Plan Review Details - Permit 10070629
Plan Review Stops For Permit 10070629
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-06-03 Cont ID  
Sent By jwitmer Date 2011-05-20 Time 08:35 Rev Time 0.00
Received By jwitmer Date 2011-05-20 Time 08:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-01-05 Cont ID  
Sent By jwitmer Date 2011-01-05 Time 13:15 Rev Time 0.50
Received By jwitmer Date 2011-01-05 Time 12:42 Sent To  
Notes
2011-01-05 13:14:22BUILDING PLAN REVIEW
 PERMIT: 10070629
 ADD: 315 FERN ST
 CONT: HENSON DEV & CONST
 TEL: (727)481-1180
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 JAN. 05/2011
 2ND REVIEW
 ACTION: DENIED
  
 ***COMMENTS NOT ADDRESSED FROM 1ST REVIEW!!!!!!
  
 1) PLEASE SUBMIT SURVEY OR SITE PLAN INDICATING THE
 FRONT OF THE BUILDING, IT APPEARS THAT THE NEW
 STOREFRONT LOCATION, THE FRONT DOOR MAY CROSS THE
 PROPERTY LINE.
 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET
 IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
 ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL
 BE PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS
 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT
 OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 2)SHEET A-1 OF PLANS DATED 8-4-10 REV.1 INDICATE A NEW
 LOCATION FOR STOREFRONT APPROXIMATELY 3'-0" IN FRONT OF
 THE OLD LOCATION SAAME AS THE FIRST SET OF PLANS.
 NO COMMENTS FROM ARCHITECT BUT RESPONCE FROM ENGINEER
 STATING NO NEW EQUIPMENT ON ROOF TOP. THERE WAS NO
 COMMENT IN FIRST REVIEW THAT STATED NEW EQUIPMENT TO BE
 INSTALLED ON THE ROOF TOP, BUT PLANS INDICATE A NEW
 EXTERIOR SLAB FOR A WALK IN FREZZER AS WELL AS WIND
 CALC REQUIREMENT FOR THE NEW STOREFRONT SYSTEM TO BE
 INSTALLED.
  
 MISSING WIND DESIGN CRITERIA:
 1609.6.2 WIND DESIGN PROCEDURES
 2.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
 2.5 PLEASE PROVIDE THE POSITIVE & NEGATIVE PRESSURES,
 COMPONENTS AND CLADDING.
  
 3A)1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 3B) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 3B)(1) STOREFRONT WINDOWS RULE 9B-72(31)(B)
 3B)(2) STOREFRONT DOOR (NOT COVERED UNDER MOST PRODUCT
 APPROVALS) RULE 9B-72(31)(A)
 3B)(3) EXTERIOR WALK IN COOLER RULE 9B-72(31)(G) MAY BE
 PART OF THIS PERMIT OR SEPERATE PERMIT, BUT THERE WILL
 BE A OPENING IN THE EXTERIOR WALL WHERE THE COOLER IS
 TO BE INSTALLED.
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-08-05 Cont ID  
Sent By jwitmer Date 2010-08-05 Time 13:18 Rev Time 1.33
Received By jwitmer Date 2010-08-05 Time 13:18 Sent To  
Notes
2010-08-05 13:40:28BUILDING PLAN REVIEW
 PERMIT: 10070629
 ADD: 315 FERN ST
 CONT: HENSON DEV & CONST
 TEL: (727)481-1180
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE SUBMIT SURVEY OR SITE PLAN INDICATING THE
 FRONT OF THE BUILDING, IT APPEARS THAT THE NEW
 STOREFRONT LOCATION, THE FRONT DOOR MAY CROSS THE
 PROPERTY LINE.
 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET
 IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
 ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL
 BE PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS
 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT
 OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 2) MISSING WIND DESIGN CRITERIA:
 1609.6.2 WIND DESIGN PROCEDURES
 2.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
 2.5 PLEASE PROVIDE THE POSITIVE & NEGATIVE PRESSURES,
 COMPONENTS AND CLADDING.
  
 3A)1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 3B) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 3B)(1) STOREFRONT WINDOWS RULE 9B-72(31)(B)
 3B)(2) STOREFRONT DOOR (NOT COVERED UNDER MOST PRODUCT
 APPROVALS) RULE 9B-72(31)(A)
 3B)(3) EXTERIOR WALK IN COOLER RULE 9B-72(31)(G)
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-12-28 Cont ID  
Sent By rlecky Date 2010-12-28 Time 14:49 Rev Time 0.00
Received By rlecky Date 2010-12-28 Time 14:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-08-17 Cont ID  
Sent By jleahy Date 2010-08-17 Time 07:55 Rev Time 0.00
Received By jleahy Date 2010-08-17 Time 07:55 Sent To  
Notes
2010-08-17 08:22:331) NO ENERGY CALCULATION 13-415.B.1 , AND SPACE CONTROL
 PER 13-415.AB.1.2
  
 2) SERVICE GROUNDING NOT PER CODE
  
 3) EQUIPMENT GROUND FOR FEEDER NOT PER CODE
  
 4) SEE 210.8 B 2 FOR GFCI REQUIREMENTS
  
 5) CONFIRM AIC RATING BEFORE FIRST INSPECTION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-12-30 Cont ID  
Sent By wjolin Date 2010-12-30 Time 14:49 Rev Time 0.00
Received By wjolin Date 2010-12-30 Time 14:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-07-29 Cont ID  
Sent By wjolin Date 2010-07-29 Time 17:17 Rev Time 0.00
Received By wjolin Date 2010-07-29 Time 16:07 Sent To  
Notes
2010-07-29 17:16:47*****REVIEW COMMENTS - FIRE*****
  
 1) SHEET A-2: RESTROOM DOOR SWING OBSTRUCTS ACCESS TO
 REAR EXIT (NFPA 101, SECTION 7.2.1.4.4).
  
 2) SHEET A-2: EQUIPMENT #60 (HOOD SUPPRESSION SYSTEM)
 NOT FOUND ON FLOOR PLAN. SEPARATE PLANS AND PERMIT
 REQUIRED FOR SUPPRESSION SYSTEM.
  
 3) TYPE K PORTABLE FIRE EXTINGUISHER PROVIDED FOR
 KITCHEN AREA; PROVIDE 2A-10BC EXTINGUISHER FOR
 NON-KITCHEN SPACE.
  
 4) SHEET A-4: PROVIDE BUILDING ADDRESS NUMBERS AT LEAST
 SIX-INCHES IN HEIGHT ON BUILDING SO NUMERALS ARE
 VISIBLE FROM THE ROAD FRONTING THE PROPERTY (NFPA 1,
 SECTION 10.12.1).
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2010-12-27 Cont ID  
Sent By lwagner Date 2010-12-27 Time 10:42 Rev Time 0.00
Received By lwagner Date 2010-12-27 Time 10:27 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2010-08-04 Cont ID  
Sent By lwagner Date 2010-08-04 Time 09:37 Rev Time 0.00
Received By lwagner Date 2010-08-04 Time 09:27 Sent To  
Notes
2010-08-04 09:36:03FUEL GAS PLAN REVIEW #1
 DENIED:
  
 1.PLEASE SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS
 ALL CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2007 FUEL GAS.
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. 9.
 RISER DIAGRAM/SHUTOFFS
  
 2. BTU LOAD AND PIPE SIZE FOR WATER HEATER IS NOT SHOWN
 ON PLAN.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-06-24 Cont ID  
Sent By ajones Date 2011-06-24 Time 13:24 Rev Time 0.00
Received By ajones Date 2011-05-20 Time 09:05 Sent To  
Notes
2011-06-06 09:06:02B--3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-12-20 Cont ID  
Sent By lmartine Date 2010-12-20 Time 16:27 Rev Time 0.00
Received By lmartine Date 2010-12-20 Time 16:26 Sent To  
Notes
2010-12-20 16:31:01B--16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-20 Cont ID  
Sent By lmartine Date 2010-08-17 Time 16:24 Rev Time 0.00
Received By lmartine Date 2010-07-26 Time 16:22 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 4 Status P Date 2011-06-24 Cont ID  
Sent By ajones Date 2011-06-24 Time 13:23 Rev Time 0.00
Received By ajones Date 2011-06-24 Time 13:23 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 3 Status F Date 2011-06-15 Cont ID  
Sent By rkussner Date 2011-06-15 Time 16:52 Rev Time 0.00
Received By rkussner Date 2011-06-15 Time 16:52 Sent To  
Notes
2011-06-15 16:56:07 
 ***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. REPEAT COMMENT: PURSUANT TO SECTION 94-441(C)(2) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR): AS
 THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF THE
 STRUCTURE'S VALUE (LISTED AS "IMPROVEMENT VALUE" WITH
 THE P.B.C. PROPERTY APPRAISER'S OFFICE), LANDSCAPING
 SHALL BE IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS
 FOUND IN ARTICLE XIV OF THE ZLDR. THE PERMITS IN PLACE
 AT THIS TIME EQUAL $39,100 AND THE IMPROVEMENT VALUE IS
 $64,372.
  
 2.REPEAT COMMENT: LANDSCAPING REQUIRES A SEPARATE
 PERMIT. PLEASE APPLY FOR A LANDSCAPE PERMIT AND SUBMIT
 TWO COPIES OF A COMPLETE LANDSCAPE PLAN SHOWING
 COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS. IT SHALL BE
 SIGNED AND SEALED BY A REGISTERED LANDSCAPE ARCHITECT.
 A CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST
 OF ALL LANDSCAPE MATERIALS AND LABOR. IT SHALL BE
 BROKEN DOWN INTO UNIT COST.
  
 3. REPEAT COMMENT: PLEASE PROVIDE THE TABULATION
 NECESSARY FOR THE EVALUATION OF COMPLIANCE WITH ARTICLE
 XIV OF THE ZONING AND LAND DEVELOPMENT REGULATIONS,
 INCLUDING THE XERISCAPE DESIGN OPTIONS.
  
 4. REPEAT COMMENT: PURSUANT TO SECTION 94-448 (D) (2),
 THE LANDSCAPE PLAN SHALL CONTAIN ALL OF THE ITEMS
 ENUMERATED IN THIS SECTION.
  
 4. REPEAT COMMENT: AN IRRIGATION PERMIT IS REQUIRED.
 PLEASE SUBMIT TWO (2) COPIES OF AN IRRIGATION PLAN THAT
 PROVIDES 120% COVERAGE TO ALL LANDSCAPED AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2010-12-21 Cont ID  
Sent By rkussner Date 2010-12-21 Time 11:48 Rev Time 0.00
Received By rkussner Date 2010-12-21 Time 11:48 Sent To  
Notes
2010-12-21 11:49:44***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. REPEAT COMMENT: PURSUANT TO SECTION 94-441(C)(2) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR): AS
 THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF THE
 STRUCTURE'S VALUE (LISTED AS "IMPROVEMENT VALUE" WITH
 THE P.B.C. PROPERTY APPRAISER'S OFFICE), LANDSCAPING
 SHALL BE IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS
 FOUND IN ARTICLE XIV OF THE ZLDR.
  
 2.REPEAT COMMENT: LANDSCAPING REQUIRES A SEPARATE
 PERMIT. PLEASE APPLY FOR A LANDSCAPE PERMIT AND SUBMIT
 TWO COPIES OF A COMPLETE LANDSCAPE PLAN SHOWING
 COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS. IT SHALL BE
 SIGNED AND SEALED BY A REGISTERED LANDSCAPE ARCHITECT.
 A CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST
 OF ALL LANDSCAPE MATERIALS AND LABOR. IT SHALL BE
 BROKEN DOWN INTO UNIT COST.
  
 3. REPEAT COMMENT: PLEASE PROVIDE THE TABULATION
 NECESSARY FOR THE EVALUATION OF COMPLIANCE WITH ARTICLE
 XIV OF THE ZONING AND LAND DEVELOPMENT REGULATIONS,
 INCLUDING THE XERISCAPE DESIGN OPTIONS.
  
 4. REPEAT COMMENT: PURSUANT TO SECTION 94-448 (D) (2),
 THE LANDSCAPE PLAN SHALL CONTAIN ALL OF THE ITEMS
 ENUMERATED IN THIS SECTION.
  
 4. REPEAT COMMENT: AN IRRIGATION PERMIT IS REQUIRED.
 PLEASE SUBMIT TWO (2) COPIES OF AN IRRIGATION PLAN THAT
 PROVIDES 120% COVERAGE TO ALL LANDSCAPED AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-08-06 Cont ID  
Sent By rkussner Date 2010-08-06 Time 15:11 Rev Time 0.00
Received By rkussner Date 2010-08-06 Time 15:11 Sent To  
Notes
2010-08-06 15:24:03***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 2. LANDSCAPING REQUIRES A SEPARATE PERMIT. PLEASE APPLY
 FOR A LANDSCAPE PERMIT AND SUBMIT TWO COPIES OF A
 COMPLETE LANDSCAPE PLAN SHOWING COMPLIANCE WITH
 SECTIONS 94-442 AND 94-445 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS. IT SHALL BE SIGNED AND SEALED
 BY A REGISTERED LANDSCAPE ARCHITECT. A CERTIFIED COST
 ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE
 MATERIALS AND LABOR. IT SHALL BE BROKEN DOWN INTO UNIT
 COST.
  
 3. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 XERISCAPE DESIGN OPTIONS.
  
 4. PURSUANT TO SECTION 94-448 (D) (2), THE LANDSCAPE
 PLAN SHALL CONTAIN ALL OF THE ITEMS ENUMERATED IN THIS
 SECTION.
  
 4. AN IRRIGATION PERMIT IS REQUIRED. PLEASE SUBMIT TWO
 (2) COPIES OF AN IRRIGATION PLAN THAT PROVIDES 120%
 COVERAGE TO ALL LANDSCAPED AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-01-05 Cont ID  
Sent By hmoser Date 2011-01-05 Time 09:44 Rev Time 0.00
Received By hmoser Date 2011-01-05 Time 09:44 Sent To  
Notes
2011-01-05 09:57:38PASS PROVISO
 1) PLEASE REFER TO SECTION 301.12 2007 FBC (M) WIND
 RESISTANCE.
 THE USE OF WOOD SLEEPERS SHALL NOT BE PERMITTED.
 PLEASE PROVIDE A ROOF CONDENSING UNIT SUPPORT DETAIL AT
 FIRST
 INSPECTION.
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR WALK IN
 COOLERS
 AND HOODS.
 3) DUCT SMOKE DETECTORS ARE REQUIRED PER SECTION
 606.2.1 AND 606.3
 2007 FBC(M)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-08-13 Cont ID  
Sent By hmoser Date 2010-08-13 Time 09:36 Rev Time 0.00
Received By hmoser Date 2010-08-13 Time 09:36 Sent To  
Notes
2010-08-13 09:39:40****PROVISOS****
  
 1. SEPARATE PERMITS REQUIRED FOR WALK IN COOLERS &
 HOODS
 2. DUCT SMOKE DETECTOR REQUIRED, FBC MECHANICAL
 606.2.1, 606.3
 3. TERMINATION OF EXHAUST TO COMPLY WITH FBC MECHANICAL
 501.2, 506.3.12.3
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-08-04 Cont ID  
Sent By lwagner Date 2010-08-04 Time 10:19 Rev Time 0.00
Received By lwagner Date 2010-08-03 Time 11:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2011-06-06 Cont ID  
Sent By aaponte Date 2011-06-06 Time 15:56 Rev Time 0.00
Received By aaponte Date 2011-06-06 Time 15:56 Sent To  
Notes
2011-06-06 15:59:59PROVISO:
 1.SHEET A-2 SHALL BE REVISED TO REFLECT EXISTING
 STOREFRONT IS NOT CHANGED.
 2. ANY NEW MECHANICAL EQUIPMENT ON ROOF SHALL BE
 ENCLOSED AND SCREENED.
 3. ALL IMPROVEMENTS TO PROPERTY SHALL BE LESS THAN
 $32,186. IF IMPROVEMENTS ARE MORE THAN THAT AMOUNT,
 SITE SHALL BE BROUGHT INTO COMPLIANCE WITH ZONING CODE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439

Review Stop Z ZONING
Rev No 2 Status F Date 2010-12-22 Cont ID  
Sent By aaponte Date 2010-12-22 Time 16:22 Rev Time 0.00
Received By aaponte Date 2010-12-22 Time 16:22 Sent To  
Notes
2010-12-22 16:23:361. REPEAT COMMENT: SHEET M-1 REFERENCE A ROOF
 CONDENSING UNIT. PLEASE PROVIDE DRAWINGS INDICATING ANY
 MECHANICAL EQUIPMENT TO BE LOCATED IN THE ROOF. ALL
 MECHANICAL EQUIPMENT SHALL BE SCREENED.
 2. PROPOSED RENOVATION EXCEED 50% OF THE IMPROVEMENT
 VALUE OF THE STRUCTURE. THE SITE SHALL BE BROUGHT BACK
 INTO COMPLIANCE WITH EXISTING REGULATIONS REGARDING
 LANDSCAPE. PLEASE LOOK AT LANDSCAPE REVIEW COMMENTS.
 PLEASE CONTACT ANA MARIA APONTE AT 561-822-1439 FOR
 ADDITIONAL INFORMATION.

Review Stop Z ZONING
Rev No 1 Status F Date 2010-08-12 Cont ID  
Sent By kdfreema Date 2010-08-11 Time 16:10 Rev Time 0.00
Received By kdfreema Date 2010-08-11 Time 16:10 Sent To  
Notes
2010-08-12 11:43:05***FAILED***
  
 PLEASE PROVIDE INFORMATION ON ANY NEW ROOFTOP EQUIPMENT
 TO BE INSTALLED, IF ANY. INCLUDE ELEVATIONS AND
 DIMENSIONAL SPECS. PLEASE NOTE THAT PURSUANT TO SEC.
 94-109 (DEFINITION OF PROJECTION,VERTICAL) ANY
 EQUIPMENT THAT EXCEEDS THE HEIGHT OF THE ROOF SHALL BE
 SCREENED IN SUCH A MANNER THAT THE ENCLOSURE APPEARS TO
 BE AN INTEGRAL PART OF THE OVERALL BUILDING DESIGN.
  
 PLEASE CONTACT KELLY FREEMAN, GIS PLANNER, AT
 561-822-1458 WITH QUESTIONS.