| Plan Review Stops For Permit 10060850 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2010-07-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-07-07 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-07-07 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2010-07-07 14:49:51 | 2903 HILLSBORO ROAD | | | PERMIT NUMBER 10060850 | | | GATE OPERATING DEVICE | | | | | | | | | 1. A KNOX KEY SWITCH IS REQUIRED TO OPERATE THE GATE. | | | PLEASE ORDER THIS DEVICE AT WWW.KNOXBOX.COM. | | | | | | 2. GATE SHALL OPERATE WHEN THE KNOX KEY SWITCH IS USED | | | BY EMERGENCY SERVICE PERSONNEL. | | | | | | 3. AFTER INSTALLATION THE KEY SWITCH IS TO BE TESTED | | | WITH FIRE RESCUE PERSONNEL. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-07-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-07-07 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-06-30 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2010-06-30 08:39:53 | IN ZONING BOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2010-07-07 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2010-07-07 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2010-07-07 |
Time |
09:58 |
Sent To |
FIRE |
|
| Notes |
|
|
|