Plan Review Details - Permit 10070762
Plan Review Stops For Permit 10070762
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2011-07-14 Cont ID  
Sent By rbrown Date 2011-07-14 Time 11:29 Rev Time 0.00
Received By rbrown Date 2011-07-14 Time 11:29 Sent To  
Notes
2011-07-14 11:32:59SOLAR STAR ATTIC FAN PRODUCT APPROVAL REVIEW ONLY:
  
 REVIEWED THE TEST REPORT SUBMITTED BY EMAIL 0N 7/13/11.
 THE DESIGN PRESSURE RATING OF +37.5 PSF / -82.5 PSF
 EXCEEDS THE CALCULATED DESIGN WIND PRESSURES FOR THE
 BUILDING AND LOCATION IN QUESTION. TEST REPORT IS
 CONSIDERED AS SUPPLEMENTARY INFORMATION TO GO WITH THE
 FLORIDA STATE PRODUCT APPROVAL THAT DOES NOT LIST A
 DESIGN PRESSURE RATING FOR THE PRODUCT.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2011-07-12 Cont ID  
Sent By rbrown Date 2011-07-12 Time 11:52 Rev Time 0.00
Received By rbrown Date 2011-07-12 Time 11:52 Sent To  
Notes
2011-07-12 11:58:30SOLAR STAR ATTIC FAN PRODUCT APPROVAL REVIEW ONLY:
  
 BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN (561) 805 6652
 E-MAIL: [email protected]
  
 REVIEWED PRODUCT APPROVAL DOCUMENTS SUBMITTED 6/28/11.
 PLEASE SUBMIT WIND PRESSURE TEST DATA AS REQUESTED IN
 THE FOLLOWING EMAIL SENT TO THE PRODUCT MANUFACTURER
 AND DISTRIBUTOR:
  
 I HAVE BEEN GIVEN A COPY OF YOUR EMAIL CORRESPONDENCE
 THAT STATES THAT THE SOLATUBE INTERNATIONAL, INC., 14"
 SOLAR STAR ATTIC FAN WILL BE UNDERGOING TESTING TO TEST
 APPLICATION STANDARD TAS 100(A) - 95 IN JULY 2011.
 PLEASE PROVIDE RESULTS FROM THOSE TESTS AS SOON AS
 POSSIBLE SO THAT WE CAN ISSUE A PERMIT BASED ON FLORIDA
 STATE PRODUCT APPROVAL # FL10884. THE PRODUCT HAS BEEN
 USED AT A PROPERTY HERE IN WEST PALM BEACH, FL, AND
 THERE IS NO JUSTIFICATION IN THE FLORIDA PRODUCT
 APPROVAL DOCUMENTATION OR ANY OTHER SOURCE TO SUPPORT
 ITS USE IN A RESIDENCE WHERE THE DESIGN WIND SPEED IS
 140 MPH (3 SECOND GUST) AND THE EXPOSURE CATEGORY IS C.
 WE NEED TO HAVE THE TAS 100(A) -95 TEST RESULTS OR SOME
 OTHER DOCUMENTATION SHOWING SUCCESSFUL TESTING FOR
 PRESSURES ASSOCIATED WITH A DESIGN WIND SPEED OF 140
 MPH (3 SECOND GUST), EXPOSURE CATEGORY C, IN TIME FOR A
 JULY 29 MAGISTRATE HEARING, OR THE PROPERTY OWNER'S
 WILL HAVE TO REQUEST AN EXTENSION WHICH MAY OR MAY NOT
 BE GRANTED BY THE MAGISTRATE.
  
 WE ACKNOWLEDGE AND ACCEPT THE FACT THAT THE PRODUCT IS
 COVERED BY FLORIDA STATE PRODUCT APPROVAL # FL10884. WE
 WILL PASS THE INSTALLATION PROVIDED WE CAN ESTABLISH
 THAT THE PRODUCT HAS BEEN TESTED TO A WIND DESIGN
 PRESSURE THAT EXCEEDS THAT WHICH IS CALCULATED FOR THE
 LOCATION AT WHICH THE PRODUCT IS INSTALLED. THE FLORIDA
 STATE PRODUCT APPROVAL # FL10884 DOES NOT STATE THE
 DESIGN WIND PRESSURE. THE SUPPORTING DOCUMENTATION FROM
 PAUL WINTER, P.E., AFFIRMS THAT THE PRODUCT WAS TESTED
 TO ASCE 7-02 AND THAT THE TESTING MEETS THE
 REQUIREMENTS OF THE CURRENT 2007 FLORIDA BUILDING CODE.
 HOWEVER THE WIND DESIGN WIND SPEEDS REQUIRED TO SHOW
 COMPLIANCE WITH THE REQUIREMENTS OF THE CURRENT 2007
 FLORIDA BUILDING CODE VARY BASED ON THE SIZE OF THE
 BUILDING AND ITS GEOGRAPHIC LOCATION IN THE STATE OF
 FLORIDA. A PRODUCT WHICH COMPLIES WHEN USED IN CENTRAL
 FLORIDA MAY NOT COMPLY WHEN USED IN COASTAL REGIONS.
 THE WEST PALM BEACH DESIGN WIND SPEED IS NOT QUITE AS
 HIGH AS MIAIMI-DADE BUT IT IS CLOSE AT 140 MPH.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2011-02-23 Cont ID  
Sent By jwitmer Date 2011-02-23 Time 09:26 Rev Time 0.77
Received By jwitmer Date 2011-02-15 Time 08:01 Sent To  
Notes
2011-02-23 10:03:41BUILDING PLAN REVIEW
 PERMIT: 10070762
 ADD: 8000 VIA VILLAGIO
 CONT: SDI SOLAR INC
 TEL: (561)722-3088
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 FEB. 23/ 2011
 ACTION: DENIED
  
 1) THE SOLAR ROOF POWERED ROOF VENTILATION FAN DOES
 HAVE A CURRENT FLORIDA APPROVAL UNDER THE 2007 FBC. THE
 SUBMITTAL THAT IS REFRENECING THE 14 INCH SOLAR STAR
 VENT AND LETTER OF EQIVALENCY REFRENCES THE ORIGINAL
 TEST WHICH EAS CONDUCTED UNDER 110 FASTEST MILE. IN
 2001
 WE USED ASCE7 98 110 FASTEST MILE. THE 2004 FBC THEN
 WENT TO ASCE 7-02 WHICH WAS A 3 SECOND GUST AND WIND
 SPEED OF 140 MPH.
 2004 FBC-B TABLE 1609.3.1 PROVIDES THE EQUIVALENT WIND
 SPEEDS BETWEEN V3S & VFM. FOR OUR WIND SPEED ZONE OF
 140 MPH (3 SECOND GUST) THE EQUIVALENT VFM WOULD BE
 120, NOT 140. THIS UNIT DOES HAVE A FLORIDA APPROVAL
 BUT SHOULD NOT BE PERMITTED NAD INSTALLED WHERE THE
 WIND SPEEDS ARE GREATER THAN 120 3S GUST.
  
 I SPOKE WITH OUR ASST. BUILDING OFFICIAL AND NO LOCAL
 APROVAL CAN BE APPLIED FOR UNLESS AN ENGINEER WILL
 PROVIDE DOCUMENTATION WHERE THE MODEL IN QUESTION CAN
 PRODUCE DOCUMENTATION FOR COMPLIANCE WITH 140 3 SECOND
 GUST. PLEASE ALSO NOTE THIS LOCATION IS A "C" ZONE
 AND THE MEAN ROOF HEIGHT IS ABOVE 15'-0" PLEASE REVIEW
 MULTIPLIERS FOR EXPOSURE AND HEIGHT.
  
  
 FROM 1ST REVIEW! THE FL 10884 REPORT SUBMITTED FOR A
 SOLAR POWERED ROOF VENTILATION FAN DOES NOT INDICATE
 ANY WIND DESIGN CRITERIA BUT REFERS TO A MIAMI-DADE
 TEST REPORT 51567.01-122-18 THAT WAS COMPLETED UNDER
 THE 2001 VERSION OF THE FLORIDA BUILDING CODE AND TEST
 WAS FOR PRESSURES OF 110 MPH FASTEST MILE. THE 2004 &
 2007 FBC USE A 3 SECOND GUST CONVERSION CHARTS WOULD
 MAKE THE 110 FASTEST MILE, 130 MPH 3 SECOND GUST.THE
 CITY OF WEST PALM BEACH IS LOCATED WITHIN A 140 MPH
 WIND ZONE. THIS PRODUCT WILL NEED TO BE RE-EVALUATED TO
 THE 140 MPH WIND ZONE, AND FIGURE IN THE HEIGHT AND
 EXPOSURE ADJUTMENT FACTORS.
 R301.1.2.1 WIND LIMITATIONS.
 R301.2.1.1 WIND DESIGN CRITERIA
 R301.1.2.1.3 WIND SPEED CONVERSION
 R301.2.1.4 EXPOSURE CATEGORY
 R301.2.1.5 BASIC WIND SPEED
  
 SECOND REVIEW THE SAME ITEMS OUTSTANDING.
 2) SDI SOLAR HEATER PANEL:
 2.1) PLEASE PROVIDE THE ACTUAL PANEL SIZE IN SQ FT
 2.2 PLEASE PROVIDE THE ACTUAL MEAN ROOF HEIGHT IN FT.
 2.3 PLEASE PROVIDE THE ACTUAL ROOF PITCH AND CIRCLE
 WHICH INSTALATION METHOD TO BE USED.
  
 IN A WORSE CASE SCENERIO;
 20 SQ FT AREA / LOCATED IN A ZONE TWO
 EXPOSURE "C"
 ROOF MEAN ROOF HEIGHT OF 35'
  
 -51.7X1.45= -74.96 PSF
  
 3/8" LAG SCREWS (FASTENER) @ 48 SQ FT
 74.96X 48 SQ FT= 3598/4= 899.52LBS PULL OUT PER
 FASTENER
 PLEASE PROVIDE DOCUMENTATION ON THE FASTENER FOR THE
 PULL OUT STRENGTH
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-11-30 Cont ID  
Sent By jwitmer Date 2010-11-30 Time 10:01 Rev Time 0.55
Received By jwitmer Date 2010-11-30 Time 10:01 Sent To  
Notes
2010-11-30 10:15:59BUILDING PLAN REVIEW
 PERMIT: 10070762
 ADD: 8000 VIA VILLAGIO
 CONT: SDI SOLAR INC
 TEL: (561)722-3088
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) THE SOLAR ROOF POWERED ROOF VENTILATION FAN DOES NOT
 HAVE A CURRENT FLORIDA APPROVAL UNDER THE 2007 FBC. THE
 SUBMITTAL THAT IS REFRENECING THE 14 INCH SOLAR STAR
 VENT AND LETTER OF EQIVALENCY WILL REQUIRE EITHER
 APPLICATION TO THE STATE UNDER RULE 9B-72 (1)(D) OR
 SUBMITTAL TO THE CITY FOR A LOCAL APPROVAL. THE CITY OF
 WEST PALM BEACH REQUIRES THE SAME TEN CRITERIA AS THE
 STATE FOR A LOCAL APPROVAL, TO BE SUBMITTED TO ASSITANT
 BUILDING OFFICIAL ROBERT BROWN TO BE REVIEWED.
  
  
 FROM 1ST REVIEW! THE FL 10884 REPORT SUBMITTED FOR A
 SOLAR POWERED ROOF VENTILATION FAN DOES NOT INDICATE
 ANY WIND DESIGN CRITERIA BUT REFERS TO A MIAMI-DADE
 TEST REPORT 51567.01-122-18 THAT WAS COMPLETED UNDER
 THE 2001 VERSION OF THE FLORIDA BUILDING CODE AND TEST
 WAS FOR PRESSURES OF 110 MPH FASTEST MILE. THE 2004 &
 2007 FBC USE A 3 SECOND GUST CONVERSION CHARTS WOULD
 MAKE THE 110 FASTEST MILE, 130 MPH 3 SECOND GUST.THE
 CITY OF WEST PALM BEACH IS LOCATED WITHIN A 140 MPH
 WIND ZONE. THIS PRODUCT WILL NEED TO BE RE-EVALUATED TO
 THE 140 MPH WIND ZONE, AND FIGURE IN THE HEIGHT AND
 EXPOSURE ADJUTMENT FACTORS.
 R301.1.2.1 WIND LIMITATIONS.
 R301.2.1.1 WIND DESIGN CRITERIA
 R301.1.2.1.3 WIND SPEED CONVERSION
 R301.2.1.4 EXPOSURE CATEGORY
 R301.2.1.5 BASIC WIND SPEED
  
 SECOND REVIEW THE SAME ITEMS OUTSTANDING.
 2) SDI SOLAR HEATER PANEL:
 2.1) PLEASE PROVIDE THE ACTUAL PANEL SIZE IN SQ FT
 2.2 PLEASE PROVIDE THE ACTUAL MEAN ROOF HEIGHT IN FT.
 2.3 PLEASE PROVIDE THE ACTUAL ROOF PITCH AND CIRCLE
 WHICH INSTALATION METHOD TO BE USED.
  
 IN A WORSE CASE SCENERIO;
 20 SQ FT AREA / LOCATED IN A ZONE TWO
 EXPOSURE "C"
 ROOF MEAN ROOF HEIGHT OF 35'
  
 -51.7X1.45= -74.96 PSF
  
 3/8" LAG SCREWS (FASTENER) @ 48 SQ FT
 74.96X 48 SQ FT= 3598/4= 899.52LBS PULL OUT PER
 FASTENER
 PLEASE PROVIDE DOCUMENTATION ON THE FASTENER FOR THE
 PULL OUT STRENGTH
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-08-24 Cont ID  
Sent By jwitmer Date 2010-08-24 Time 10:33 Rev Time 1.22
Received By jwitmer Date 2010-08-24 Time 10:33 Sent To  
Notes
2010-08-24 13:16:00BUILDING PLAN REVIEW
 PERMIT: 10070762
 ADD: 8000 VIA VILLAGIO
 CONT: SDI SOLAR INC
 TEL: (561)722-3088
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE FL 10884 REPORT SUBMITTED FOR A SOLAR POWERED
 ROOF VENTILATION FAN DOES NOT INDICATE ANY WIND DESIGN
 CRITERIA BUT REFERS TO A MIAMI-DADE TEST REPORT
 51567.01-122-18 THAT WAS COMPLETED UNDER THE 2001
 VERSION OF THE FLORIDA BUILDING CODE AND TEST WAS FOR
 PRESSURES OF 110 MPH FASTEST MILE. THE 2004 & 2007 FBC
 USE A 3 SECOND GUST CONVERSION CHARTS WOULD MAKE THE
 110 FASTEST MILE, 130 MPH 3 SECOND GUST.THE CITY OF
 WEST PALM BEACH IS LOCATED WITHIN A 140 MPH WIND ZONE.
 THIS PRODUCT WILL NEED TO BE RE-EVALUATED TO THE 140
 MPH WIND ZONE, AND FIGURE IN THE HEIGHT AND EXPOSURE
 ADJUTMENT FACTORS.
 R301.1.2.1 WIND LIMITATIONS.
 R301.2.1.1 WIND DESIGN CRITERIA
 R301.1.2.1.3 WIND SPEED CONVERSION
 R301.2.1.4 EXPOSURE CATEGORY
 R301.2.1.5 BASIC WIND SPEED
  
  
 2) SDI SOLAR HEATER PANEL:
 2.1) PLEASE PROVIDE THE ACTUAL PANEL SIZE IN SQ FT
 2.2 PLEASE PROVIDE THE ACTUAL MEAN ROOF HEIGHT IN FT.
 2.3 PLEASE PROVIDE THE ACTUAL ROOF PITCH AND CIRCLE
 WHICH INSTALATION METHOD TO BE USED.
  
 IN A WORSE CASE SCENERIO;
 20 SQ FT AREA / LOCATED IN A ZONE TWO
 EXPOSURE "C"
 ROOF MEAN ROOF HEIGHT OF 35'
  
 -51.7X1.45= -74.96 PSF
  
 3/8" LAG SCREWS (FASTENER) @ 48 SQ FT
 74.96X 48 SQ FT= 3598/4= 899.52LBS PULL OUT PER
 FASTENER
 PLEASE PROVIDE DOCUMENTATION ON THE FASTENER FOR THE
 PULL OUT STRENGTH
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-11-30 Cont ID  
Sent By rmcdouga Date 2010-11-30 Time 08:00 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2010-11-30 08:02:44TO J WITMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-29 Cont ID  
Sent By rmcdouga Date 2010-07-29 Time 08:32 Rev Time 0.00
Received By rmcdouga Date 2010-07-29 Time 08:32 Sent To  
Notes
2010-07-29 08:32:51SENT TO ZONING

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-08-24 Cont ID  
Sent By jwitmer Date 2010-08-24 Time 13:16 Rev Time 0.20
Received By jwitmer Date 2010-08-24 Time 13:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-08-06 Cont ID  
Sent By lfranco Date 2010-08-06 Time 16:17 Rev Time 0.00
Received By lfranco Date 2010-07-29 Time 15:12 Sent To B
Notes
***NONE***