Plan Review Details - Permit 10070707
Plan Review Stops For Permit 10070707
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-08-23 Cont ID  
Sent By shill Date 2010-08-23 Time 16:46 Rev Time 0.00
Received By shill Date 2010-08-23 Time 16:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-07-29 Cont ID  
Sent By shill Date 2010-07-29 Time 14:57 Rev Time 0.00
Received By shill Date 2010-07-29 Time 14:57 Sent To  
Notes
2010-07-29 15:00:15****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEE PAGE 11 OF THE PRODUCT APPROVAL, CONNECTION TYPE
 3 IS HIGHLIGHTED BUT THIS CONNECTION TYPE IS NOT
 PERMITTED IN MASONRY SUBSTRATE.
  
 2. PLEASE REVISE INSTALLATION SCHEDULE TO SPECIFY
 SHUTTER CONNECTION MOUNTING TYPE, WHICH SHOULD
 CORRELATE WITH THE ANCHOR CHARTS (FOR INSTANCE, 3 TOP).
  
 3. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL
 BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE,. FBC R301, FBC1609, FBC*106.
  
 3. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
 APPLICATION STATES IT IS THROUGH THE GARAGE, OVERHEAD
 GARAGE DOOR CANNOT BE THE EMERGENCY ESCAPE. PLEASE SHOW
 ENOUGH INFORMATION ON THE PLAN TO SHOW COMPLIANCE WITH
 FBCR310.4.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-05 Cont ID  
Sent By lmartine Date 2010-08-05 Time 14:22 Rev Time 0.00
Received By lmartine Date 2010-08-05 Time 14:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-29 Cont ID  
Sent By shill Date 2010-07-29 Time 15:00 Rev Time 0.00
Received By shill Date 2010-07-27 Time 16:05 Sent To  
Notes
2010-07-27 16:05:34TO BLDG <$5000
  