2010-11-18 07:08:186501 NORTH JOG ROAD
 PERMIT NUMBER 10070305
 FIRE ALARM SYSTEM INSTALLATION
  
  
 1. NO CONTRACT INFORMATION COULD BE LOCATED IN THE
 RE-SUBMITTAL INFORMATION. PLEASE PROVIDE A COPY OF THE
 CONTRACT DECLARING THE COST OF THE PROJECT TO INCLUDE
 LABOR AND MATERIALS. PREVIOUSLY THE WORK WAS VALUED AT
 $ 10,000.00 WHICH APPEARS LOW FOR THE SCOPE OF THE
 PROPOSED WORK.
  
 2. PLEASE PROVIDE CUT SHEETS ON FIRE ALARM EQUIPMENT
 PLANNED FOR USE.
  
 3. ENSURE ALL AREAS OF THE BUILDING ARE PROPERLY
 COVERED BY FIRE ALARM SIGNALING DEVICES.
  
 4. ENTIRE SYSTEM IS TO BE TESTED WITH THIS OFFICE AFTER
 INSTALLATION.
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-07-28 Cont ID  
Sent By mcarsill Date 2010-07-28 Time 14:59 Rev Time 0.00
Received By mcarsill Date 2010-07-28 Time 14:31 Sent To  
Notes
2010-07-28 14:58:58SOLID WASTE AUTHORITY
 6501 NORTH JOG ROAD
 PERMIT NUMBER 10070305
 INSTALL FIRE ALARM SYSTEM
  
  
 1. PERMIT APPLICATION DECLARES A VALUE OF $ 10,000.00
 DOLLARS. THIS VALUE APPEARS LOW. VALUE OF THE JOB
 SHOULD REFLECT LABOR AND EQUIPMENT. PLEASE PROVIDE A
 COPY OF THE CONTRACT.
  
 2. NO FIRE ALARM EQUIPMENT NOTED IN RESTROOMS.
  
 3. NO FIRE ALARM EQUIPMENT SHOWN IN LOCKER ROOM,
 BREAKROOM, OR OTHER LOCKER ROOM.
  
 4. SEVERAL LARGE SHREDDERS ARE DISPLAYED ON FLOOR PLAN.
 ARE THERE ENOUGH SIGNALING APPLIANCES TO COMPENSATE FOR
 ANY NOISE THAT MAY BE PRODUCED BY THESE APPLIANCES.
  
 5. PLEASE EXPLAIN PRE-ACTION EQUIPMENT THAT IS
 DISPLAYED ON THE PLANS.
  
 6. ENTIRE FIRE ALARM SYSTEM INSTALLATION TO COMPLY WITH
 THE REQUIREMENTS OF NFPA 72, THE NATIONAL FIRE ALARM
 CODE.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FM200
 SYSTEM PLANNED TO BE INSTALLED.
  
 8. NO SIGNALING APPLIANCES LOCATED IN VIEWING GALLERY,
 CONTROL ROOM, CONTROL ROOM EXTENSION, OR UNNAMED
 ADJACENT ROOM LOCATED IN THE VICINTY OF THESE ROOMS.
  
 9. NO FIRE ALARM DEVICES DISPLAYED IN OBW CONTROL ROOM.
  
 10. THE OBW SHREDDER, AND THE THREE OTHER SHREDDERS
 APPEAR TO CONTAIN DOORS. NO FIRE ALARM SIGNALING
 APPLIANCES NOTED.
  
 11. WRONG EDITION OF THE FLORIDA FIRE PREVENTION CODE
 REFERENCED. SHOULD READ THE 2007 EDITION NOT THE 2004
 EDITION.
  
 12. ARE ANY BACKFLOW PREVENTION DEVICES BEING
 SUPERVISED OUTSIDE OF THE BUILDING BY THIS FIRE ALARM
 CONTROL PANEL.
  
 13. THE FIRE ALARM SYSTEM IS TO BE MONITORED BY A
 LICENSED COMPANY WHO IS THIRD PARTY APPROVED TO MONITOR
 FIRE ALARM SYSTEMS AS A CENTRAL STATION, APPROVED FOR
 CENTRAL STATION SERVICE.
  
 14. ARE PROTECTED COVERS AND CAGES WARRANTED TO PROTECT
 THE FIRE ALARM SYSTEM EQUIPMENT FROM ANY MECHANICAL
 DAMAGE.
  
 15. A KNOX BOX WILL REQUIRED TO ACCESS THE FIRE ALARM
 SYSTEM IF ONE IS NOT ALREADY AVAILABLE. PLEASE GO TO
 WWW.KNOXBOX.COM TO ORDER A KEY BOX.
  
 16. ENTIRE FIRE ALARM SYSTEM IS TO BE TESTED WITH THIS
 OFFICE AFTER INSTALLATION TO ENSURE PROPER OPERATION.
  
 17. MONIOTRING AND MAINTENANCE AGREEMENTS ARE REQUIRED
 FOR THIS FIRE ALARM SYSTEM.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-11-18 Cont ID  
Sent By mcarsill Date 2010-11-18 Time 07:08 Rev Time 0.00
Received By mcarsill Date 2010-11-10 Time 10:46 Sent To  
Notes
2010-11-10 10:46:06TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-09-10 Cont ID  
Sent By lmartine Date 2010-09-10 Time 08:59 Rev Time 0.00
Received By lmartine Date 2010-09-10 Time 08:59 Sent To  
Notes
2010-09-10 09:00:17IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-28 Cont ID  
Sent By mcarsill Date 2010-07-28 Time 14:59 Rev Time 0.00
Received By mcarsill Date 2010-07-13 Time 08:59 Sent To  
Notes
2010-07-13 08:59:16IN FIRE BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved