Plan Review Details - Permit 10060769
Plan Review Stops For Permit 10060769
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-06-30 Cont ID  
Sent By btrobaug Date 2010-06-30 Time 11:42 Rev Time 0.00
Received By btrobaug Date 2010-06-30 Time 11:39 Sent To I
Notes
2010-06-30 11:42:18SEE THE FOLLOWING 2008 CODE CHANGES:
  
 210.4 (B) DISCONNECTING MEANS. EACH MULTIWIRE BRANCH
 CIRCUIT SHALL BE PROVIDED WITH A MEANS THAT WILL
 SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS AT
 THE POINT WHERE THE BRANCH CIRCUIT ORIGINATES.
  
 210.4 (D) GROUPING. THE UNGROUNDED AND GROUNDED
 CONDUCTORS OF EACH MULTIWIRE BRANCH CIRCUIT SHALL BE
 GROUPED BY WIRE TIES OR SIMILAR MEANS IN AT LEAST ONE
 LOCATION WITHIN THE PANELBOARD OR OTHER POINT OF
 ORIGINATION.
  
 210.12 (B) DWELLING UNITS. ALL 120-VOLT, SINGLE PHASE,
 15- AND 20-AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS
 INSTALLED IN DWELLING UNIT FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR
 SIMILAR ROOMS OR AREAS SHALL BE PROTECTED BY A LISTED
 ARC-FAULT CIRCUIT INTERRUPTER, COMBINATION-TYPE,
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
  
 406.11 TAMPER-RESISTANT RECEPTACLES IN DWELLING UNITS.
 IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT, 15- AND
 20-AMPERE RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT
 RECEPTACLES.
  
 SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2
 RESIDENTIAL FLORIDA BUILDING CODE.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-30 Cont ID  
Sent By btrobaug Date 2010-06-30 Time 11:42 Rev Time 0.00
Received By btrobaug Date 2010-06-28 Time 10:06 Sent To PC
Notes
2010-06-28 10:06:27UNDER 5K ELECTRIC


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved