Plan Review Details - Permit 10060551
Plan Review Stops For Permit 10060551
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-06-24 Cont ID  
Sent By mawillia Date 2010-06-24 Time 13:00 Rev Time 0.00
Received By mawillia Date 2010-06-23 Time 16:48 Sent To  
Notes
2010-06-24 12:42:57*****PROVISO******
  
 THE FIRE ALARM PLAN (FA 0.1 & FA 1.0) FIRE-STAMPED
 ACCORDINGLY; READY FOR PERMIT ISSUANCE.
  
  
 REVISED PLANS (THAT HAVE BEEN REVIEWED/APPROVED/STAMPED
 BY CSD) SHALL BE REQUIRED PRIOR TO THE FIRE ALARM FINAL
 - 302 WITH THE FOLLOWING CONDITIONS:
  
 1. FIRE ALARM DEVICE IDENTIFYING NUMBERS LISTED IN THE
 FIRE ALARM RISER SHALL BE CLEAR AND READABLE.
 2. AMEND NOTE #16 IN THE FIRE ALARM NOTES TO REFLECT
 THAT: DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL
 FIRE ALARM.
 3. SMOKE DETECTORS SHOWN IN THE FIRE ALARM SYSTEM
 LAYOUT SHALL HAVE ITS OWN IDENTIFYING ADDRESS/NUMBER.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW