Plan Review Details - Permit 10070303
Plan Review Stops For Permit 10070303
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-09-30 Cont ID  
Sent By mcarsill Date 2010-09-30 Time 12:26 Rev Time 0.00
Received By mcarsill Date 2010-09-30 Time 12:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-07-27 Cont ID  
Sent By mcarsill Date 2010-07-27 Time 14:38 Rev Time 0.00
Received By mcarsill Date 2010-07-27 Time 14:29 Sent To  
Notes
2010-07-27 14:38:056501 NORTH JOG ROAD
 PERMIT NUMBER 10070303
 "INSTALL FIRE ALARM SYSTEM"
  
 1. WRONG LIFE SAFETY CODE REFERENCED ON PAGE FS-1.
 SHOULD READ 2006 EDITION NOT 2004 EDITION. SAME PROBLEM
 EXISTS ON PAGE FS-3.
  
 2. PLANS ILLUSTRATE FIRE ALARM AND FM200 FIRE
 SUPPRESSION EQUIPMENT. PERMIT APPLICATION ONLY REFLECTS
 INSTALLATION OF FIRE ALARM SYSTEM.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE FM200 FIRE SUPPRESSION SYSTEM.
  
 4. PLEASE ILLUSTATRATE WIRES TO THE INITIATING AND
 SIGNALING APPLIANCES SHOWN ON THE FLOOR.
  
 5. PLEASE REMIT A COPY OF THE CONTRACT AS THE VALUE
 APPEARS LOW. IS THE VALUE REFLECTED ON THE PERMIT THAT
 FOR THE FIRE ALARM AND THE FM200 SYSTEM? THE VALUE OF
 THE PERMIT SHOULD INCLUDE LABOR AND MATERIALS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-09-10 Cont ID  
Sent By lmartine Date 2010-09-10 Time 08:45 Rev Time 0.00
Received By lmartine Date 2010-09-10 Time 08:45 Sent To  
Notes
2010-09-10 08:46:07IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-09-10 Cont ID  
Sent By lmartine Date 2010-07-27 Time 08:45 Rev Time 0.00
Received By lmartine Date 2010-07-13 Time 08:58 Sent To  
Notes
2010-07-13 08:58:25IN FIRE BOX