| Plan Review Stops For Permit 10070545 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2010-08-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-08-19 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-08-19 |
Time |
16:07 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2010-07-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-07-26 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-07-26 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2010-07-26 16:28:25 | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF THE PRODUCT APPROVAL FOR THE | | | SPECIFIC DOOR THAT IS BEING REPLACED. THREE DIFFERENT | | | PRODUCT APPROVALS WERE SUBMITTED TWO ARE FOR GLAZED | | | DOORS. IF THE DOOR IS A SIX PANEL WITH NO GLASS IN IT | | | THEN NOA NO. 08-1015.05 IS THE CORRECT ONE AND YOU CAN | | | SUBMIT AN ADDITIONAL COPY OF IT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2010-07-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2010-07-27 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2010-07-27 |
Time |
10:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2010-08-13 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-08-13 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-08-13 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2010-08-13 09:58:09 | GAVE TO ROBERT MC. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-08-06 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-08-05 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-07-23 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2010-07-23 10:58:25 | GAVE TO ROBBIE | | | 1&2 FAMILY REVIEW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2010-09-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-09-30 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-09-30 |
Time |
10:42 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2010-08-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-08-19 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-08-19 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2010-08-19 16:00:07 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) FBCR M1602.2 PROHIBITS RETURN AIR FROM A BATHROOM. | | | THE PLANS INDICATE RETURNS AT BOTH BATHROOMS. SUBMIT | | | CORRECTED PLANS. | | | | | | 2) THE PLANS INDICATE THAT ALL OF THE DUCT WORK IS 8" | | | FLEX AND THAT ALL OF THE ROOMS WILL BE SUPPLIED WITH | | | 300 CFM OF AIR. THIS DOES NOT COMPLY WITH THE | | | REQUIREMENTS OF THE FLORIDA BUILDING CODE FOR CORRECTLY | | | SIZING AN HVAC SYSTEM. FBCR M1601.1 REQUIRES DUCT | | | SYSTEMS TO BE DESIGNED IN ACCORDANCE WITH ACCA MANUAL D | | | OR OTHER APPROVED METHOD. THE HEAT GAIN AND BTU/HR OF | | | COOLING REQUIRED FOR EACH ROOM NEEDS TO BE DETERMINED. | | | THEN THE DUCT CAN BE PROPERLY SIZED TO THE CFM AND | | | VELOCITY NEEDED FOR THE ROOM SERVED IN ACCORDANCE WITH | | | THE MANUAL J AND MANUAL D DUCT DESIGN. SUBMIT CORRECTED | | | PLANS. | | | | | | 3) THE NAME AND LICENSE NUMBER OF THE HVAC CONTRACTOR | | | RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2010-07-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-07-26 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-07-26 |
Time |
16:29 |
Sent To |
|
|
| Notes |
| 2010-07-26 16:41:45 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS AS REQUIRED BY FBC M1401.3. | | | | | | 2) SUBMIT TWO SETS OF FLOOR PLANS SHOWING THE LOCATIONS | | | OF THE AIR HANDLERS, CONDENSERS, DISCONNECTS, SERVICE | | | OUTLETS, DUCT SIZES, SUPPLY LOCATIONS, GRILL SIZES, CFM | | | AT EACH SUPPLY, RETURN LOCATIONS AND SIZES, TRANSFER | | | DUCT/GRILL LOCATIONS AND SIZES. SPECIFY THE HEATING AND | | | COOLING EQUIPMENT ON THE PLANS INCLUDING MODEL NUMBERS | | | AND SPECIFICATIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2010-07-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-07-26 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-07-26 |
Time |
16:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2010-10-06 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2010-10-06 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2010-10-06 |
Time |
14:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2010-08-26 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2010-08-26 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2010-08-24 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2010-08-26 10:45:36 | PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THE AC | | | UNITS IN THE SETBACK. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2010-08-05 |
|
|
Cont ID |
|
| Sent By |
astelly |
Date |
2010-08-05 |
Time |
21:16 |
Rev Time |
0.00 |
| Received By |
astelly |
Date |
2010-08-05 |
Time |
21:16 |
Sent To |
I |
|
| Notes |
| 2010-08-05 21:18:43 | AMY STELLY | | | PLANNING AND ZONING | | | 561-822-1442 | | | | | | PLEASE PROVIDE A SURVEY SHOWING LOCATION AND SETBACKS | | | OF AC UNIT. YOUR SUBMISSION MAY GENERATE ADDITIONAL | | | COMMENTS. | | | |
|
|