| 2010-07-07 14:15:25 | 400 NORTH CONGRESS AVENUE |
| | INSTALLATION OF FIRE ALARM SYSTEM IN AN EXISTING |
| | BUILDING |
| | PERMIT NUMBER 10070051 |
| | |
| | |
| | 1. THE EXISTING FIRE ALARM SYSTEM IS TO REMAIN |
| | OPERATIONAL UNTIL THE NEW FIRE ALARM SYSTEM AND |
| | EQUIPMENT IS INSTALLED AND READY TO BE SWITCHED OVER. A |
| | FIRE WATCH IS REQUIRED WHENEVER A REQUIRED FIRE SAFETY |
| | SYSTEM IS OUT OF SERVICE FOR MORE THAN FOUR HOURS IN A |
| | TWENTY FOUR HOUR PERIOD. ALL REQUESTS FOR FIRE WATCH |
| | SHALL BE IN WRITING TO THE BATTALION CHIEF OF FIRE |
| | PREVENTION OR HIS DESIGNEE. FIRE WATCH PERSONNEL SHALL |
| | BE RADIO OR TELEPHONE EQUIPPED AND MAINTAIN A LOG OF |
| | ACTIVITIES. |
| | |
| | 2. THE ENTIRE FIRE ALARM SYSTEM SHALL BE INSTALLED IN |
| | ACCORDANCE WITH NFPA 72, THE NATIONAL FIRE ALARM CODE. |
| | |
| | 3. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF |
| | THREE FEET FROM AIR CONDITIONER DIFFUSERS. |
| | |
| | 4. ENTIRE FIRE ALARM SYSTEM SHALL BE TESTED WHEN |
| | INSTALLATION IS COMPLETE. |
| | |
| | 5. DUCT DETECTORS SHALL SEND A GENERAL ALARM SIGNAL. |
| | |
| | 6. THE CENTRAL STATION SHALL RECEIVE WATERFLOW, GENERAL |
| | ALARM, SUPERVISORY, AND TROUBLE SIGNALS. |
| | |
| | 7. ENTIRE FIRE ALARM SYSTEM SHALL BE INSTALLED IN AN |
| | APPROVED MANNER IN ACCORDANCE WITH RECOGNIZED CODES AND |
| | STANDARDS. |
| | |
| | 8. THE APPROPRIATE SMOKE DETECTORS SHALL CAUSE THE |
| | ELEVATORS TO PERFORM PHASE I ELEVATOR RECALL. |
| | |
| | 9. THE FIRE ALARM SIGNALING APPLIANCES SHALL BE AUDIBLE |
| | ENOUGH OVER AMBIENT NOISE LEVELS. |
| | |
| | APPROVED PROVISO |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |