Plan Review Details - Permit 10060906
Plan Review Stops For Permit 10060906
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-08-25 Cont ID  
Sent By shill Date 2010-08-25 Time 07:43 Rev Time 0.00
Received By rmcdouga Date 2010-08-24 Time 15:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-08-16 Cont ID  
Sent By shill Date 2010-08-16 Time 18:27 Rev Time 0.00
Received By shill Date 2010-08-16 Time 18:27 Sent To  
Notes
2010-08-16 18:28:29OK PER JOHN DICKINSON (CONTRACT REVIEWER) PX 3182
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-08-03 Cont ID  
Sent By wjolin Date 2010-08-03 Time 14:48 Rev Time 0.00
Received By wjolin Date 2010-08-03 Time 13:46 Sent To  
Notes
2010-08-03 14:47:44*****APPROVED*****
  
 1) SHEET A-4: PROVIDE A 90-MINUTE FIRE RATED DOOR
 ASSEMBLY FOR RECEIVING #109A WHICH HAS A TWO-HOUR RATED
 WALL.
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-25 Cont ID  
Sent By rmcdouga Date 2010-08-25 Time 07:44 Rev Time 0.00
Received By rmcdouga Date 2010-07-01 Time 10:33 Sent To  
Notes
2010-07-01 10:35:58C-9

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-08-06 Cont ID  
Sent By hmoser Date 2010-08-06 Time 10:46 Rev Time 0.00
Received By hmoser Date 2010-08-06 Time 09:43 Sent To  
Notes
2010-08-06 10:58:01PASS PROVISO
 PLANS SHOW EXHAUST DUCT TERMINATING IN THE EXISTING
 MECHANICAL ROOM . PLEASE REFER TO SECTION 501.2 2007
 FBC (M) EXHAUST DISCHARGE ( SHALL BE DISCHARGED
 OUTDOORS )
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-07-13 Cont ID  
Sent By lwagner Date 2010-07-13 Time 14:13 Rev Time 0.00
Received By lwagner Date 2010-07-13 Time 11:13 Sent To  
Notes
2010-07-13 14:14:04REVISION OK