Plan Review Details - Permit 10070718
Plan Review Stops For Permit 10070718
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-08-17 Cont ID  
Sent By jwitmer Date 2010-08-17 Time 13:42 Rev Time 1.35
Received By jwitmer Date 2010-08-17 Time 13:42 Sent To  
Notes
2010-08-17 13:57:35BUILDING PLAN REVIEW
 PERMIT: 10070718
 ADD: 1177 CLARE AVE
 CONT: A K CONSTRUCTION & REMODELING
 TEL: (561)239-1852
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE SCOPE OF WORK HAS INCREASED FROM THE EXPIRED
 PERMIT 06082252, THE PLANS CURRENTLY INDICATE WORK
 BEING COMPLETED WITHIN EACH OF THE TENANT SPACES PLEASE
 UPDATE THE VALUE OF SCOPE OF PERMIT.
  
 2) PLEASE CORRECT THTE ADDRESS (1156 ELIZABETH AVE) AND
 PROPERTY CONTROL NUMBER (74-43-43-28-09-007-0250) ON
 THE PERMIT APPLICATION IF THE WHOLE COMPLEX IS BEING
 PERMITED. THE WRONG PCN IS ON THE PERMIT APPLICATION
 THIS WILL NEED TO BE CORRECTED REGARDLESS OF SCOPE OF
 WORK.
  
 3) MANY OF THE TENANT SPACES INDICATE WAREHOUSE, PLEASE
 PROVIDE A OCCUPANCY TYPE, THE DESCRIPTION WAREHOUSE
 COULD BE TAKEN AS A S-1, S-2, F-1 OR F-2 OCCUPANCY
 PLEASE REVIEW
 TABLE 508.3.3 FOR OCCUPANCY SEPERATION REQUIREMENTS
 WALL TYPE IN HOURS. THE CHANGE OF OCCUPANCY BETWEEN
 TTHTE MERCANTILE / S-2 OCCUPANCIES WILL REQUIRE 2 HR
 SEPERATION WALL.
 DEPENDING ON THE S-1 AND S-2 OCCUPANCIES THERE WOULD
 ALSO BE 2 HR SEPERATION REQUIRED.
  
 3) IN BOTH RETAIL (MERCANTILE) SPACES PLEASE PROVIDE
 THE LIFE SAFETY PLAN WITH KIOSK, COUNTERS, ETC TO
 INDICATE PATH OF TRAVEL. IT APPEARS IN SUITE # 7 THE
 COMMON PATH OF TRAVEL OF TRAVEL OF 75 FEET IS EXCEEDED
 SEE SECTION 1014.3 & TABLE 1019.2.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-08-09 Cont ID  
Sent By lmartine Date 2010-08-09 Time 16:06 Rev Time  
Received By lmartine Date 2010-08-09 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-07-29 Cont ID  
Sent By wjolin Date 2010-07-29 Time 13:34 Rev Time 0.00
Received By wjolin Date 2010-07-29 Time 12:34 Sent To  
Notes
2010-07-29 13:34:10*****DENIED*****
  
 NOTE: SCOPE OF WORK HAS INCREASED FROM ORIGINAL EXPIRED
 PERMIT #06082252. ORIGINAL DESIGN APPEARS TO BE VALID
 FOR ONLY SUITE #6 AND SUITE #7. INCREASED VALUE MAY NOT
 BE ACCURATE. INCREASED SCOPE MAY REQUIRE NEW SIGN/SEAL.
  
 SHEET A-3
 1) MERCANTILE OCCUPANCIES REQUIRE 2-HOUR SEPARATION
 FROM STORAGE OCCUPANCIES (REFERENCE NFPA 101, TABLE
 6.1.14.4.1B).
  
 2) MERCANTILE OCCUPANCIES (SUITE # 7) REQUIRE TWO EXITS
 WHEN THE TRAVEL DISTANCE TO AN EXIT EXCEEDS 75 FEET
 (REFERENCE NFPA 101, SECTION 37.2.4.3).
  
 3) STORAGE OCCUPANCIES REQUIRE TWO EXITS WHEN THE
 TRAVEL DISTANCE TO AN EXIT EXCEEDS 50 FEET (REFERENCE
 NFPA 101, SECTION 42.2.4.1(2) AND TABLE 42.2.5).
  
 4) PROVIDE ADDRESS SUITE NUMBERS AT LEAST SIX-INCHES IN
 HEIGHT AND PLACED IN A VISIBLE LOCATION FROM THE ROAD
 (REFERENCE NFPA 1, SECTION 10.12.1.2).
  
 5) PROVIDE PORTABLE FIRE EXTINGUISHERS PER NFPA 10.
  
 6) FIRE RATED WALLS, PARTITIONS ETC. SHALL BE
 IDENTIFIED WITH SIGNS OR STENCILING READING "FIRE
 BARRIER-PROTECT ALL OPENINGS" OR SIMILAR LANGUAGE.
 LETTERING SHALL BE IN 4-INCHES HIGH, 1/2-INCH STROKE,
 AND SPACED NOT MORE THAN 15-FEET ON-CENTER (REFERENCE
 NFPA 101, SECTION 8.3.2.4).
  
 7) PROVIDE MECHANICAL DUCT DAMPER LOCATIONS IF
 APPLICABLE.
  
 SHEET E-1
 1) PROVIDE EMERGENCY LIGHTING FOR WEST AREA OF SUITE
 #2.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-07 Cont ID  
Sent By jwitmer Date 2010-09-07 Time 07:48 Rev Time 0.00
Received By jwitmer Date 2010-07-28 Time 09:09 Sent To  
Notes
2010-07-28 09:09:45C 19
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-08-13 Cont ID  
Sent By hmoser Date 2010-08-13 Time 10:53 Rev Time 0.00
Received By hmoser Date 2010-08-13 Time 10:47 Sent To  
Notes
2010-08-13 10:54:05NO MECHANICAL REQUIRED .

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-08-05 Cont ID  
Sent By lwagner Date 2010-08-05 Time 13:59 Rev Time 0.00
Received By lwagner Date 2010-08-04 Time 10:53 Sent To  
Notes
2010-08-05 14:00:38FBC EXISTING BUILDING CODE 2007
 FBC PLUMBING 2007

Review Stop Z ZONING
Rev No 1 Status P Date 2010-09-07 Cont ID  
Sent By lfranco Date 2010-09-07 Time 10:15 Rev Time 0.00
Received By lfranco Date 2010-09-07 Time 10:15 Sent To  
Notes
***NONE***