Plan Review Details - Permit 10070389
Plan Review Stops For Permit 10070389
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-10-22 Cont ID  
Sent By jwitmer Date 2010-10-22 Time 14:43 Rev Time 2.20
Received By jwitmer Date 2010-10-20 Time 13:48 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2010-09-21 Cont ID  
Sent By jwitmer Date 2010-09-21 Time 09:30 Rev Time 0.77
Received By jwitmer Date 2010-09-21 Time 08:45 Sent To  
Notes
2010-09-21 09:59:59BUILDING PLAN REVIEW
 PERMIT: 08010251/ REV 10070389
 ADD: 2223 PALM BEACH LAKES # 101
 CONT: CONFORT BUILDERS
 TEL: (561)662-2455
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 SEPTEMBER 21/2010
 3RD REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
  
 1A)SEMI-COMPLIED. PLEASE PROVIDE A SITE PLAN WITH THE
 NEW EGRESS DOORS AT SIDE OF BUILDING INDICATING THE
 ACCESSIBLE PATH TO THE PUBLIC WAY. 11-4.1.3(8)(A)(II)
 ACCESSIBLE ENTRANCES MUST BE PROVIDED IN A NUMBER AT
 LEAST EQUIVALENT TO THE NUMBER OF EXITS REQUIRED BY THE
 APPLICABLE BUILDING/FIRE CODES. THE EXTERIOR DOORS FROM
 HALL'S 3 & 4 ARE MISSING ON THE DEVELOPED PLAN DATED
 8/23/2010. WITH THE ACCORDIAN DOORS IN THE CLOSED
 POSITION THESE ROOMS ALL HAVE AN OCCUPANT LOAD GREATER
 THAN 50 OCCUPANTS REQUIRING 2 MEANS OF EGRESS. FBC-B
 1015.1(1).
  
 THE PLANS ARE NOT CONSISTENT IN INDICATING THE NEW
 RECESSED EXIT ENCLOSURES:
 A-1 SCOPE OF WORK THE NEW RECESSED EXIT ENCLOSURES ARE
 MISSING
 A-3 THE LIFE SAFETY PLAN THEY ARE MISSING AND THE
 ADDITIONAL EXIT SIGNAGE.
 A-4 THE REFLECTED CEILING PLAN THE ENCLOSURES ARE
 MISSING AND EXIT SIGNAGE ,
 NOTE NO STRUCTURAL INFORMATION WAS PROVIDED FOR THE NEW
 RESSED ENCLOSURE, PRODUCT APPROVAL FOR DOOR
 E-1 ALSO IS EFFECTED WITH THE ADDITIONAL EXIT LIGHT
 REQUIREMENTS.
  
 1B-G-I) COMPLIED.
  
 1J) SECOND REQUEST,PLANS ALSO INDICATE ON A-2 A NEW
 STOREFRONT DOOR AND WINDOW SYSTEM, PLEASE PROVIDE WIND
 DESIGN CRITERIA:
  
 1609.6.2 WIND DESIGN PROCEDURES
 1J)(1) COMPLIED.
  
 1J)(2)COMPLIED.
  
 1J)(3) SECOND REQUEST, AN EXPOSURE CATEGORY SHALL BE
 DETERMINED IN ACCORDANCE WITH 1609.4. SHEET A-1
 (8/23/10) INDICATES A "B" EXPOSURE, PLEASE REVIEW
 SECTION
 FBC-B 1609.4.3 EXPOSURE C THIS EXPOSURE SHALL ALSO
 APPLY TO ANY BUILDING LOCATED WITHIN EXPOSURE B-TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF EXPOSURE
 C-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9
 M) AND WIDTH GREATER THAN 150 FT. IN THE UPWIND
 DIRECTION.
  
 1J)(4) SINCE THE EXPOSURE "C" HAS ADJUSTMENT FACTOR
 PLEASE REVIEW PRESSURES. PROVIDE THE MEAN ROOF HEIGHT.
 A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * SHALL
 BE DETERMINED FROM TABLE 1609.6.2.1(4) THEDESIGNER OF
 RECORD IS APPERANTLY LOOKING FOR END ZONE CONDITIONS
 "WORST CASE" WITH PRESSURES OF -60.88 (A-1)
 THE SUBMITTED PRODUCT APPROVAL FOR THE FRONT DOOR ARE
 LOW AT +/-55 PSF.
  
 1K) SECOND REQUEST, WILL NEED TO BE RE-REVIEWED FOR
 EXPOSURE "C" FACTORS. NOTE NO PRODUCT APPROVALS WERE
 SUBMITTED.
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 1) EXTERIOR DOORS FRONT ENTRY
 2) EXERIOR SIDE DOORS- MISSING
  
 1L)2ND REQUEST. 106.3.3 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 1M) SECOND REQUEST, NEW EXTERIOR OPENINGS PLEASE
 PROVIDE DETAILS ON THE MWFRS CONTINIOUS LOAD PATH. WITH
 REQUEST IS NOW FOR THE NEW EXIT RECESS FOR BANQUET
 HALL # 3& 4.
  
 1N)COMPLIED.
  
 1O) SECOND REQUEST, PLEASE PROVIDE MANUFACTURERS
 DETAILS ON THE FOLDING PARTITION AS TO INSTALATION,
 106.1.2 ADDITIONAL INFORMATION REQUIRED. IT IS NOT
 KNOWN IF THESE LOADS WILL BE IMPOSED ONTO THE ROOF
 CEILING ASSEMBLY OR NOT? AND WHAT THESE LOADS MAY BE,
 THIS ITEM CAN BE A BUILDING PROVISO: AND BE SUBMITTED
 AFTER THTE PERMIT ISSUANCE ONCE REVIEWED BY THE DESIGN
 PROFESSIONAL.
  
 1P) COMPLIED.
  
 1R) COMPLIED.
  
 1S) COMPLIED.
  
 2) COMPLIED.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-08-25 Cont ID  
Sent By jwitmer Date 2010-08-25 Time 15:39 Rev Time 2.22
Received By jwitmer Date 2010-08-25 Time 15:38 Sent To  
Notes
2010-08-25 16:32:53BUILDING PLAN REVIEW
 PERMIT: 08010251/ REV 10070389
 ADD: 2223 PALM BEACH LAKES # 101
 CONT: ADELFOS CONSTRUCTION
 TEL: (561)662-2455
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 AUGUST 25/2010
 2ND REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
  
 1) 2007 EXISTING BUILDING CODE. 912.1.4 ACCESSIBILITY.
 ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 912.8. 912.8
 ACCESSIBILITY. EXISTING BUILDINGS OR PORTIONS THEREOF
 THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING.
 11-4.1.6(1)(D) NO ALTERATION OF AN EXISTING ELEMENT,
 SPACE, OR AREA OF A BUILDING OR FACILITY SHALL IMPOSE A
 REQUIREMENT FOR GREATER ACCESSIBILITY THAN THAT WHICH
 WOULD BE REQUIRED FOR NEW CONSTRUCTION.
  
 1A)SEMI-COMPLIED. PLEASE PROVIDE A SITE PLAN WITH THE
 NEW EGRESS DOORS AT SIDE OF BUILDING INDICATING THE
 ACCESSIBLE PATH TO THE PUBLIC WAY. 11-4.1.3(8)(A)(II)
 ACCESSIBLE ENTRANCES MUST BE PROVIDED IN A NUMBER AT
 LEAST EQUIVALENT TO THE NUMBER OF EXITS REQUIRED BY THE
 APPLICABLE BUILDING/FIRE CODES. THE EXTERIOR DOORS FROM
 HALL'S 2,3 & 4 ARE MISSING ON THE DEVELOPED PLAN DATED
 8/23/2010. WITH THE ACCORDIAN DOORS IN THE CLOSED
 POSITION THESE ROOMS ALL HAVE AN OCCUPANT LOAD GREATER
 THAN 50 OCCUPANTS REQUIRING 2 MEANS OF EGRESS. FBC-B
 1015.1(1).
  
 1B-G) COMPLIED.
  
 1H) SECOND REQUEST, PLEASE PROVIDE ON THE SITE PLAN,
 THE DISTANCE FROM THE PROPERTY LINE TO THE NEW EXTERIOR
 DOOR. TABLE 704.8.
  
 1I) SECOND REQUEST, THE BACK EXIT PLESE INDICATE BACK
 EXIT CONDITIONS, IS THIS AN ACCESSIBLE EGRESS?
 11-4.1.6(1)(D). & EXISTING BUILDING CODE TABLE 912.4
  
  
 1J) SECOND REQUEST,PLANS ALSO INDICATE ON A-2 A NEW
 STOREFRONT DOOR AND WINDOW SYSTEM, PLEASE PROVIDE WIND
 DESIGN CRITERIA:
  
 1609.6.2 WIND DESIGN PROCEDURES
 1J)(1) COMPLIED.
  
 1J)(2)COMPLIED.
  
 1J)(3) SECOND REQUEST, AN EXPOSURE CATEGORY SHALL BE
 DETERMINED IN ACCORDANCE WITH 1609.4. SHEET A-1
 (8/23/10) INDICATES A "B" EXPOSURE, PLEASE REVIEW
 SECTION
 FBC-B 1609.4.3 EXPOSURE C THIS EXPOSURE SHALL ALSO
 APPLY TO ANY BUILDING LOCATED WITHIN EXPOSURE B-TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF EXPOSURE
 C-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9
 M) AND WIDTH GREATER THAN 150 FT. IN THE UPWIND
 DIRECTION.
  
 1J)(4) SINCE THE EXPOSURE "C" HAS ADJUSTMENT FACTOR
 PLEASE REVIEW PRESSURES. PROVIDE THE MEAN ROOF HEIGHT.
 A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * SHALL
 BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 1K) SECOND REQUEST, WILL NEED TO BE RE-REVIEWED FOR
 EXPOSURE "C" FACTORS. NOTE NO PRODUCT APPROVALS WERE
 SUBMITTED.
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 1) EXTERIOR DOORS
 2) DOORS
  
 1L)2ND REQUEST. 106.3.3 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 1M) SECOND REQUEST, NEW EXTERIOR OPENINGS PLEASE
 PROVIDE DETAILS ON THE MWFRS CONTINIOUS LOAD PATH.
  
 1N) SECOND REQUEST, A-2 INDICATES NEW STOREFRONT SYSTEM
 AND DECREASING THE STOREFRONT OPENING BY APPROXIMATELY
 12 LINEAL FEET WITH NO STRUCTURAL INFORMATION ON THE
 EXTERIOR WALL SYSTEM.MWFRS
 CONTINIOUS LOAD PATH.
  
 1O) SECOND REQUEST, PLEASE PROVIDE MANUFACTURERS
 DETAILS ON THE FOLDING PARTITION AS TO INSTALATION,
 106.1.2 ADDITIONAL INFORMATION REQUIRED. IT IS NOT
 KNOWN IF THESE LOADS WILL BE IMPOSED ONTO THE ROOF
 CEILING ASSEMBLY OR NOT? AND WHAT THESE LOADS MAY BE,
 THIS ITEM CAN BE A BUILDING PROVISO: AND BE SUBMITTED
 AFTER THTE PERMIT ISSUANCE ONCE REVIEWED BY THE DESIGN
 PROFESSIONAL.
  
 1P) COMPLIED.
  
 1R) COMPLIED.
  
 1S) COMPLIED.
  
 2) THE A SHEETS NOR E-1 INDICATE COMPLIANCE WITH THE
 2007 EXISTING BUILDING CODE 912.2.2 FIRE ALARM SYSTEMS
 & 2007 FBC-B 907.2.1 ALSO REVIEW EXCEPTION.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-07-21 Cont ID  
Sent By jwitmer Date 2010-07-21 Time 09:11 Rev Time 3.20
Received By jwitmer Date 2010-07-21 Time 08:50 Sent To  
Notes
2010-07-21 10:36:29BUILDING PLAN REVIEW
 PERMIT: 08010251/ REV 10070389
 ADD: 2223 PALM BEACH LAKES # 101
 CONT: ADELFOS CONSTRUCTION
 TEL: (561)662-2455
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 2007 EXISTING BUILDING CODE. 912.1.4 ACCESSIBILITY.
 ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 912.8. 912.8
 ACCESSIBILITY. EXISTING BUILDINGS OR PORTIONS THEREOF
 THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING.
 11-4.1.6(1)(D) NO ALTERATION OF AN EXISTING ELEMENT,
 SPACE, OR AREA OF A BUILDING OR FACILITY SHALL IMPOSE A
 REQUIREMENT FOR GREATER ACCESSIBILITY THAN THAT WHICH
 WOULD BE REQUIRED FOR NEW CONSTRUCTION.
  
 1A) PLEASE PROVIDE A SITE PLAN WITH THE NEW EGRESS
 DOORS AT SIDE OF BUILDING INDICATING THE ACCESSIBLE
 PATH TO THE PUBLIC WAY. 11-4.1.3(8)(A)(II) ACCESSIBLE
 ENTRANCES MUST BE PROVIDED IN A NUMBER AT LEAST
 EQUIVALENT TO THE NUMBER OF EXITS REQUIRED BY THE
 APPLICABLE BUILDING/FIRE CODES.
  
 1B) PLANS INDICATE A CHANGE IN OCCUPANCY,A A-3
 OCCUPANCY WITH 4292 SQ FT OF A-3 OCCUPANCY WITH UNFIXED
 SEATING. TABLE 1004.1.1 INDICATES 7 SQ FT PER OCCUPANT
 PROVIDING AN OCCUPANT LOAD OF 614 PLEASE CORRECT
 OCCUPANCY DATA TABULATION.
  
 1C) PLEASE UPDATE THE OCCUPANCY DATA TABULATION FOR
 EACH OF THE ASSEMBLY ROOMS USING 7 SQ FT/ OCCUPANT FOR
 UNFIXED SEATING USAGE. TABLE 1004.1.1.
  
 1D) PLEASE REVIEW NOTE ON A-2 FOR A MINIMUM OF 8 INCHES
 BETWEEN THE ACCORDIAN DOOR AND NEW DOOR. SEE ROOM 107
 AND SECTION 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT
 ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN
 IN FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE
 REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 1E) SHEET A-2 AND E-1 BOTH INDICATE ROOM 106 TO BE A
 KITCHEN, KITCHETTE. PLEASE REVIEW 1014.2 EXCEPTION# 1
 NO EGRESS THROUGH A KITCHEN.
  
 1F) SHEET A-2 INDICATES AN EXIT CORRIDOR # 102 WITH
 UNRATED CORRIDOR WALLS, PLEASE REVIEW FBC-B TABLE
 1017.1 WHICH REQUIRES RATED WALL.
  
 1G) SHEET A-2 CORRIDOR 102 REQUIRES 1 HR RATED WALLS
 PLEASE REVIEW FBC-B TABLE 715.4 FOR OPENING
 PROTECTIVES.
  
 1H) PLEASE PROVIDE ON THE SITE PLAN, THE DISTANCE FROM
 THE PROPERTY LINE TO THE NEW EXTERIOR DOOR. TABLE
 704.8.
  
 1I) THE BACK EXIT PLESE INDICATE BACK EXIT CONDITIONS,
 IS THIS AN ACCESSIBLE EGRESS? 11-4.1.6(1)(D). &
 EXISTING BUILDING CODE TABLE 912.4
  
  
 1J) PLANS ALSO INDICATE ON A-2 A NEW STOREFRONT DOOR
 AND WINDOW SYSTEM, PLEASE PROVIDE WIND DESIGN CRITERIA:
  
 1609.6.2 WIND DESIGN PROCEDURES
 1J)(1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 1J)(2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 1J)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 1J)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 1K) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 1) EXTERIOR DOORS
 2) DOORS
  
 1L) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 1M) NEW EXTERIOR OPENINGS PLEASE PROVIDE DETAILS ON THE
 MWFRS CONTINIOUS LOAD PATH.
  
 1N) A-2 INDICATES NEW STOREFRONT SYSTEM AND DECREASING
 THE STOREFRONT OPENING BY APPROXIMATELY 12 LINIEAL FEET
 WITH NO STRUCTURAL INFORMATION ON THE EXTERIOR WALL
 SYSTEM.MWFRS
 CONTINIOUS LOAD PATH.
  
 1O) PLEASE PROVIDE MANUFACTURERS DETAILS ON THE FOLDING
 PARTITION AS TO INSTALATION, 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 1P) SHEET A-2 FAILS TO INDICATE COMPLIANCE WITH FBC-B
 906.1.
  
 1R) PLEASE PROVIDE COMPLIANCE WITH INTERIOR FINISHES
 FBC-B 803.1 & TABLE 803.5.
  
 1S) MISSING DETAILS ON THE KITCHEN SINK:
 SINKS: 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED
 WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK
  
 2) THE A SHEETS NOR E-1 INDICATE COMPLIANCE WITH THE
 2007 EXISTING BUILDING CODE 912.2.2 FIRE ALARM SYSTEMS
 & 2007 FBC-B 907.2.1 ALSO REVIE EXCEPTION.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2010-10-25 Cont ID  
Sent By jwitmer Date 2010-10-25 Time 11:21 Rev Time 0.00
Received By jwitmer Date 2010-10-25 Time 11:21 Sent To  
Notes
2010-10-25 11:23:32REVIEWED PER D WISE COMMENT MADE ; GROUPING OF MAIN
 DISCONNECTS, NOT MORE THAN 6 THROWS OF HAND. JW

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2010-09-20 Cont ID  
Sent By dwise Date 2010-09-20 Time 17:05 Rev Time 0.00
Received By dwise Date 2010-09-20 Time 17:05 Sent To  
Notes
2010-09-20 17:07:41OK PER JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE
 NUMBER PX3182

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2010-08-30 Cont ID  
Sent By shill Date 2010-08-30 Time 18:01 Rev Time 0.00
Received By shill Date 2010-08-30 Time 18:01 Sent To  
Notes
2010-08-30 18:38:26***********NEED MORE ELECTRICAL INFOMATION************
 1)NEED BUILDING MAIN SERVICE RISER DIAGRAM 2)
 LOAD CALCUATIONS SHOWING NEW EQUIPMENT LOAD
 3)WIRING DIAGRAM SHOWING CONDUIT AND WIRE SIZES

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-07-21 Cont ID  
Sent By btrobaug Date 2010-07-21 Time 13:42 Rev Time 0.00
Received By btrobaug Date 2010-07-21 Time 12:14 Sent To  
Notes
2010-07-21 12:43:43 
  
 REVISION DENIED
  
 1} THE DESIGNER OF RECORD IS THE ONLY PERSON AUTHORIZED
 TO REVISE HIS/HER PLAN. TAKE ALL PROPOSED CHANGES TO
 THE DESIGNER TO BE REDRAWN.
  
 2} 210.62 SHOW WINDOWS.
 AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED
 WITHIN 450 MM (18 IN.) OF THE TOP OF A SHOW WINDOW FOR
 EACH 3.7 LINEAR M (12 LINEAR FT) OR MAJOR FRACTION
 THEREOF OF SHOW WINDOW AREA MEASURED HORIZONTALLY AT
 ITS MAXIMUM WIDTH.***INDICATE LOCATION ON PLANS AND ADD
 TO PANEL SCHEDULE.
  
 3} 220.43 SHOW-WINDOW AND TRACK LIGHTING.
 (A) SHOW WINDOWS. FOR SHOW-WINDOW LIGHTING, A LOAD OF
 NOT LESS THAN 660 VOLT-AMPERES/LINEAR METER OR 200
 VOLT-AMPERES/LINEAR FOOT SHALL BE INCLUDED FOR A SHOW
 WINDOW, MEASURED HORIZONTALLY ALONG ITS BASE.
  
 NOTE: THE PANEL CAND CIRCUIT DESIGNATION NUMBERS ARE
 "M" ON THE PERMIT SET OF PLANS AND "A" ON THE REVISION,
 CORRELATE SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2010-10-15 Cont ID  
Sent By mcarsill Date 2010-10-15 Time 11:52 Rev Time 0.00
Received By mcarsill Date 2010-10-15 Time 11:30 Sent To  
Notes
2010-10-15 11:52:272223 PALM BEACH LAKES BOULEVARD
 PERMIT NUMBER 10070389
  
  
  
 1. SEPARATE PLANS AND PERMIT REQUIRED FOR THE FIRE
 SPRINKLER SYSTEM REMODELING.
  
 2. SEPARATE PLANS AND PERMIT REQUIRED FOR THE FIRE
 ALARM SYSTEM. THE FIRE ALARM SYSTEM WHEN ACTIVATED
 SHALL PROVIDE VOICE EVACUATION INSTRUCTIONS TO
 OCCUPANTS BASED ON THE PROPOSED OCCUPANT LOAD.
  
 3. ALL RATED FIRE EXIT DOORS SHALL BE EQUIPPED WITH
 APPROVED FIRE RATED PANIC HARDWARE. ALL EXIT DOORS
 SUBJECT TO AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE EQUIPPED WITH PANIC HARDWARE.
  
 4. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOORS.
  
 5. ALL FIRE RATED WALLS ARE TO BE PROPERLY IDENTIFIED
 WITH THE HOURLY RATING AND THE WORDING TO PROTECT ALL
 PENETRATIONS.
  
 6. ALL PROPOSED HALLS ARE TO BE EQUIPPED WITH EMERGENCY
 LIGHTING EQUIPMENT TO PROVIDE THE MINIMUM FOOT CANDLES
 REQUIRED IN THE EVENT OF LOSS OF POWER.
  
 7. FINAL OCCUPANT LOAD TO BE DETERMINED BY THIS OFFICE.
  
 8. CROWD MANAGEMENT TRAINING IS REQUIRED FOR THE OWNERS
 OR OPERATORS SINCE THE OCCUPANT IS EXPECTED TO EXCEED
 250 PERSONS. PLEASE GO TO THE MARYLAND STATE FIRE
 MARSHAL'S OFFICE, CLICK THE CROWD MANAGEMENT TRAINING
 ICON, WATCH THE VIDEO, TAKE AND PASS THE TEST, AND
 SUBMIT CERTIFICATES TO THIS OFFICE.
  
 9. A KNOX-BOX IS REQUIRED IF ONE DOES NOT EXIST FOR THE
 PROPERTY ALREADY. PLEASE GO TO WWW.KNOXBOX.COM TO ORDER
 AN EMERGENCY KEY BOX FOR FIRE RESCUE PURPOSES.
  
 10. PLEASE SUBMIT PRODUCT INFORMATION FOR THE DIVIDING
 HALL PARTITIONS. FLAME SPREAD INFORMATION REQUIRED FOR
 THESE PARTITIONS.
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2010-09-29 Cont ID  
Sent By mcarsill Date 2010-09-29 Time 12:44 Rev Time 0.00
Received By mcarsill Date 2010-09-29 Time 12:29 Sent To  
Notes
2010-09-29 12:43:582223 PALM BEACH LAKES BOULEVARD
 PERMIT NUMBER 10070389
  
  
 1. SHEETS A-1 AND A-2 DO NOT MATCH. SHEET A-2 DISPLAYS
 A LARGER PORTION OF THE BUILDING THAN THAT DESCRIBED ON
 SHEET A-1.
  
 2. THE LIFE SAFETY PLAN ON SHEET A-3 DOES NOT MATCH THE
 PROPOSED FLOOR PLAN SHOWN ON PAGE A-4. SEVERAL DOORS
 ARE MISSING FROM THE LIFE SAFETY PLAN.
  
 3. IT APPEARS THAT 500 OCCUPANTS ARE PLANNED BUT NO
 INFORMATION PROVIDED REGARDING A FIRE ALARM SYSTEM
 CAPABLE OF PROVIDING VOICE EVACUATION CAPABILITIES.
 PLEASE PROVIDE THESE DETAILS.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM INSTALLATION AND FIRE SPRINKLER REMODELING.
  
 5. THE PLANS ARE VERY CONFUSING AND THE SEVERAL SHEETS
 DO NOT APPEAR TO CORRESPOND WITH ONE ANOTHER. PLEASE
 COORDINATE SHEETS
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-08-31 Cont ID  
Sent By shill Date 2010-08-31 Time 16:58 Rev Time 0.00
Received By shill Date 2010-08-31 Time 16:58 Sent To  
Notes
2010-08-31 16:58:50OK PER JOHN DICKINSON CONTRACTOR PLAN REVIEWER LICENSE
 PX 3182

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-07-28 Cont ID  
Sent By wjolin Date 2010-07-28 Time 11:42 Rev Time 0.00
Received By wjolin Date 2010-07-28 Time 11:40 Sent To  
Notes
2010-07-28 11:42:01*****APPROVED*****
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-10-14 Cont ID  
Sent By lmartine Date 2010-10-14 Time 10:37 Rev Time 0.00
Received By lmartine Date 2010-10-14 Time 10:37 Sent To  
Notes
2010-10-14 10:40:28IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-09-16 Cont ID  
Sent By lmartine Date 2010-09-16 Time 14:25 Rev Time 0.00
Received By lmartine Date 2010-09-16 Time 14:25 Sent To  
Notes
2010-09-16 14:34:06********************EXPEDITED*************************
 B--1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-02 Cont ID  
Sent By lwagner Date 2010-08-02 Time 13:29 Rev Time 0.00
Received By lwagner Date 2010-07-15 Time 11:49 Sent To  
Notes
2010-07-15 13:12:34********************EXPEDITED********************
 B--12

Review Stop P PLUMBING
Rev No 4 Status P Date 2010-10-22 Cont ID  
Sent By lwagner Date 2010-10-22 Time 08:06 Rev Time 0.00
Received By lwagner Date 2010-10-22 Time 08:06 Sent To  
Notes
2010-10-22 08:25:07*******PROVISO******
  
 51 FIXTURE UNITS WILL REQUIRE A 1" COLD WATER FEED.
 FBC PLUMBING 2007 604.3 AND TABLE 603.1

Review Stop P PLUMBING
Rev No 3 Status P Date 2010-09-17 Cont ID  
Sent By lwagner Date 2010-09-17 Time 08:42 Rev Time 0.00
Received By lwagner Date 2010-09-17 Time 07:35 Sent To  
Notes
2010-09-17 08:20:18*******PROVISO******
  
 51 FIXTURE UNITS WILL REQUIRE A 1??? COLD WATER FEED.
 FBC PLUMBING 2007 604.3 AND TABLE 603.1
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2010-09-08 Cont ID  
Sent By lwagner Date 2010-09-08 Time 10:54 Rev Time 0.00
Received By lwagner Date 2010-08-26 Time 10:30 Sent To  
Notes
2010-08-26 11:23:40FBC PLUNBING 2007 REVIEW #2
 DENIED:
  
 1. WITH THE ADDITION OF WATER CLOSETS IN THE WOMENS
 ROOM, ONE STALL WOULD NEED TO COMPLY WITH 11-4.22.4
 NOTE** THE REQUIRED FIXTURE COUNT FOR MEN IS 4 WC'S OR
 50% OF WC'S COULD BE URINALS. THE FIXTURE COUNT FOR
 WOMEN WOULD BE 6 WC'S DUE TO POTTY PARITY. THE UNISEX
 RESTROOM IS PERMITTED TO BE USED FOR THE WOMENS FIXTURE
 COUNT
  
 4. SHEET A-5 FBC 2007 11-4.17 ADA STALLS IN MENS AND
 WOMENS ROOMS DO NOT COMPLY WITH FIGURE 30(E).
 11-4.22.4 WATER CLOSETS. IF TOILET STALLS ARE PROVIDED,
 THEN AT LEAST ONE SHALL BE A STANDARD TOILET STALL
 COMPLYING WITH SECTION 11-4.17; WHERE SIX OR MORE
 STALLS ARE PROVIDED, IN ADDITION TO THE STALL COMPLYING
 WITH SECTION 11-4.17.3, AT LEAST ONE STALL 36 INCHES
 (915 MM) WIDE WITH AN OUTWARD SWINGING, SELF-CLOSING
 DOOR AND PARALLEL GRAB BARS COMPLYING WITH FIGURE 30(D)
 AND SECTION 11-4.26 SHALL BE PROVIDED. WATER CLOSETS IN
 SUCH STALLS SHALL COMPLY WITH SECTION 11-4.16.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-08-02 Cont ID  
Sent By lwagner Date 2010-08-02 Time 13:18 Rev Time 0.00
Received By lwagner Date 2010-07-27 Time 06:36 Sent To  
Notes
2010-07-27 15:23:30FBC PLUNBING 2007 REVIEW #1
 DENIED:
  
 1. IF FROM BUILDING TOTAL OCCUPANTS IS 614 THEN
 REQUIRED WATER CLOSETS FOR WOMEN WOULD BE 5.
 PLUMBING TABLE 403.1
  
 2. ONE SERVICE SINK WILL BE REQUIRED TABLE 403.1
  
 3. ONE UNISEX TOILET WOULD BE REQUIRED
 E. IN ASSEMBLY AND MERCANTILE OCCUPANCIES, A UNISEX
 TOILET ROOM, IN ACCORDANCE WITH SECTION 403.7, SHALL BE
 PROVIDED WHERE AN AGGREGATE OF SIX OR MORE MALE AND
 FEMALE WATER CLOSETS ARE REQUIRED. IN BUILDINGS OF
 MIXED OCCUPANCY, ONLY THOSE WATER CLOSETS REQUIRED FOR
 THE ASSEMBLY OR MERCANTILE OCCUPANCY SHALL BE USED TO
 DETERMINE THE UNISEX TOILET ROOM REQUIREMENT.
  
 4. FBC 2007 11-4.17 ADA STALL SHALL COMPLY WITH FIGURE
 30(E)
  
 5. A DOMESTIC WATER RISER DIAGRAM IS REQUIRED.
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 6. ALTHOUGH THE FIXTURE COUNT MAY CHANGE, THE CURCUIT
 VENT IN THE SANITARY RISER WILL REQUIRE A DRY VENT
 BETWEEN THE LAST TWO WATER CLOSETS FBC PLUMBING 911.2
  
 7. 4" PIPE IS REQUIRED UP TO THE FIRST ADA WATER CLOSET
 IN DRAWING.
 PLUMBING TABLE 710.1 (2)
  
 8. THE FLOOR DRAINS IN THE RESTROOMS REQUIRE TRAP
 PRIMERS.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  