| Plan Review Stops For Permit 10070030 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2010-07-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-07-07 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-07-07 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2010-07-07 12:22:48 | 300 EXECUTIVE CENTER DRIVE | | | TENANT BUILD-OUT FOR NEW DIALYSIS CLINIC- FIRE ALARM | | | PERMIT NUMBER 10070030 | | | | | | | | | 1. WATERFLOW SWITCH SHALL ACTIVATE A WATERFLOW ALARM | | | NOT A GENERAL ALARM AS IDENTIFIED AS ITEM # 5. | | | | | | 2. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT | | | LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS. | | | | | | 3. THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN | | | ACCORDANCE WITH NFPA 72, THE NATIONAL FIRE ALARM CODE. | | | | | | 4. INSTALLATION SUBJECT TO FIELD INSPECTION AND | | | APPROVAL. | | | | | | 5. DUCT DETECTOR WHEN ACTIVATED SHALL CAUSE A GENERAL | | | ALARM SIGNAL. | | | | | | 6. WHEN COMPLETED, THE ENTIRE FIRE ALARM SYSTEM IS TO | | | BE TESTED WITH REPRESENTATIVES OF THIS OFFICE. | | | | | | APPROVED PROVISO | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-07-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-07-07 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-07-01 |
Time |
10:00 |
Sent To |
|
|
| Notes |
| 2010-07-06 10:01:02 | IN FIRE BOX |
|
|
|