Plan Review Details - Permit 10060798
Plan Review Stops For Permit 10060798
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-08-04 Cont ID  
Sent By shill Date 2010-08-04 Time 18:27 Rev Time 0.00
Received By shill Date 2010-08-04 Time 18:27 Sent To  
Notes
2010-08-04 18:29:59***PROVISO***
  
 PER CONTRACTOR, ENTIRE JOB IS IN ZONE 4.
  
 PLEASE BE ADVISED THAT IF YOU CIRCLE ZONE 5 PRESSURES,
 DESIGNING TO ZONE 5 WILL BE ENFORCED.
  
 PROVIDE A FLOOR PLAN AT INSPECTION SHOWING SHUTTER
 LOCATION RELATIVE TO BUILDING CORNER.
  
 ISSUED AT CONTRACTOR'S RISK
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-07-06 Cont ID  
Sent By shill Date 2010-07-06 Time 10:47 Rev Time 0.00
Received By shill Date 2010-07-06 Time 10:47 Sent To  
Notes
2010-07-06 10:48:50****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEE PAGE 8 OF THE PRODUCT APPROVAL. ENGINEERING
 REQUIRES -57.2, BUT THIS JOB HAS BEEN DESIGNED TO
 -50PSF. YOU MUST USE -60PSF TO COMPLY WITH DESIGN
 PRESSURE OF -57.2.
  
 PLEASE REVISE INSTALLATION SCHEDULE ACCORDINGLY.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-06 Cont ID  
Sent By shill Date 2010-07-06 Time 10:48 Rev Time 0.00
Received By shill Date 2010-06-29 Time 09:17 Sent To  
Notes
2010-06-29 09:18:04IN MISC.1 BOX