Plan Review Details - Permit 10070338
Plan Review Stops For Permit 10070338
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-08-17 Cont ID  
Sent By jwitmer Date 2010-08-17 Time 10:19 Rev Time 1.22
Received By jwitmer Date 2010-08-17 Time 10:19 Sent To  
Notes
2010-08-17 10:21:14CBC CAN NOT INSTALL WINDOW AND DOORS ON A HIGH RISE,
 THIS WORK WILL BE COMPLETED UNDER A SEPERATE PERMIT,
 EITHER A CGC OR COUNTY SPECIALTY CONTRACTOR LICENSED
 WINDOW INSTALER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-07-19 Cont ID  
Sent By jwitmer Date 2010-07-19 Time 10:18 Rev Time 1.33
Received By jwitmer Date 2010-07-19 Time 10:18 Sent To  
Notes
2010-07-20 14:50:10BUILDING PLAN REVIEW
 PERMIT: 10070338
 ADD: 1801 S FLAGLER # 803
 CONT: ENVISION CONSTRUCTION LLC
 TEL: (954)579-9001
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-1 INDICATES THTE REMOVAL AND REPLACEMENT OF
 EXTERIOR SLIDING GLASS DOORS AND EXTERIOR SWING DOOR.
 THIS WOULD BE WORKING OUT OF THE SCOPE OF A CBC LICENSE
 SINCE THIS IS HIGH-RISE CONSTRUCTION. FL S
 489.105(3)(B). "BUILDING CONTRACTOR" MEANS A CONTRACTOR
 WHOSE SERVICES ARE LIMITED TO CONSTRUCTION OF
 COMMERCIAL BUILDINGS AND SINGLE-DWELLING OR
 MULTIPLE-DWELLING RESIDENTIAL BUILDINGS, WHICH
 COMMERCIAL OR RESIDENTIAL BUILDINGS DO NOT EXCEED THREE
 STORIES IN HEIGHT, AND ACCESSORY USE STRUCTURES IN
 CONNECTION THEREWITH OR A CONTRACTOR WHOSE SERVICES ARE
 LIMITED TO REMODELING, REPAIR, OR IMPROVEMENT OF ANY
 SIZE BUILDING IF THE SERVICES DO NOT AFFECT THE
 STRUCTURAL MEMBERS OF THE BUILDING.
  
 2) PLEASE PROVIDE WIND DESIGN CRITERIA AND ASSOCIATED
 PRESSURES FOR A 18 STORY HIGHRISE, COASTAL EXPOSURE AND
 THE SLIDING GLASS DOOR AND SWING DOOR BEING LOCATED
 WITHIN THE END ZONE (ZONE 5).
 1609.6.2 WIND DESIGN PROCEDURES
 2.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-07-22 Cont ID  
Sent By btrobaug Date 2010-07-22 Time 07:39 Rev Time 0.00
Received By btrobaug Date 2010-07-22 Time 07:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-08-13 Cont ID  
Sent By mcarsill Date 2010-08-13 Time 12:40 Rev Time 0.00
Received By mcarsill Date 2010-08-13 Time 12:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-08-04 Cont ID  
Sent By mcarsill Date 2010-08-04 Time 10:50 Rev Time 0.00
Received By mcarsill Date 2010-08-04 Time 10:43 Sent To  
Notes
2010-08-04 10:49:581801 SOUTH FLAGLER DRIVE, UNIT 803
 PERMIT NUMBER 10070338
 REMODELING OF EXISTING CONDOMINIUM UNIT
  
  
 1. PLANS DO NOT INDICATE IF AN EXISTING FIRE SPRINKLER
 SYSTEM IS PRESENT. PLEASE ADVISE IF FIRE SPRINKLER
 SYSTEM IS PRESENT.
  
 2. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 4. CONSTRUCTION DEBRIS AND ACTIVITIES SHALL NOT
 INTERFERE WITH ANY REQUIRED EXITS FROM THE BUILDING.
  
 5. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS WITHIN THE UNIT.
  
 6. PLEASE ENSURE THAT THE EXISTING SMOKE ALARMS ARE IN
 GOOD WORKING ORDER.
  
 7. PLANS DO NOT INDICATE THE LOCATIONS OF ANY EXISTING
 FIRE ALARM EQUIPMENT CONTAINED WITHIN OR IMMEDIATELY
 OUTSIDE OF UNIT.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-17 Cont ID  
Sent By jwitmer Date 2010-08-17 Time 10:19 Rev Time 0.00
Received By jwitmer Date 2010-08-10 Time 09:46 Sent To  
Notes
2010-08-11 09:49:44B-15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-04 Cont ID  
Sent By lmartine Date 2010-08-04 Time 15:26 Rev Time 0.00
Received By lmartine Date 2010-07-14 Time 08:57 Sent To  
Notes
2010-07-14 08:57:34B-13

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-08-04 Cont ID  
Sent By hmoser Date 2010-08-04 Time 12:16 Rev Time 0.00
Received By lmartine Date 2010-08-04 Time 12:16 Sent To  
Notes
2010-08-04 12:18:03THERE WERE NO MECHANICAL PLANS SUBMITTED WITH THE
 PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-07-21 Cont ID  
Sent By lwagner Date 2010-07-21 Time 10:03 Rev Time 0.00
Received By lwagner Date 2010-07-21 Time 10:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-07-22 Cont ID  
Sent By eschneid Date 2010-07-22 Time 17:34 Rev Time 0.25
Received By eschneid Date 2010-07-22 Time 17:34 Sent To  
Notes
***NONE***