Plan Review Details - Permit 10070030
Plan Review Stops For Permit 10070030
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-07-07 Cont ID  
Sent By mcarsill Date 2010-07-07 Time 12:22 Rev Time 0.00
Received By mcarsill Date 2010-07-07 Time 12:14 Sent To  
Notes
2010-07-07 12:22:48300 EXECUTIVE CENTER DRIVE
 TENANT BUILD-OUT FOR NEW DIALYSIS CLINIC- FIRE ALARM
 PERMIT NUMBER 10070030
  
  
 1. WATERFLOW SWITCH SHALL ACTIVATE A WATERFLOW ALARM
 NOT A GENERAL ALARM AS IDENTIFIED AS ITEM # 5.
  
 2. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT
 LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS.
  
 3. THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 72, THE NATIONAL FIRE ALARM CODE.
  
 4. INSTALLATION SUBJECT TO FIELD INSPECTION AND
 APPROVAL.
  
 5. DUCT DETECTOR WHEN ACTIVATED SHALL CAUSE A GENERAL
 ALARM SIGNAL.
  
 6. WHEN COMPLETED, THE ENTIRE FIRE ALARM SYSTEM IS TO
 BE TESTED WITH REPRESENTATIVES OF THIS OFFICE.
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION