| 2010-08-12 13:35:40 | BUILDING PLAN REVIEW |
| | PERMIT: 10080137 |
| | ADD: 411 51ST ST |
| | CONT: CHECKMATE HOMES SERVICES |
| | TEL: (561)602-2465 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) R01.2.1.4 EXPOSUEW CATEGORY, SHEET A INDICATES THIS |
| | TO BE A "B" EXPOSURE, PLEASE REVIEW THE TYPE "C" |
| | EXPOSURE, THIS STRUCTURE IS LOCATED IN A "C" EXPOSURE. |
| | |
| | 2) WITH THE "C" EXPOSURE PLEASE PROVIDE THE POSITIVE & |
| | NEGATIVE PRESSURES ASSOCIATED WITH THIS EXPOSURE |
| | (MULTIPLIER OF 1.15). PLEASE PROVIDE THE PRESSURES FOR |
| | THE INTERIOR ZONES AS WELL AS THE CORNER ZONES. TABLE |
| | R301.2(2) & TABLE R301.2(3). |
| | |
| | 3) THE PLANS INDICATE A STRAPPING DETAIL FOR A TYPICAL |
| | WINDOW BUT DO NOT PROVIDE THE STRAPPING FOR THE 12'-0" |
| | WIDE OPENING. THE OTHER ISSUE WITH THIS OPENING IS THE |
| | AMOUNT OF FULL LENGTH STUDS AND JACK STUDS THAT ARE |
| | REQUIRED, THE PLANS DO NOT FEFLECT AN ACCURATE CORNER |
| | AND CONNECTION TO THE MWFRS. |
| | |
| | 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5) THE LAWSON WINDOWS SUBMITTED NOA: 09-0720.05 ARE A |
| | NON-IMPACT UNIT THAT WILL REQUIRE STORM SHUTTERS. |
| | PLEASE SUBMIT THE SHUTTER PRODUCT APPROVAL WITH THE |
| | FOLOWING: |
| | PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| | SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND |
| | MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC |
| | 1609.1.4. |
| | FL BLD CODE 2004 SECTION 106.3.3, |
| | 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE |
| | SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS, |
| | UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR |
| | REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT |
| | TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT |
| | APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | PLEASE PROVIDE ANCHORING AND SYSTEM WHICH WILL ALLOW |
| | FOR THE REQUIRED SEPERATION FROM GLAZING TO SHUTTER |
| | SINCE THE WINDOWS ARE A FLANGE MOUNT TYPE WINDOW. |
| | |
| | 6) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| | REPORTS ARE AS FOLLOWS: |
| | 6A) STORM SHUTTERS OR PANELS RULE 9B-72(31) (E) |
| | |
| | 6B) ROOFING ASSEMBLIES RULE 9B-73(31) (D) |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |