Plan Review Details - Permit 10070051
Plan Review Stops For Permit 10070051
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-07-07 Cont ID  
Sent By mcarsill Date 2010-07-07 Time 14:15 Rev Time 0.00
Received By mcarsill Date 2010-07-07 Time 13:45 Sent To  
Notes
2010-07-07 14:15:25400 NORTH CONGRESS AVENUE
 INSTALLATION OF FIRE ALARM SYSTEM IN AN EXISTING
 BUILDING
 PERMIT NUMBER 10070051
  
  
 1. THE EXISTING FIRE ALARM SYSTEM IS TO REMAIN
 OPERATIONAL UNTIL THE NEW FIRE ALARM SYSTEM AND
 EQUIPMENT IS INSTALLED AND READY TO BE SWITCHED OVER. A
 FIRE WATCH IS REQUIRED WHENEVER A REQUIRED FIRE SAFETY
 SYSTEM IS OUT OF SERVICE FOR MORE THAN FOUR HOURS IN A
 TWENTY FOUR HOUR PERIOD. ALL REQUESTS FOR FIRE WATCH
 SHALL BE IN WRITING TO THE BATTALION CHIEF OF FIRE
 PREVENTION OR HIS DESIGNEE. FIRE WATCH PERSONNEL SHALL
 BE RADIO OR TELEPHONE EQUIPPED AND MAINTAIN A LOG OF
 ACTIVITIES.
  
 2. THE ENTIRE FIRE ALARM SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 72, THE NATIONAL FIRE ALARM CODE.
  
 3. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF
 THREE FEET FROM AIR CONDITIONER DIFFUSERS.
  
 4. ENTIRE FIRE ALARM SYSTEM SHALL BE TESTED WHEN
 INSTALLATION IS COMPLETE.
  
 5. DUCT DETECTORS SHALL SEND A GENERAL ALARM SIGNAL.
  
 6. THE CENTRAL STATION SHALL RECEIVE WATERFLOW, GENERAL
 ALARM, SUPERVISORY, AND TROUBLE SIGNALS.
  
 7. ENTIRE FIRE ALARM SYSTEM SHALL BE INSTALLED IN AN
 APPROVED MANNER IN ACCORDANCE WITH RECOGNIZED CODES AND
 STANDARDS.
  
 8. THE APPROPRIATE SMOKE DETECTORS SHALL CAUSE THE
 ELEVATORS TO PERFORM PHASE I ELEVATOR RECALL.
  
 9. THE FIRE ALARM SIGNALING APPLIANCES SHALL BE AUDIBLE
 ENOUGH OVER AMBIENT NOISE LEVELS.
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-07 Cont ID  
Sent By mcarsill Date 2010-07-07 Time 14:15 Rev Time 0.00
Received By mcarsill Date 2010-07-06 Time 11:48 Sent To  
Notes
2010-07-06 11:48:44IN FIRE BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved