Plan Review Details - Permit 10070676
Plan Review Stops For Permit 10070676
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-08-19 Cont ID  
Sent By jwitmer Date 2010-08-19 Time 07:57 Rev Time 0.55
Received By jwitmer Date 2010-08-19 Time 07:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-07-29 Cont ID  
Sent By jwitmer Date 2010-07-29 Time 08:23 Rev Time 1.00
Received By jwitmer Date 2010-07-29 Time 08:23 Sent To FIRE
Notes
2010-07-29 08:47:36BUILDING PLAN REVIEW
 PERMIT: 10070676
 ADD: 901 45TH ST
 CONT: FREEDOM CONSTRUCTION
 TEL: (561)622-4400
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 JULY 29/2010
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS ONLY SHOW THE STAIRS AREA TO BE DEMOLISHED.
 PLEASE PROVIDE A EGRESS PLAN INDICATING THAT THESE
 STAIRS ARE NOT A REQUIRED EGRESS. FBC-B 1019.1 & TABLE
 1019.1. THE PLAN INDICATES THAT IT DOES NOT ALTER THE
 CURRENT EGRESS PATHWAYS PLEASE DEMONSTRATE THAT THE
 REMOVAL OF THIS STAIR WILL STILL MEET THE EGRESS
 REQUIREMENTS OF 1019.1 AND TRAVEL DISTANCES FOUND UNDER
 TABLE 1016.1.
  
 2) PLANS ARE FOR THE DEMOLISHION OF A STARWAY BUT ALSO
 TO BUILD WHAT APPEARS TO BE AN EXTERIOR WALL, PLEASE
 PROVIDE WIND DESIGN CRITERIA:
 1609.6.2 WIND DESIGN PROCEDURES
 2.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 3) PLANS FAIL TO IDENTIFY TO WHAT CODE THEY ARE BEING
 DESIGNED TO AND TO WHAT LEVEL OF ALTERATION THE EXTENT
 OF WORK WILL BE? 2007/2009 FLORIDA EXISTING BUILDING
 CODE 401.4.
  
 4) THE PLANS DO NOT INDICATE THE REMOVAL OF AN EXIT
 SIGN, THIS SHOULD ALSO BE INDICATED ON THE PLANS AND
 POSSIBILITY OF DIRECTIONAL SIGNAGE.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-08-17 Cont ID  
Sent By mcarsill Date 2010-08-17 Time 11:52 Rev Time 0.00
Received By mcarsill Date 2010-08-17 Time 11:28 Sent To  
Notes
2010-08-17 11:52:33ST. MARY'S HOSPITAL
 901-45TH STREET
 PERMIT NUMBER 10070676
  
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. PROPER VENTILATION IS REQUIRED IF GASOLINE POWERED
 CUTTING SAWS ARE USED TO PREVENT THE BUILD-UP OF CARBON
 MONOXIDE (CO) CARBON MONOXIDE IS A COLORLESS, ODORLESS,
 AND TASTELESS GAS THAT IS ALSO FLAMMABLE IN THE PROPER
 CONCENTRATION. PLEASE ENSURE THAT PROPER VENTILATION
 CONTROLS ARE IN PLACE.
  
 3. ALL EXITS ARE TO REMAIN CLEAR AND UNOBSTRUCTED WHILE
 WORK IS OCCURRING.
  
 4. ALL EXIT ACCESS IS TO REMAIN CLEAR AND UNOBSTRUCTED.
  
  
 APPROVED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-07-29 Cont ID  
Sent By mcarsill Date 2010-07-29 Time 10:23 Rev Time 0.00
Received By mcarsill Date 2010-07-29 Time 09:59 Sent To  
Notes
2010-07-29 10:22:47ST. MARY'S HOSPITAL
 901-45TH STREET
 PERMIT NUMBER 10070676
  
 1. PLANS ONLY ILLUSTRATE A PORTION OF THE IMPACTED
 FLOORS. HOW MANY REQUIRED AND NONREQUIRED EXITS ARE IN
 THESE LOCATIONS. IS THE STAIR PLANNING ON BEING
 DEMOLISHED A REQUIRED STAIR? WHAT IS THE EXIT CAPACITY
 OF THE STAIR BEING DEMOLISHED?
  
 2. PLEASE DELINEATE TRAVEL DISTANCES TO EXITS AND ANY
 DEAD-ENDS THAT CURRENTLY EXIST.
  
 3. PLEASE ILLUSTRATE ALL EXISTING EXIT SIGNS AND
 EMERGENCY LIGHTS ON THE FLOORS WHERE THE DEMOLITION IS
 PLANNED.
  
 4. PLEASE DOCUMENT OCCUPANT LOADS FOR THE FLOORS THAT
 ARE IMPACTED.
  
 5. PLEASE ILLUSTRATE ANY DIRECTIONAL EXIT SIGNS.
  
 6. WHAT FIRE PROTECTION EQUIPMENT IS CONTAINED WITHIN
 THE STAIRWELL THAT IS PLANNED FOR DEMOLITION. ARE ANY
 STANDPIPES, FIRE SPRINKLER LINES, FIRE ALARM EQUIPMENT,
 EMERGENCY LIGHTING, OR OTHER EQUIPMENT OR DEVICES
 PRESENT.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-15 Cont ID  
Sent By lmartine Date 2010-08-15 Time 10:29 Rev Time 0.00
Received By lmartine Date 2010-08-15 Time 10:28 Sent To  
Notes
2010-08-15 10:33:19IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-29 Cont ID  
Sent By mcarsill Date 2010-07-29 Time 10:23 Rev Time 0.00
Received By mcarsill Date 2010-07-27 Time 17:39 Sent To  
Notes
2010-07-27 17:39:33GAVE TO JIM