| 2010-07-21 14:58:43 | FAILED |
| | |
| | 1) PROVIDE AN OVERALL PLAN OF THE BUILDING SHOWING |
| | WHERE THIS IS LOCATED. THE ELECTRICAL PLAN THAT WAS |
| | SUBMITTED DOES NOT MATCH THE EXISTING CONDITION WHERE |
| | STAFF THINKS THE AWNING IS PROPOSED. |
| | |
| | 2) THE SITE PLAN SHOWING THE AWNING SHALL ACCURATELY |
| | SHOW THE SURROUNDING CONDITIONS, INCLUDING THE EXISTING |
| | PALM TO THE WEST OF THE PATIO, AS WELL AS SHOW THE |
| | AWNING TO SCALE ON THE PLAN. CURRENT PLAN DOES NOT SHOW |
| | AWNING TO SCALE OR ACCURATELY AS A DOME STYLE AWNING. |
| | |
| | 3) PROVIDE AN ELEVATION SHOWING THE AWING ON THE |
| | BUILDING, INCLUDING THE REQUIRED EIGHT (8) FOOT MINIMUM |
| | HEIGHT. |
| | |
| | 4) SECTION 94-109(1) OF THE ZONING AND LAND DEVELOPMENT |
| | REGULATIONS REQUIRES THE TYPE OF AWNING USED AND ITS |
| | FORM, MATERIALS AND COLOR SHALL BE CONSISTENT WITH THE |
| | DESIGN CHARACTER OF THE BUILDING TO WHICH IT IS |
| | ATTACHED. THE EXISTING AWNINGS ON THE BUILDING ARE |
| | RECTANGULAR, THEREFORE, A DOME AWNING IS NOT CONSISTENT |
| | WITH THE EXISTING DESIGN CHARACTER. ADDITIONALLY, THE |
| | EXISTING AWNINGS ON THE BUILDING HAVE A COLOR PATTERN |
| | ESTABLISHED OF GREEN WITH RED TRIM. |
| | |
| | 5) SECTION 94-109(2) OF THE ZONING AND LAND DEVELOPMENT |
| | REGULATIONS REQUIRES THAT AWNINGS SHALL BE LOCATED |
| | BETWEEN, RATHER THAN ACROSS, SIGNIFICANT VERTICAL |
| | ARCHITECTURAL FEATURES THAT MAKE UP THE COMPOSITION OF |
| | THE FACADE, SUCH AS PILASTERS OR PROTRUDING COLUMNS. |
| | AWNING FRAMING SHALL ALIGN WITH STOREFRONT FRAMING. THE |
| | PROPOSED AWNING SHALL NOT EXTEND PAST THE STOREFRONT |
| | FRAMING. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
| | |
| | |