Plan Review Details - Permit 10070313
| Plan Review Stops For Permit 10070313 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2010-08-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-08-19 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-08-19 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2010-08-19 12:10:46 | 8100 OKEECHOBEE BOULEVARD | | | PERMIT NUMBER 10070313 | | | | | | | | | THIS WRITER ALONG WITH WESLEY JOLIN SPOKE TO TOM | | | WINCHESTER BY TELEPHONE RECENTLY REGARDING THE SECURITY | | | LOCKS FOR THE DOORS. HE EXPLAINED THAT A MOTION SENSOR | | | UNLOCKS THE DOORS AND THE "PUSH TO EXIT" BUTTON IS | | | SOMEWHAT REDUNDANT. EXIT DOORS ARE FAIL SAFE AND NOT | | | FAIL SECURED. | | | | | | | | | APPROVED | | | | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2010-07-23 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2010-07-23 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2010-07-23 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2010-07-23 13:18:49 | *****DENIED***** | | | | | | 1) LOSS OF POWER TO THE PART OF THE ACCESS CONTROL | | | SYSTEM THAT LOCKS THE FRONT DOORS SHALL AUTOMATICALLY | | | UNLOCK THE DOORS IN THE DIRECTION OF EGRESS. | | | 2) THE MANUAL DOOR RELEASE DEVICE SHALL BE UNOBSTRUCTED | | | AND READ, ???PUSH TO EXIT???. WHEN PUSHED, THE MANUAL | | | RELEASE DEVICE SHALL RESULT IN DIRECT INTERRUPTION OF | | | POWER TO THE LOCK-INDEPENDENT OF THE ACCESS CONTROL | | | SYSTEM ELECTRONICS-AND THE DOORS SHALL REMAIN UNLOCKED | | | FOR NOT LESS THAN 30 SECONDS. | | | 3) ACTIVATION OF THE BUILDING FIRE DETECTION SYSTEM OR | | | SIGNALING SYSTEM SHALL AUTOMATICALLY UNLOCK THE DOORS | | | IN THE DIRECTION OF EGRESS. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | & WESLEY JOLIN | | | FIRE PLAN REVIEW | | | 561-805-6730 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2010-08-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-08-19 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-08-05 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2010-08-05 11:28:44 | SENT TO FIRE BOX. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-07-23 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2010-07-23 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2010-07-13 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2010-07-13 09:50:08 | IN FIRE BOX |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |