Plan Review Details - Permit 10070277
Plan Review Stops For Permit 10070277
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-08-04 Cont ID  
Sent By mcarsill Date 2010-08-04 Time 09:58 Rev Time 0.00
Received By mcarsill Date 2010-08-04 Time 09:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-07-23 Cont ID  
Sent By wjolin Date 2010-07-23 Time 13:15 Rev Time 0.00
Received By wjolin Date 2010-07-23 Time 13:12 Sent To  
Notes
2010-07-23 13:13:31*****DENIED*****
  
 1) PROVIDE CORRECT ADDRESS; 400 NORTH FLAGLER DRIVE NOT
 400 SOUTH FLAGLER DRIVE
 2) HVAC DUCT DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM CONDITION.
 3) PROVIDE SMOKE ALARMS OUTSIDE EVERY SLEEPING AREA.
 4) PROVIDE ANNUNCIATOR PANEL
 5) DEVICE ADDRESSES NOT GIVEN
 6) PLEASE PROVIDE WHAT VOICE EVACUATION MESSAGE WILL
 SAY
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-04 Cont ID  
Sent By mcarsill Date 2010-08-04 Time 09:58 Rev Time 0.00
Received By mcarsill Date 2010-07-29 Time 12:57 Sent To  
Notes
2010-07-29 12:58:15INCOMING SENT TO FIRE ALARM BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-23 Cont ID  
Sent By wjolin Date 2010-07-23 Time 13:12 Rev Time 0.00
Received By wjolin Date 2010-07-13 Time 09:00 Sent To  
Notes
2010-07-13 09:00:31IN FIRE BOX