Plan Review Details - Permit 10070545
Plan Review Stops For Permit 10070545
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-08-19 Cont ID  
Sent By rmcdouga Date 2010-08-19 Time 16:07 Rev Time 0.00
Received By rmcdouga Date 2010-08-19 Time 16:07 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-07-26 Cont ID  
Sent By rmcdouga Date 2010-07-26 Time 16:21 Rev Time 0.00
Received By rmcdouga Date 2010-07-26 Time 16:21 Sent To  
Notes
2010-07-26 16:28:25DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF THE PRODUCT APPROVAL FOR THE
 SPECIFIC DOOR THAT IS BEING REPLACED. THREE DIFFERENT
 PRODUCT APPROVALS WERE SUBMITTED TWO ARE FOR GLAZED
 DOORS. IF THE DOOR IS A SIX PANEL WITH NO GLASS IN IT
 THEN NOA NO. 08-1015.05 IS THE CORRECT ONE AND YOU CAN
 SUBMIT AN ADDITIONAL COPY OF IT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-07-27 Cont ID  
Sent By jleahy Date 2010-07-27 Time 10:35 Rev Time 0.00
Received By jleahy Date 2010-07-27 Time 10:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-13 Cont ID  
Sent By lmartine Date 2010-08-13 Time 09:57 Rev Time 0.00
Received By lmartine Date 2010-08-13 Time 09:57 Sent To  
Notes
2010-08-13 09:58:09GAVE TO ROBERT MC.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-06 Cont ID  
Sent By lmartine Date 2010-08-05 Time 16:26 Rev Time 0.00
Received By lmartine Date 2010-07-23 Time 10:57 Sent To  
Notes
2010-07-23 10:58:25GAVE TO ROBBIE
 1&2 FAMILY REVIEW

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2010-09-30 Cont ID  
Sent By rmcdouga Date 2010-09-30 Time 10:42 Rev Time 0.00
Received By rmcdouga Date 2010-09-30 Time 10:42 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2010-08-19 Cont ID  
Sent By rmcdouga Date 2010-08-19 Time 15:52 Rev Time 0.00
Received By rmcdouga Date 2010-08-19 Time 15:52 Sent To  
Notes
2010-08-19 16:00:072007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) FBCR M1602.2 PROHIBITS RETURN AIR FROM A BATHROOM.
 THE PLANS INDICATE RETURNS AT BOTH BATHROOMS. SUBMIT
 CORRECTED PLANS.
  
 2) THE PLANS INDICATE THAT ALL OF THE DUCT WORK IS 8"
 FLEX AND THAT ALL OF THE ROOMS WILL BE SUPPLIED WITH
 300 CFM OF AIR. THIS DOES NOT COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE FOR CORRECTLY
 SIZING AN HVAC SYSTEM. FBCR M1601.1 REQUIRES DUCT
 SYSTEMS TO BE DESIGNED IN ACCORDANCE WITH ACCA MANUAL D
 OR OTHER APPROVED METHOD. THE HEAT GAIN AND BTU/HR OF
 COOLING REQUIRED FOR EACH ROOM NEEDS TO BE DETERMINED.
 THEN THE DUCT CAN BE PROPERLY SIZED TO THE CFM AND
 VELOCITY NEEDED FOR THE ROOM SERVED IN ACCORDANCE WITH
 THE MANUAL J AND MANUAL D DUCT DESIGN. SUBMIT CORRECTED
 PLANS.
  
 3) THE NAME AND LICENSE NUMBER OF THE HVAC CONTRACTOR
 RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-07-26 Cont ID  
Sent By rmcdouga Date 2010-07-26 Time 16:29 Rev Time 0.00
Received By rmcdouga Date 2010-07-26 Time 16:29 Sent To  
Notes
2010-07-26 16:41:452007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS AS REQUIRED BY FBC M1401.3.
  
 2) SUBMIT TWO SETS OF FLOOR PLANS SHOWING THE LOCATIONS
 OF THE AIR HANDLERS, CONDENSERS, DISCONNECTS, SERVICE
 OUTLETS, DUCT SIZES, SUPPLY LOCATIONS, GRILL SIZES, CFM
 AT EACH SUPPLY, RETURN LOCATIONS AND SIZES, TRANSFER
 DUCT/GRILL LOCATIONS AND SIZES. SPECIFY THE HEATING AND
 COOLING EQUIPMENT ON THE PLANS INCLUDING MODEL NUMBERS
 AND SPECIFICATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-07-26 Cont ID  
Sent By rmcdouga Date 2010-07-26 Time 16:28 Rev Time 0.00
Received By rmcdouga Date 2010-07-26 Time 16:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2010-10-06 Cont ID  
Sent By ajones Date 2010-10-06 Time 14:03 Rev Time 0.00
Received By ajones Date 2010-10-06 Time 14:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2010-08-26 Cont ID  
Sent By ajones Date 2010-08-26 Time 10:44 Rev Time 0.00
Received By ajones Date 2010-08-24 Time 16:45 Sent To  
Notes
2010-08-26 10:45:36PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THE AC
 UNITS IN THE SETBACK.

Review Stop Z ZONING
Rev No 1 Status F Date 2010-08-05 Cont ID  
Sent By astelly Date 2010-08-05 Time 21:16 Rev Time 0.00
Received By astelly Date 2010-08-05 Time 21:16 Sent To I
Notes
2010-08-05 21:18:43AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PLEASE PROVIDE A SURVEY SHOWING LOCATION AND SETBACKS
 OF AC UNIT. YOUR SUBMISSION MAY GENERATE ADDITIONAL
 COMMENTS.
  