Plan Review Details - Permit 10070642
Plan Review Stops For Permit 10070642
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-07-28 Cont ID  
Sent By jgomez Date 2010-08-03 Time 09:50 Rev Time 0.00
Received By jgomez Date 2010-07-27 Time 16:06 Sent To  
Notes
2010-07-28 09:52:14BUILDING REVISION APPROVED WITH PROVISO:
  
 1- REVISE DESIGN PRESSURES ON SHEET S-1. DESIGN
 PRESSURES SHOWN ON THE 2 STORY SKETCH DON'T MATCH THE
 DESIGN PRESSURES SHOWN UNDER THE TWO STORY WORST CASE
 SCENARIO AND UNDER THE WIND PRESSURES SHOWN FOR THE TWO
 STORY EDGE AND INTERIOR ZONES. SEE COMMENTS ON SHEET
 S-1 SUBMITTED.
  
 2- PROVIDE COMPLETE STRUCTURAL DRAWINGS SHOWING
 HOISTWAY CONSTRUCTION TO SUPPORT THE ELEVATOR GUIDE
 RAILS. SEE ELEVATOR SPECIFICATIONS SUBMITTED ON
 7/29/10.
  
  
  
 ***REMAINDER***
  
 PROVIDE INFORMATION REQUESTED ON PROVISO DATED 7/01/10.
 SEE COPY BELOW.
  
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF TILE ADHESIVE. TITESET ROOFING ADHESIVE
 SUBMITTED IS NOT LISTED ON THE ROOF TILE NOA. NEED TO
 SHOW WHAT'S THE MIN. ATTACHMENT RESISTANCE TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.
  
 B) SEALOFLEX WATERPROOFING NOA 05-0901.04: ENGINEER
 NEEDS TO REVISE THE RAS 117 CALCULATIONS. THE MIN.
 FASTENER SEPARATION SHALL NOT BE LESS THAN 4"O.C. SEE
 SEC. 8.1 OF RAS 117.
  
 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 105.3.3 CITY AMENDMENTS TO
 FBC. THIS APPLIES TO PRODUCT APPROVALS THAT NEED TO BE
 RE-SUBMITTED.
  
 3- SHEET S1: REVISE DESIGN PRESSURES FOR WALL OPENINGS
 IN EXPOSURE "C". REVISE SKETCH FOR ONE STORY ALSO AND
 COORDINATE WITH DESIGN PRESSURES SHOWN AT BOTTOM OF
 PAGE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-08-04 Cont ID  
Sent By jwitmer Date 2010-08-04 Time 13:45 Rev Time 0.33
Received By jwitmer Date 2010-08-04 Time 13:45 Sent To  
Notes
2010-08-04 13:47:35SHEET E-1 REV # 2 THE ADDITION OF ELEVATOR 6720 MOTOR
 LOAD TOTAL AMPS 111 OF 125 AMP PANEL.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmartine Date 2010-07-26 Time 17:59 Sent To  
Notes
2010-07-26 18:00:16*****************EXPEDITED******************
 R--12

Review Stop Z ZONING
Rev No 1 Status P Date 2010-08-03 Cont ID  
Sent By lfranco Date 2010-08-02 Time 13:38 Rev Time 0.00
Received By lfranco Date 2010-08-02 Time 13:37 Sent To  
Notes
***NONE***