Plan Review Details - Permit 10070196
Plan Review Stops For Permit 10070196
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-08-16 Cont ID  
Sent By jwitmer Date 2010-08-16 Time 10:39 Rev Time 0.10
Received By jwitmer Date 2010-08-16 Time 10:39 Sent To  
Notes
2010-08-16 10:40:09RESTAMP PLANS SUTTLE REVISIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-07-12 Cont ID  
Sent By jwitmer Date 2010-07-12 Time 13:20 Rev Time 0.77
Received By jwitmer Date 2010-07-12 Time 13:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-07-21 Cont ID  
Sent By btrobaug Date 2010-07-21 Time 11:00 Rev Time 0.00
Received By btrobaug Date 2010-07-21 Time 10:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-08-12 Cont ID  
Sent By wjolin Date 2010-08-12 Time 13:19 Rev Time 0.00
Received By wjolin Date 2010-08-12 Time 13:10 Sent To  
Notes
2010-08-12 13:16:16*****APPROVED*****
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-08-03 Cont ID  
Sent By wjolin Date 2010-08-03 Time 12:27 Rev Time 0.00
Received By wjolin Date 2010-08-03 Time 11:23 Sent To  
Notes
2010-08-03 12:26:50*****REVIEW COMMENTS - FIRE*****
  
 1) PROVIDE SUITE NUMBER IN TITLE BLOCK INFORMATION.
  
 2) PROVIDE MINIMUM 6" TALL ADDRESS SUITE NUMBER ON
 BUILDING.
  
 3) ALL DEMOLITION WORK SHALL COMPLY WITH NFPA 241.
  
 4) ALL NEW WORK SHALL COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE, 2007 EDITION.
  
 5) SHEET A-1: "EXISTING/DEMO PLAN PLAN" DOES NOT APPEAR
 TO BE SCALED AT 1/4"=1'-0".
  
 6) SHEET A-2: PROVIDE PORTABLE FIRE EXTINGUISHERS PER
 NFPA 10.
  
 7) SHEET A-2: AUTOMOTIVE SERVICE AND REPAIR CLASSIFIES
 AS AN INDUSTRIAL OCCUPANCY, NOT A BUSINESS OCCUPANCY.
  
 8) SHEET A-2: PROVIDE EXIT SIGNAGE AND EMERGENCY
 LIGHTING FOR SMALL CORRIDOR ADJACENT TO RESTROOM.
  
 9) SHEET A-2: EXISTING RESTROOM DOOR SWING OBSTRUCTS
 EGRESS FROM NEWLY FORMED CORRIDOR (NFPA 101, 2007 ED,
 SECTION 7.2.1.4.4).
  
 10) SHEET A-2: DOOR LOCKS SHALL BE OPERABLE FROM THE
 EGRESS SIDE AND SHALL NOT REQUIRE THE USE OF A KEY,
 TOOL, OR SPECIAL KNOWLEDGE TO OPEN.
  
 11) SHEET A-2: ADDITIONAL FIRE SPRINKLERS WILL BE
 REQUIRED BELOW THE NEW GARAGE DOOR. SEPARATE PLANS AND
 PERMIT REQUIRED FOR FIRE SPRINKLER WORK.
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-12 Cont ID  
Sent By wjolin Date 2010-08-12 Time 13:19 Rev Time 0.00
Received By wjolin Date 2010-08-11 Time 08:21 Sent To  
Notes
2010-08-11 08:23:15SENT TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-03 Cont ID  
Sent By wjolin Date 2010-08-03 Time 12:27 Rev Time 0.00
Received By wjolin Date 2010-07-08 Time 12:16 Sent To  
Notes
2010-07-08 12:16:12B-6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-07-19 Cont ID  
Sent By hmoser Date 2010-07-19 Time 13:00 Rev Time 0.00
Received By hmoser Date 2010-07-19 Time 13:00 Sent To  
Notes
2010-07-19 13:02:26DO NOT NEED MECHANICAL PERMIT FOR DEMO .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop Z ZONING
Rev No 1 Status P Date 2010-07-22 Cont ID  
Sent By lfranco Date 2010-07-22 Time 12:46 Rev Time 0.00
Received By lfranco Date 2010-07-22 Time 12:46 Sent To P
Notes
2010-07-22 12:49:11PLANNING AND ZONING: *** PASSED, *ZONING REVIEW NOT
 REQUIRED: INTERIOR WORK ONLY AND THE VALUE OF PROPOSED
 WORK DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE. ****
  
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]