Plan Review Details - Permit 10060787
Plan Review Stops For Permit 10060787
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-08-04 Cont ID  
Sent By shill Date 2010-08-04 Time 19:23 Rev Time 0.00
Received By shill Date 2010-08-04 Time 19:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-07-12 Cont ID  
Sent By shill Date 2010-07-12 Time 11:59 Rev Time 0.00
Received By shill Date 2010-07-12 Time 11:59 Sent To  
Notes
2010-07-12 12:03:54****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISE EXPOSURE CATEGORY TO EXPOSURE C OR PROVIDE
 ENGINEERING ANALYSIS FOR USING EXPOSURE B PRESSURES AS
 THIS PARCEL IS LOCATED IN A TRANSITION ZONE, SEE
 FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE CHANGED
 EFFECTIVE MARCH 1, 2009.
  
 2. PLEASE REVISE INSTALLATION SCHEDULE TO INCLUDE
 SHUTTER CONNECTION MOUNTING TYPE. THIS SHOULD CORRELATE
 WITH THE ANCHOR CHARTS (FOR EXAMPLE, 1 TOP OR 2
 BOTTOM).
  
 3. PLEASE INDICATE WHICH OPENINGS WILL BE ACCORDION,
 WHICH WILL BE PANELS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-07-29 Cont ID  
Sent By jwitmer Date 2010-07-29 Time 12:48 Rev Time 0.00
Received By jwitmer Date 2010-07-29 Time 12:48 Sent To B
Notes
2010-07-29 12:48:40INCOMING SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-12 Cont ID  
Sent By shill Date 2010-07-12 Time 12:03 Rev Time 0.00
Received By shill Date 2010-06-29 Time 09:12 Sent To  
Notes
2010-06-29 09:12:59IN MISC.1 BOX