| Plan Review Stops For Permit 10070629 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2011-06-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2011-05-20 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2011-05-20 |
Time |
08:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2011-01-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2011-01-05 |
Time |
13:15 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2011-01-05 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2011-01-05 13:14:22 | BUILDING PLAN REVIEW | | | PERMIT: 10070629 | | | ADD: 315 FERN ST | | | CONT: HENSON DEV & CONST | | | TEL: (727)481-1180 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | JAN. 05/2011 | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | ***COMMENTS NOT ADDRESSED FROM 1ST REVIEW!!!!!! | | | | | | 1) PLEASE SUBMIT SURVEY OR SITE PLAN INDICATING THE | | | FRONT OF THE BUILDING, IT APPEARS THAT THE NEW | | | STOREFRONT LOCATION, THE FRONT DOOR MAY CROSS THE | | | PROPERTY LINE. | | | FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET | | | IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY | | | ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL | | | BE PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS | | | 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT | | | OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY. | | | | | | 2)SHEET A-1 OF PLANS DATED 8-4-10 REV.1 INDICATE A NEW | | | LOCATION FOR STOREFRONT APPROXIMATELY 3'-0" IN FRONT OF | | | THE OLD LOCATION SAAME AS THE FIRST SET OF PLANS. | | | NO COMMENTS FROM ARCHITECT BUT RESPONCE FROM ENGINEER | | | STATING NO NEW EQUIPMENT ON ROOF TOP. THERE WAS NO | | | COMMENT IN FIRST REVIEW THAT STATED NEW EQUIPMENT TO BE | | | INSTALLED ON THE ROOF TOP, BUT PLANS INDICATE A NEW | | | EXTERIOR SLAB FOR A WALK IN FREZZER AS WELL AS WIND | | | CALC REQUIREMENT FOR THE NEW STOREFRONT SYSTEM TO BE | | | INSTALLED. | | | | | | MISSING WIND DESIGN CRITERIA: | | | 1609.6.2 WIND DESIGN PROCEDURES | | | 2.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN | | | ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE | | | ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. | | | | | | 2.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN | | | ACCORDANCE WITH SECTION1609.5. | | | | | | 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN | | | ACCORDANCE WITH 1609.4. | | | | | | 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * | | | SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) | | | 2.5 PLEASE PROVIDE THE POSITIVE & NEGATIVE PRESSURES, | | | COMPONENTS AND CLADDING. | | | | | | 3A)1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS | | | REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE | | | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS | | | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF | | | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE | | | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES | | | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH | | | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS | | | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE | | | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. | | | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE | | | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. | | | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) | | | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL | | | MISSILE TEST. | | | | | | 3B) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING | | | REPORTS ARE AS FOLLOWS: | | | 3B)(1) STOREFRONT WINDOWS RULE 9B-72(31)(B) | | | 3B)(2) STOREFRONT DOOR (NOT COVERED UNDER MOST PRODUCT | | | APPROVALS) RULE 9B-72(31)(A) | | | 3B)(3) EXTERIOR WALK IN COOLER RULE 9B-72(31)(G) MAY BE | | | PART OF THIS PERMIT OR SEPERATE PERMIT, BUT THERE WILL | | | BE A OPENING IN THE EXTERIOR WALL WHERE THE COOLER IS | | | TO BE INSTALLED. | | | | | | 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE | | | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | JIM WITMER C. B. O. | | | COMMERCIAL COMBINATION PLAN REVIEW | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE | | | CUSTOMER SERVICE SURVEY AT: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2010-08-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-08-05 |
Time |
13:18 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2010-08-05 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2010-08-05 13:40:28 | BUILDING PLAN REVIEW | | | PERMIT: 10070629 | | | ADD: 315 FERN ST | | | CONT: HENSON DEV & CONST | | | TEL: (727)481-1180 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PLEASE SUBMIT SURVEY OR SITE PLAN INDICATING THE | | | FRONT OF THE BUILDING, IT APPEARS THAT THE NEW | | | STOREFRONT LOCATION, THE FRONT DOOR MAY CROSS THE | | | PROPERTY LINE. | | | FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET | | | IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY | | | ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL | | | BE PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS | | | 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT | | | OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY. | | | | | | 2) MISSING WIND DESIGN CRITERIA: | | | 1609.6.2 WIND DESIGN PROCEDURES | | | 2.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN | | | ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE | | | ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. | | | | | | 2.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN | | | ACCORDANCE WITH SECTION1609.5. | | | | | | 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN | | | ACCORDANCE WITH 1609.4. | | | | | | 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * | | | SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) | | | 2.5 PLEASE PROVIDE THE POSITIVE & NEGATIVE PRESSURES, | | | COMPONENTS AND CLADDING. | | | | | | 3A)1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS | | | REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE | | | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS | | | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF | | | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE | | | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES | | | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH | | | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS | | | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE | | | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. | | | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE | | | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. | | | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) | | | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL | | | MISSILE TEST. | | | | | | 3B) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING | | | REPORTS ARE AS FOLLOWS: | | | 3B)(1) STOREFRONT WINDOWS RULE 9B-72(31)(B) | | | 3B)(2) STOREFRONT DOOR (NOT COVERED UNDER MOST PRODUCT | | | APPROVALS) RULE 9B-72(31)(A) | | | 3B)(3) EXTERIOR WALK IN COOLER RULE 9B-72(31)(G) | | | | | | 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE | | | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | JIM WITMER C. B. O. | | | COMMERCIAL COMBINATION PLAN REVIEW | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE | | | CUSTOMER SERVICE SURVEY AT: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2010-12-28 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2010-12-28 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2010-12-28 |
Time |
14:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2010-08-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2010-08-17 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2010-08-17 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2010-08-17 08:22:33 | 1) NO ENERGY CALCULATION 13-415.B.1 , AND SPACE CONTROL | | | PER 13-415.AB.1.2 | | | | | | 2) SERVICE GROUNDING NOT PER CODE | | | | | | 3) EQUIPMENT GROUND FOR FEEDER NOT PER CODE | | | | | | 4) SEE 210.8 B 2 FOR GFCI REQUIREMENTS | | | | | | 5) CONFIRM AIC RATING BEFORE FIRST INSPECTION. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2010-12-30 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2010-12-30 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2010-12-30 |
Time |
14:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2010-07-29 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2010-07-29 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2010-07-29 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2010-07-29 17:16:47 | *****REVIEW COMMENTS - FIRE***** | | | | | | 1) SHEET A-2: RESTROOM DOOR SWING OBSTRUCTS ACCESS TO | | | REAR EXIT (NFPA 101, SECTION 7.2.1.4.4). | | | | | | 2) SHEET A-2: EQUIPMENT #60 (HOOD SUPPRESSION SYSTEM) | | | NOT FOUND ON FLOOR PLAN. SEPARATE PLANS AND PERMIT | | | REQUIRED FOR SUPPRESSION SYSTEM. | | | | | | 3) TYPE K PORTABLE FIRE EXTINGUISHER PROVIDED FOR | | | KITCHEN AREA; PROVIDE 2A-10BC EXTINGUISHER FOR | | | NON-KITCHEN SPACE. | | | | | | 4) SHEET A-4: PROVIDE BUILDING ADDRESS NUMBERS AT LEAST | | | SIX-INCHES IN HEIGHT ON BUILDING SO NUMERALS ARE | | | VISIBLE FROM THE ROAD FRONTING THE PROPERTY (NFPA 1, | | | SECTION 10.12.1). | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | & WESLEY JOLIN | | | FIRE PLAN REVIEW | | | 561-805-6730 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2010-12-27 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2010-12-27 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2010-12-27 |
Time |
10:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2010-08-04 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2010-08-04 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2010-08-04 |
Time |
09:27 |
Sent To |
|
|
| Notes |
| 2010-08-04 09:36:03 | FUEL GAS PLAN REVIEW #1 | | | DENIED: | | | | | | 1.PLEASE SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS | | | ALL CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | | FBC-2007 FUEL GAS. | | | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. 9. | | | RISER DIAGRAM/SHUTOFFS | | | | | | 2. BTU LOAD AND PIPE SIZE FOR WATER HEATER IS NOT SHOWN | | | ON PLAN. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2011-06-24 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2011-06-24 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2011-05-20 |
Time |
09:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2010-12-20 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-12-20 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-12-20 |
Time |
16:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-12-20 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-08-17 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-07-26 |
Time |
16:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
4 |
Status |
P |
Date |
2011-06-24 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2011-06-24 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2011-06-24 |
Time |
13:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
F |
Date |
2011-06-15 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2011-06-15 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2011-06-15 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2011-06-15 16:56:07 | | | | ***LANDSCAPE REVIEW FAILED*** | | | | | | PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT. | | | | | | 1. REPEAT COMMENT: PURSUANT TO SECTION 94-441(C)(2) OF | | | THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR): AS | | | THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF THE | | | STRUCTURE'S VALUE (LISTED AS "IMPROVEMENT VALUE" WITH | | | THE P.B.C. PROPERTY APPRAISER'S OFFICE), LANDSCAPING | | | SHALL BE IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS | | | FOUND IN ARTICLE XIV OF THE ZLDR. THE PERMITS IN PLACE | | | AT THIS TIME EQUAL $39,100 AND THE IMPROVEMENT VALUE IS | | | $64,372. | | | | | | 2.REPEAT COMMENT: LANDSCAPING REQUIRES A SEPARATE | | | PERMIT. PLEASE APPLY FOR A LANDSCAPE PERMIT AND SUBMIT | | | TWO COPIES OF A COMPLETE LANDSCAPE PLAN SHOWING | | | COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF THE | | | ZONING AND LAND DEVELOPMENT REGULATIONS. IT SHALL BE | | | SIGNED AND SEALED BY A REGISTERED LANDSCAPE ARCHITECT. | | | A CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST | | | OF ALL LANDSCAPE MATERIALS AND LABOR. IT SHALL BE | | | BROKEN DOWN INTO UNIT COST. | | | | | | 3. REPEAT COMMENT: PLEASE PROVIDE THE TABULATION | | | NECESSARY FOR THE EVALUATION OF COMPLIANCE WITH ARTICLE | | | XIV OF THE ZONING AND LAND DEVELOPMENT REGULATIONS, | | | INCLUDING THE XERISCAPE DESIGN OPTIONS. | | | | | | 4. REPEAT COMMENT: PURSUANT TO SECTION 94-448 (D) (2), | | | THE LANDSCAPE PLAN SHALL CONTAIN ALL OF THE ITEMS | | | ENUMERATED IN THIS SECTION. | | | | | | 4. REPEAT COMMENT: AN IRRIGATION PERMIT IS REQUIRED. | | | PLEASE SUBMIT TWO (2) COPIES OF AN IRRIGATION PLAN THAT | | | PROVIDES 120% COVERAGE TO ALL LANDSCAPED AREAS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462. |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
2010-12-21 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2010-12-21 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2010-12-21 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2010-12-21 11:49:44 | ***LANDSCAPE REVIEW FAILED*** | | | | | | PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT. | | | | | | 1. REPEAT COMMENT: PURSUANT TO SECTION 94-441(C)(2) OF | | | THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR): AS | | | THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF THE | | | STRUCTURE'S VALUE (LISTED AS "IMPROVEMENT VALUE" WITH | | | THE P.B.C. PROPERTY APPRAISER'S OFFICE), LANDSCAPING | | | SHALL BE IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS | | | FOUND IN ARTICLE XIV OF THE ZLDR. | | | | | | 2.REPEAT COMMENT: LANDSCAPING REQUIRES A SEPARATE | | | PERMIT. PLEASE APPLY FOR A LANDSCAPE PERMIT AND SUBMIT | | | TWO COPIES OF A COMPLETE LANDSCAPE PLAN SHOWING | | | COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF THE | | | ZONING AND LAND DEVELOPMENT REGULATIONS. IT SHALL BE | | | SIGNED AND SEALED BY A REGISTERED LANDSCAPE ARCHITECT. | | | A CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST | | | OF ALL LANDSCAPE MATERIALS AND LABOR. IT SHALL BE | | | BROKEN DOWN INTO UNIT COST. | | | | | | 3. REPEAT COMMENT: PLEASE PROVIDE THE TABULATION | | | NECESSARY FOR THE EVALUATION OF COMPLIANCE WITH ARTICLE | | | XIV OF THE ZONING AND LAND DEVELOPMENT REGULATIONS, | | | INCLUDING THE XERISCAPE DESIGN OPTIONS. | | | | | | 4. REPEAT COMMENT: PURSUANT TO SECTION 94-448 (D) (2), | | | THE LANDSCAPE PLAN SHALL CONTAIN ALL OF THE ITEMS | | | ENUMERATED IN THIS SECTION. | | | | | | 4. REPEAT COMMENT: AN IRRIGATION PERMIT IS REQUIRED. | | | PLEASE SUBMIT TWO (2) COPIES OF AN IRRIGATION PLAN THAT | | | PROVIDES 120% COVERAGE TO ALL LANDSCAPED AREAS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
2010-08-06 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2010-08-06 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2010-08-06 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2010-08-06 15:24:03 | ***LANDSCAPE REVIEW FAILED*** | | | | | | PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT. | | | | | | 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF | | | THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE | | | (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE | | | WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF | | | THE ZLDR. | | | | | | 2. LANDSCAPING REQUIRES A SEPARATE PERMIT. PLEASE APPLY | | | FOR A LANDSCAPE PERMIT AND SUBMIT TWO COPIES OF A | | | COMPLETE LANDSCAPE PLAN SHOWING COMPLIANCE WITH | | | SECTIONS 94-442 AND 94-445 OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS. IT SHALL BE SIGNED AND SEALED | | | BY A REGISTERED LANDSCAPE ARCHITECT. A CERTIFIED COST | | | ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE | | | MATERIALS AND LABOR. IT SHALL BE BROKEN DOWN INTO UNIT | | | COST. | | | | | | 3. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE | | | EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING | | | AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE | | | XERISCAPE DESIGN OPTIONS. | | | | | | 4. PURSUANT TO SECTION 94-448 (D) (2), THE LANDSCAPE | | | PLAN SHALL CONTAIN ALL OF THE ITEMS ENUMERATED IN THIS | | | SECTION. | | | | | | 4. AN IRRIGATION PERMIT IS REQUIRED. PLEASE SUBMIT TWO | | | (2) COPIES OF AN IRRIGATION PLAN THAT PROVIDES 120% | | | COVERAGE TO ALL LANDSCAPED AREAS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2011-01-05 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2011-01-05 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2011-01-05 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2011-01-05 09:57:38 | PASS PROVISO | | | 1) PLEASE REFER TO SECTION 301.12 2007 FBC (M) WIND | | | RESISTANCE. | | | THE USE OF WOOD SLEEPERS SHALL NOT BE PERMITTED. | | | PLEASE PROVIDE A ROOF CONDENSING UNIT SUPPORT DETAIL AT | | | FIRST | | | INSPECTION. | | | 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR WALK IN | | | COOLERS | | | AND HOODS. | | | 3) DUCT SMOKE DETECTORS ARE REQUIRED PER SECTION | | | 606.2.1 AND 606.3 | | | 2007 FBC(M) | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2010-08-13 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2010-08-13 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2010-08-13 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2010-08-13 09:39:40 | ****PROVISOS**** | | | | | | 1. SEPARATE PERMITS REQUIRED FOR WALK IN COOLERS & | | | HOODS | | | 2. DUCT SMOKE DETECTOR REQUIRED, FBC MECHANICAL | | | 606.2.1, 606.3 | | | 3. TERMINATION OF EXHAUST TO COMPLY WITH FBC MECHANICAL | | | 501.2, 506.3.12.3 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2010-08-04 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2010-08-04 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2010-08-03 |
Time |
11:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2011-06-06 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2011-06-06 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2011-06-06 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2011-06-06 15:59:59 | PROVISO: | | | 1.SHEET A-2 SHALL BE REVISED TO REFLECT EXISTING | | | STOREFRONT IS NOT CHANGED. | | | 2. ANY NEW MECHANICAL EQUIPMENT ON ROOF SHALL BE | | | ENCLOSED AND SCREENED. | | | 3. ALL IMPROVEMENTS TO PROPERTY SHALL BE LESS THAN | | | $32,186. IF IMPROVEMENTS ARE MORE THAN THAT AMOUNT, | | | SITE SHALL BE BROUGHT INTO COMPLIANCE WITH ZONING CODE. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2010-12-22 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2010-12-22 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2010-12-22 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2010-12-22 16:23:36 | 1. REPEAT COMMENT: SHEET M-1 REFERENCE A ROOF | | | CONDENSING UNIT. PLEASE PROVIDE DRAWINGS INDICATING ANY | | | MECHANICAL EQUIPMENT TO BE LOCATED IN THE ROOF. ALL | | | MECHANICAL EQUIPMENT SHALL BE SCREENED. | | | 2. PROPOSED RENOVATION EXCEED 50% OF THE IMPROVEMENT | | | VALUE OF THE STRUCTURE. THE SITE SHALL BE BROUGHT BACK | | | INTO COMPLIANCE WITH EXISTING REGULATIONS REGARDING | | | LANDSCAPE. PLEASE LOOK AT LANDSCAPE REVIEW COMMENTS. | | | PLEASE CONTACT ANA MARIA APONTE AT 561-822-1439 FOR | | | ADDITIONAL INFORMATION. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2010-08-12 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2010-08-11 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2010-08-11 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2010-08-12 11:43:05 | ***FAILED*** | | | | | | PLEASE PROVIDE INFORMATION ON ANY NEW ROOFTOP EQUIPMENT | | | TO BE INSTALLED, IF ANY. INCLUDE ELEVATIONS AND | | | DIMENSIONAL SPECS. PLEASE NOTE THAT PURSUANT TO SEC. | | | 94-109 (DEFINITION OF PROJECTION,VERTICAL) ANY | | | EQUIPMENT THAT EXCEEDS THE HEIGHT OF THE ROOF SHALL BE | | | SCREENED IN SUCH A MANNER THAT THE ENCLOSURE APPEARS TO | | | BE AN INTEGRAL PART OF THE OVERALL BUILDING DESIGN. | | | | | | PLEASE CONTACT KELLY FREEMAN, GIS PLANNER, AT | | | 561-822-1458 WITH QUESTIONS. |
|
|