Plan Review Details - Permit 10080159
Plan Review Stops For Permit 10080159
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-10-25 Cont ID  
Sent By jwitmer Date 2010-10-25 Time 14:48 Rev Time 0.55
Received By jwitmer Date 2010-10-25 Time 14:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-08-18 Cont ID  
Sent By jwitmer Date 2010-08-18 Time 08:31 Rev Time 0.77
Received By jwitmer Date 2010-08-18 Time 08:31 Sent To  
Notes
2010-08-18 08:38:32BUILDING PLAN REVIEW
 PERMIT: 10080159
 ADD:2139 PALM BEACH LAKES BLVD
 CONT: KNIGHT ELECTRIC CO
 TEL: (561)689-3500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) EMERGENCY AND STANDBY POWER SYSTEMS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE NFPA 70, NATIONAL
 ELECTRICAL CODE, NFPA 110 AND NFPA 111.
  
 7.4.1 ROTATING ENERGY CONVERTERS SHALL BE INSTALLED ON
 SOLID FOUNDATIONS TO PROHIBIT SAGGING OF FUEL, EXHAUST,
 OR LUBRICATING-OIL PIPING AND DAMAGE TO PARTS RESULTING
 IN LEAKAGE AT JOINTS.
  
 7.4.1.1 SUCH FOUNDATIONS OR STRUCTURAL BASES SHALL
 RAISE THE ENGINE AT LEAST 150 MM (6 IN.) ABOVE THE
 FLOOR OR GRADE LEVEL AND BE OF SUFFICIENT ELEVATION TO
 FACILITATE LUBRICATING-OIL DRAINAGE AND
 EASE OF MAINTENANCE.
  
 7.4.2 FOUNDATIONS SHALL BE OF THE SIZE (MASS) AND TYPE
 RECOMMENDED BY THE ENERGY CONVERTER MANUFACTURER.
  
 7.4.3 WHERE REQUIRED TO PREVENT TRANSMISSION OF
 VIBRATION DURING OPERATION, THE FOUNDATION SHALL BE
 ISOLATED FROM THE SURROUNDING FLOOR OR OTHER
 FOUNDATIONS, OR BOTH, IN ACCORDANCE WITH THE
 MANUFACTURER'S RECOMMENDATIONS AND ACCEPTED STRUCTURAL
 ENGINEERING PRACTICES.
  
 7.4.4 THE EPS SHALL BE MOUNTED ON A FABRICATED METAL
 SKID BASE OF THE TYPE THAT SHALL RESIST DAMAGE DURING
 SHIPPING AND HANDLING. AFTER INSTALLATION, THE BASE
 SHALL MAINTAIN ALIGNMENT OF THE UNIT DURING OPERATION.
 PLANS DO NOT PROVIDE INFORMATION FOR SECONDARY
 CONTAINMENT. NFPA 110: 7.9.12 LISTED GENERATOR SUBBASE
 SECONDARY CONTAINMENT FUEL TANKS OF 2498 L (660 GAL)
 CAPACITY AND BELOW SHALL BE PERMITTED TO BE INSTALLED
 OUTDOORS OR INDOORS WITHOUT DIKING OR REMOTE
 IMPOUNDING.
  
 2) MISSING WIND DESIGN CRITERIA:
 1609.6.2 WIND DESIGN PROCEDURES
 1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-09-17 Cont ID  
Sent By lmartine Date 2010-09-17 Time 11:31 Rev Time 0.00
Received By lmartine Date 2010-09-17 Time 11:31 Sent To  
Notes
2010-09-17 11:32:25SEE PLANS FOR JAKE'S STAMP AND SIGNATURE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-08-18 Cont ID  
Sent By jleahy Date 2010-08-18 Time 16:24 Rev Time 0.00
Received By jleahy Date 2010-08-18 Time 16:24 Sent To  
Notes
2010-08-18 16:25:08NO RISER DIAGRAM
  
 NO LOAD CALCULATION
  
 NO PANEL SCHEDULE(S)

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-10-22 Cont ID  
Sent By mcarsill Date 2010-10-22 Time 09:10 Rev Time 0.00
Received By mcarsill Date 2010-10-21 Time 14:21 Sent To  
Notes
2010-10-22 09:11:42RECEIVED ELECTRONIC MAIL FROM KNIGHT ELECTRIC
 ADDRESSING PREVIOUS FIRE COMMENTS.
  
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-08-24 Cont ID  
Sent By mcarsill Date 2010-08-24 Time 12:28 Rev Time 0.00
Received By mcarsill Date 2010-08-24 Time 12:10 Sent To  
Notes
2010-08-24 12:28:502139 PALM BEACH LAKES BOULEVARD
 PERMIT NUMBER 10080159
 "PROVIDE 175KW DIESEL GENERATOR SET AND ATS"
  
  
 1. THE GENERATOR AND FUEL TANK SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 30 AND NFPA 37. NO NOTES ON THE
 PLANS SEEM TO REFLECT THESE CODE REQUIREMENTS.
  
 2. NO WARNING SIGNS OR APPROPRIATE LABELING OBSERVED
 FOR THE STORAGE AND USE OF THE DIESEL FUEL. NO NFPA 704
 DIAMOND ILLUSTRATED FOR THE HAZARDS OF THE DIESEL FUEL.
  
 3. PLEASE ILLUSTRATE THE REQUIRED SETBACKS REQUIRED FOR
 THE DIESEL FUEL STORAGE TANK FROM OTHER PROPERTIES AND
 IMPORTANT BUILDINGS.
  
 4. PLEASE DESCRIBE WHAT EQUIPMENT THE GENERATOR WILL
 PROVIDE POWER FOR. DOES THE GENERATOR PROVIDE POWER TO
 NORMAL OR EMERGENCY SYSTEMS AND EQUIPMENT.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2010-08-11 Cont ID  
Sent By lwagner Date 2010-08-11 Time 11:28 Rev Time 0.00
Received By lwagner Date 2010-08-11 Time 11:26 Sent To  
Notes
2010-08-11 11:29:46DIESEL GENERATOR

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-04 Cont ID  
Sent By lmartine Date 2010-10-04 Time 10:59 Rev Time 0.00
Received By lmartine Date 2010-10-04 Time 10:59 Sent To  
Notes
2010-10-04 11:00:52C--14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-10-04 Cont ID  
Sent By lmartine Date 2010-09-17 Time 10:58 Rev Time 0.00
Received By lmartine Date 2010-08-10 Time 15:47 Sent To  
Notes
2010-08-10 15:49:58SENT TO C-16

Review Stop P PLUMBING
Rev No 1 Status N Date 2010-08-11 Cont ID  
Sent By lwagner Date 2010-08-11 Time 11:26 Rev Time 0.00
Received By lwagner Date 2010-08-11 Time 11:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2010-10-14 Cont ID  
Sent By jroach Date 2010-10-14 Time 09:50 Rev Time 0.00
Received By jroach Date 2010-10-14 Time 09:50 Sent To  
Notes
2010-10-14 09:51:05ZONING PLAN REVIEW
  
 DATE OF REVIEW: 10/14/10
 PERMIT NO.: 10080159
 ADDRESS: 2139 PALM BEACH LAKES BOULEVARD
 CONTRACTOR/CONTACT: JOAN FORD
 TELEPHONE NO.: 561.689.3500
 SCOPE OF REVIEW: GENERATOR
  
 REVIEW STATUS: PASSED WITH PROVISOS
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1) NO LANDSCAPING SHALL BE REMOVED AS PART OF THE
 INSTALLATION OF THE GENERATOR.
  
 2) PRIOR TO FINAL INSPECTION, A SEPARATE PERMIT
 APPLICATIONS SHALL BE SUBMITTED FOR THE REQUIRED
 ENCLOSURE AND LANDSCAPING. SUCH IMPROVEMENTS SHALL BE
 INSTALLED PRIOR TO ISSUANCE OF A CERTIFICATE OF
 COMPLETION.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-09-01 Cont ID  
Sent By jroach Date 2010-09-01 Time 09:40 Rev Time 0.00
Received By jroach Date 2010-09-01 Time 09:40 Sent To  
Notes
2010-09-01 09:53:34ZONING PLAN REVIEW
  
 PERMIT NO.: 10080159
 ADDRESS: 2139 PALM BEACH LAKES BLVD.
 CONTRACTOR/CONTACT: PHILLIP KNIGHT
 TELEPHONE NO.: 561.689.3500
 SCOPE OF REVIEW: DIESEL GENERATOR
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) PURSUANT TO SECTION 94-443(B) OF THE CITY???S ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDRS),
 NONRESIDENTIAL USES SHALL PROVIDE A FIVE (5) FOOT WIDE
 LANDSCAPE BUFFER ALONG THE ENTIRE PROPERTY LINE.
 THEREFORE, THE GENERATOR (AND REQUIRED SCREENING, AS
 DESCRIBED BELOW) SHALL NOT ENCROACH INTO THE REQUIRED
 BUFFER.
  
 2) PURSUANT TO SECTION 94-444(B) OF THE CITY???S ZLDRS,
 GENERATORS SHALL NOT BE PERMITTED UNLESS APPROPRIATE
 SCREENING IS PROVIDED. SCREENING SHALL BE CONSTRUCTED
 OF BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE
 MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL. THE
 SCREENING SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO (2) FOOT INTERVALS. PLEASE NOTE, THE
 SCREENING SHALL COMPLETELY OBSCURE THE GENERATOR.
 THEREFORE, BE SURE THAT THE PROPOSED FENCE/WALL IS OF
 SUFFICIENT HEIGHT (85???).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  