Plan Review Details - Permit 10060790
Plan Review Stops For Permit 10060790
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-09-13 Cont ID  
Sent By shill Date 2010-09-13 Time 11:42 Rev Time 0.00
Received By shill Date 2010-09-13 Time 11:42 Sent To  
Notes
2010-09-13 11:42:51SEPARATE PERMIT REQUIRED FOR SHUTTERS OR PROVIDE IMPACT
 WINDOW PRODUCT APPROVAL AT INSPECTION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-08-23 Cont ID  
Sent By shill Date 2010-08-23 Time 16:01 Rev Time 0.00
Received By shill Date 2010-08-23 Time 16:01 Sent To  
Notes
2010-08-23 16:02:09****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. ADDRESSED.
  
 2. PROVIDE A SITE PLAN SHOWING PROPOSED IMPROVEMENT AND
 DISTANCE TO PROPERTY LINE.
  
 3 - 6. ADDRESSED.
  
 7. PLEASE SHOW HOW THE REDUCED WIDTH WILL AFFECT
 EXITING, FBC CH. 10.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-07-07 Cont ID  
Sent By shill Date 2010-07-07 Time 15:27 Rev Time 0.00
Received By shill Date 2010-07-07 Time 15:27 Sent To  
Notes
2010-07-07 16:30:43****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. EITHER SHOW HOW THIS STRUCTURAL EXTERIOR RENOVATION
 IS EXEMPT FROM ENGINEERING OR PROVIDE ENGINEERING FOR
 THIS IMPROVEMENT.
  
 2. PROVIDE A SITE PLAN SHOWING PROPOSED IMPROVEMENT AND
 DISTANCE TO PROPERTY LINE.
  
 3. BOND BREAK REQUIRED FBC1404.2.1.
  
 4. DECLARE BUILDING TYPE, FBC 5. IT APPEARS THAT YOU
 PROPOSE TO INSTALL COMBUSTIBLE MATERIAL IN A BUILDING
 WHICH CURRENTLY HAS NON COMBUSTIBLE EXTERIOR BEARING
 WALLS; DEMONSTRATE THAT THIS IS PERMITTED UNDER THE
 CODE.
  
 5. DECLARE WIND DESIGN CRITERIA FBC1603.1.4.
  
 6. PROVIDE A COMPLETE STRUCTURAL DETAIL FOR PROPOSED
 WORK. IT IS NOT CLEAR HOW THIS WILL RESIST WIND LOADS
 AS DETAIL WAS INCOMPLETE, ALL FASTENERS NOT SPECIFIED
 AND NO STRAPS SPECIFIED.
 FBC106, FBC 1609.
  
 7. PLEASE SHOW HOW THE REDUCED WIDTH WILL AFFECT
 EXITING, FBC CH. 10.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-09-13 Cont ID  
Sent By shill Date 2010-09-13 Time 11:42 Rev Time 0.00
Received By shill Date 2010-09-07 Time 16:50 Sent To  
Notes
2010-09-07 16:51:09INCOMING SENT TO S HILL DESK/ JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-23 Cont ID  
Sent By shill Date 2010-08-23 Time 16:02 Rev Time 0.00
Received By shill Date 2010-08-09 Time 10:07 Sent To  
Notes
2010-08-09 10:08:01SENT TO S. HILL'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-07 Cont ID  
Sent By shill Date 2010-07-07 Time 16:30 Rev Time 0.00
Received By shill Date 2010-06-29 Time 10:02 Sent To  
Notes
2010-06-29 10:04:16UNDER 5K BUILDING


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved