Plan Review Details - Permit 10060532
Plan Review Stops For Permit 10060532
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-08-25 Cont ID  
Sent By shill Date 2010-08-25 Time 12:16 Rev Time 0.00
Received By shill Date 2010-08-25 Time 12:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-07-14 Cont ID  
Sent By lmartine Date 2010-07-14 Time 09:56 Rev Time 0.00
Received By dwise Date 2010-08-23 Time 16:48 Sent To  
Notes
2010-07-14 10:56:39BUILDING REVIEW COMMENTS
  
  
 1)
 PROVIDE COMPLETE SPECIFICATIONS FOR GENERATOR.
  
 2)
 SHOW ANY OPENINGS (OPERABLE WINDOWS AND DOORS) WITHIN
 10' OF THE GENERATOR.
  
 3)
 CONSTRUCTION VALUE PROVIDED ON THE APPLICATION IS NOT
 ACCEPTABLE, PLEASE REVISE VALUE TO INCLUDE ALL COSTS
 ASSOCIATED WITH THE INSTALLATION.
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2010-08-23 Cont ID  
Sent By dwise Date 2010-08-23 Time 17:27 Rev Time 0.00
Received By dwise Date 2010-08-23 Time 17:27 Sent To  
Notes
2010-08-23 17:28:28OK PER JOHN DICKINSON CONTRACTOR PLAN REVIEWER LICENSE
 PX 3182

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2010-08-23 Cont ID  
Sent By dwise Date 2010-08-23 Time 16:51 Rev Time 0.00
Received By dwise Date 2010-08-23 Time 16:51 Sent To  
Notes
2010-08-23 17:02:06OK PER JOHN DICKINSON CONTRACTOR PLAN REVIEWER LICENSE
 PX 3182
2010-08-23 17:01:17NEW SUBMITED LOAD CALCUATIONS AND PANEL SCHEDULE DO NOT
 MATCH,LOADCALCUATION SHOWS 87.5 AMPS ON 100 AMP FEEDER
 AND PANEL, WITHOUT WATER HEATER, WATER HEATER HEATER
 SHOWN ON PANEL SCHEDULE,SHOW FACTORY INSTALLED FEEDER
 SIZE IN 11/4 CONDUIT BETWEEN EXISTING 150AMP PANEL AND
 NEW TRANSFER SWITCH PANEL COMBO

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2010-08-19 Cont ID  
Sent By shill Date 2010-08-19 Time 18:55 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2010-08-19 18:59:40STILL NEED CORRECT PANEL SCHEDULE AND LOAN CALCUATION
 JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE NUNBER PX
 3182 CELL 561 7183230

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-06-30 Cont ID  
Sent By btrobaug Date 2010-06-30 Time 08:29 Rev Time 0.00
Received By btrobaug Date 2010-06-30 Time 08:23 Sent To Z
Notes
2010-06-30 08:29:25THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING
 RECOMMENDED SETBACKS AND ELECTRICAL SPEC'S FOR THE
 GENERATOR AND TRANSFER SWITCH.
  
 2} PROVIDE A CALCULATION FOR THE LOAD BEING SERVED BY
 THE GENERATOR.
  
 3} PROVIDE FEEDER SIZES FROM THE GENERATOR TO THE ATS.
  
 4} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL FOR THE GENERATOR,
 EQUIPMENT(TRANSFER SWITCHES, PANELS ETC.), AND PAD PER
 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN RESUBMITTING,
 AND GET A RECEIPT FROM THE PERMIT CLERK.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-23 Cont ID  
Sent By rmcdouga Date 2010-08-23 Time 17:02 Rev Time 0.00
Received By rmcdouga Date 2010-08-23 Time 17:02 Sent To  
Notes
2010-08-23 17:02:49TO ELECT BOX UNDER $5000

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-14 Cont ID  
Sent By lmartine Date 2010-07-14 Time 10:56 Rev Time 0.00
Received By lmartine Date 2010-06-17 Time 08:43 Sent To  
Notes
2010-06-22 08:43:42UNDER 5K ELECTRIC

Review Stop Z ZONING
Rev No 2 Status P Date 2010-08-25 Cont ID  
Sent By eschneid Date 2010-08-25 Time 11:41 Rev Time 0.50
Received By eschneid Date 2010-08-24 Time 17:13 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-07-07 Cont ID  
Sent By eschneid Date 2010-07-07 Time 10:49 Rev Time 0.50
Received By eschneid Date 2010-07-07 Time 10:49 Sent To G
Notes
2010-07-07 10:58:41FAILED
  
 1) PROVIDE TWO COPIES OF A SURVEY, LESS THAN ONE YEAR
 OLD, WHICH SHOWS THE EXISTING STRUCTURES AND THE
 SETBACKS OF THE STRUCTURES TO THE PROPERTY LINES.
  
 2) PROVIDE THE GENERATOR AND PAD LOCATION ON A SITE
 PLAN, OR MARKED UP COPY OF THE SURVEY, WHICH SHOWS THE
 PROPOSED GENERATOR LOCATION, INCLUDING SETBACKS FROM
 THE PROPERTY LINES AND THE BUILDING. THE BUILDING
 SETBACKS WILL DETERMINE THE GENERATOR SETBACK.
 GENERATOR MAY NOT ENCROACH MORE THAN FOUR (4) FEET INTO
 A REQUIRED SETBACK.
  
 3) PROVIDE THE EXACT DIMENSIONS OF THE GENERATOR AND
 THE PAD.
  
 4) IS ANY LANDSCAPE (TREES OR SHRUBS) BEING AFFECTED BY
 THE GENERATOR INSTALLATION? SHRUBS SHALL BE RELOCATED
 ON-SITE. IF TREES ARE BEING IMPACTED, THEN A TREE
 ALTERATION PERMIT IS REQUIRED FROM THE PLANNING AND
 ZONING DEPARTMENT PRIOR TO THE TREE IMPACT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.