Plan Review Details - Permit 10060617
Plan Review Stops For Permit 10060617
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-09-27 Cont ID  
Sent By rmcdouga Date 2010-09-27 Time 11:54 Rev Time 0.00
Received By rmcdouga Date 2010-09-27 Time 11:54 Sent To  
Notes
2010-09-27 11:56:02SENT TO ZONING

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-07-12 Cont ID  
Sent By rmcdouga Date 2010-07-12 Time 13:39 Rev Time 0.00
Received By rmcdouga Date 2010-07-12 Time 13:39 Sent To  
Notes
2010-07-12 14:32:122007 FBC W/2009 REVISIONS
 POOL
  
 DENIED BY BUILDING
  
 1) ACCESS FROM THE RESIDENCE TO THE POOL IS ALSO
 REQUIRED TO MEET THE BARRIER REQUIREMENTS OF FBC
 R4101.17. THE METHODS THAT CAN BE USED ARE SPECIFIED IN
 FBC R4101.17. SPECIFY ON THE PLANS THE METHOD THAT WILL
 BE USED FOR THIS PROJECT.
  
 2) A SEPARATE PERMIT FOR GAS IS REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-09-27 Cont ID  
Sent By rmcdouga Date 2010-09-27 Time 11:55 Rev Time 0.00
Received By rmcdouga Date 2010-09-27 Time 11:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-07-12 Cont ID  
Sent By lfranco Date 2010-06-30 Time 13:06 Rev Time 0.00
Received By rmcdouga Date 2010-07-12 Time 13:39 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2010-07-12 Cont ID  
Sent By rmcdouga Date 2010-07-12 Time 13:34 Rev Time 0.00
Received By rmcdouga Date 2010-07-12 Time 13:33 Sent To  
Notes
2010-07-12 13:38:37A SEPARATE PERMIT IS REQUIRED FOR GAS. TWO COPIES OF
 GAS ISOMETRIC DRAWINGS WILL BE REQUIRED TO BE
 SUBMITTED.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2010-06-21 Cont ID  
Sent By swurafti Date 2010-06-21 Time 16:52 Rev Time 0.00
Received By swurafti Date 2010-06-21 Time 16:51 Sent To  
Notes
2010-06-21 16:51:56HISTORIC APPROVED BY FMITTNER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-15 Cont ID  
Sent By shill Date 2010-10-15 Time 11:32 Rev Time 0.00
Received By shill Date 2010-09-21 Time 13:15 Sent To  
Notes
2010-09-21 13:15:37INCOMING TO R MCDOUGAL DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-12 Cont ID  
Sent By rmcdouga Date 2010-07-12 Time 14:28 Rev Time 0.00
Received By rmcdouga Date 2010-06-21 Time 11:36 Sent To  
Notes
2010-06-22 11:36:34IN ZONING BOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-09-27 Cont ID  
Sent By rmcdouga Date 2010-07-12 Time 13:13 Rev Time 0.00
Received By rmcdouga Date 2010-09-27 Time 11:54 Sent To  
Notes
2010-07-12 13:33:392007 FBC W/2009 REVISIONS
 POOL
  
 DENIED BY PLUMBING
  
 1) THE POOL PUMP IS SPECIFIED AS A 1.5 HP IN THE FLOW
 RATE CALCULATIONS ON THE PLANS AND AS A 1 HP PUMP AT
 THE OTHER LOCATIONS ON SHEET 1. PLEASE CORRECT. THE
 ALLOWABLE FLOW RATES WILL BE EXCEEDED IF THE 1.5 HP
 PUMP IS INSTALLED.
  
 2) SUBMIT TWO COPIES OF THE SPECIFICATIONS AND PRODUCT
 DATA SHEETS WHICH INDICATE THE LOSS IN TDH FOR THE GAS
 POOL HEATER AND CARTRIDGE FILTER THAT WILL BE
 INSTALLED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2010-10-08 Cont ID  
Sent By lfranco Date 2010-10-08 Time 17:47 Rev Time 0.00
Received By lfranco Date 2010-09-30 Time 10:32 Sent To I
Notes
2010-10-08 17:49:09PLANNING AND ZONING: *** PASSED, A FENCE PERMIT WAS
 APPROVED ON 8/19/10 ****

Review Stop Z ZONING
Rev No 1 Status F Date 2010-06-30 Cont ID  
Sent By lfranco Date 2010-06-30 Time 13:04 Rev Time 0.00
Received By lfranco Date 2010-06-23 Time 11:12 Sent To E
Notes
2010-06-30 13:12:14PLANNING AND ZONING: **** FAILED ****
  
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PROVIDE DIMENSIONS TO ALL PROPERTY LINES OF POOL
 (EQUIPMENT) ON BOTH THE SURVEY AND SITE PLAN. PURSUANT
 TO SECTION 94-305(B)(4) OF THE ZLDR: MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
  
 3. AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT
 FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINIMUM STANDARDS PROVIDED BELOW: REFERENCE THIS
 PERMIT AS THE MASTER PERMIT WHEN SUBMITTING FOR THE
 FENCE PERMIT. ADD NOTATION ON THE FENCE PERMIT THAT THE
 APPLICATION OF THE FENCE PERMIT IS TO COMPLY WITH THE
 COMMENTS OF THE POOL PERMIT.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B) AND
 (C):
 B. EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE. AT
 LEAST 90 PERCENT OF THE SURFACE AREA OF ALL SCREEN
 ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH WHICH
 AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT SHALL
 BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  