STEEL.
  
 WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS. PROVIDE TYPE OF
 LANDSCAPING TO BE INSTALLED. A FOUR-SIDED ENCLOSURE
 WITH MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL, AN
 OBSCURING GATE IS REQUIRED AS A CONDITION FOR SITE PLAN
 APPROVAL. CONTACT ROBERT KUSSNER (LANDSCAPE PLANNER)
 FOR MORE INFORMATION (561) 822-1462
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-09-07 Cont ID  
Sent By lfranco Date 2010-09-07 Time 11:01 Rev Time 0.00
Received By lfranco Date 2010-09-07 Time 11:01 Sent To FIRE
Notes
2010-09-07 11:05:48PLANNING AND ZONING: **** FAILED ****
  
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION
 (SHOW LOCATION OF FREEZER/SLAB ON SURVEY W/ DIMENSIONS
 FROM ALL PROPERTY LINES, SEE COMMENTS #4).
  
 3. AN APPROVED EASEMENT CONSENT FORM FROM THE CITY OF
 WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES (4TH
 FLOOR, CITY HALL) IS REQUIRED FOR ALL PROPOSED
 FENCES/WALLS.
  
 4. INDICATE SETBACK DIMENSIONS FROM PROPOSED
 MECHANICAL/FREEZER EQUIPMENT TO ALL PROPERTY LINES.
 PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  