Plan Review Details - Permit 10060422
Plan Review Stops For Permit 10060422
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-02-04 Cont ID  
Sent By jgomez Date 2011-02-04 Time 10:58 Rev Time 0.00
Received By jgomez Date 2011-02-04 Time 10:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-11-03 Cont ID  
Sent By jgomez Date 2010-11-03 Time 10:28 Rev Time 0.00
Received By jgomez Date 2010-11-03 Time 10:28 Sent To  
Notes
2010-11-03 11:18:41RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- A) PROPERTY IS LOCATED ON FLOOD ZONE A5. EXISTING
 HOUSE AND NEW ADDITION NEED TO HAVE A MINIMUM FINISHED
 FLOOR ELEVATION OF 7'-6" AS REQUIRED BY CITY ORDINANCE
 SEC. 94-546 (A)(B). SURVEY AND PROPOSED PLANS NEED TO
 SHOW THE NEW REQUIRED FINISHED FLOOR ELEVATION.
  
 RESPONSE TO SUBMITTAL:
 * FINISH FLOOR ELEVATION SHOWN ON PLANS DON'T MATCH ONE
 SHOWN ON NEW SURVEY. ** FLOOR PLANS DON'T SHOW THE
 FINISH FLOOR ELEVATION OF THE NEW ADDITION.
  
 B) CERTIFICATE ELEVATION WILL BE REQUIRED. (THIS WILL
 BE REQUIRED LATER ON DURING CONSTRUCTION TO VERIFY
 FINISH FLOOR ELEVATION).
  
 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 3- ENGINEER OF RECORD TO REVISE THE DESIGN PARAMETERS
 ON SHEET #1:
 A) CURRENT BUILDING CODE IS THE FBC 2007 WITH 2009
 REVISIONS, NOT FBC 2009 WITH 2009 REVISIONS. REVISE
 NOTES UNDER THE ROOF PLAN NOTES ALSO.
  
 B) ENGINEER NEEDS TO INCREASE THE ROOF SHEATHING UPLIFT
 AND ROOF-TO-WALL UPLIFT LOADS BY 20% AS REQUIRED BY
 SEC. R301.2.1.4.3(2). SHOW COMPLIANCE WITH THIS
 SECTION. (REPEAT COMMENT. NOT ADDRESSED).
  
 C) ONLY THE ROOF TOTAL DEAD LOAD WAS PROVIDED. SPECIFY
 ALL DEAD AND LIVE LOADS INCLUDING THE ATTIC LIVE LOAD
 AS REQUIRED BY TABLE R301.5 (REPEAT COMMENT. NOT
 ADDRESSED).
  
 4- SHEET #2: PROVIDE DIMENSIONS FOR NEW SHOWER AND
 TOILET ROOM TO VERIFY COMPLIANCE WITH THE CLEARANCES
 REQUIRED BY FIGURE R307.1. NOTE: CHECK THE 21 IN.
 CLEARANCE REQUIRED IN FRONT OF THE TOILET. (REPEAT
 COMMENT. FLOOR PLAN DOESN'T PROVIDE THE ROOM
 DIMENSIONS. IT ONLY SHOWS 2' FROM THE WATER CLOSET TO
 THE CENTER OF THE DOOR. ALL WATER CLOSETS ARE NO THE
 SAME. NEED TO PROVIDE ACTUAL ROOM DIMENSIONS ON PLANS
 FOR BOTH WATER CLOSET AND SHOWER ENCLOSURES).
  
 5- SHEET #4:
 A) REVISE GABLE END DETAIL TO COMPLY WITH SEC. R609.4
 AND SEC. R601.2. NEED TO PROVIDE A CONTINUOUS LOAD PATH
 WALL AND ROOF. PROVIDE COMPLETE SPECIFICATIONS FOR ALL
 CONNECTORS. EG: SIZE AND SPACING. ALSO, COORDINATE
 INFORMATION WITH REQUIREMENTS OF ITEM 3(B) ABOVE.
 (REPEAT COMMENT). THERE IS NO INFORMATION OF HOW IS THE
 GABLE END ROOF TRUSS ATTACHED TO THE BOND BEAM TO
 PROVIDE CONTINUOUS LOAD PATH TO THE WALL. ALSO,
 COORDINATE WITH ITEM #3(B) ABOVE.
  
 B) PROVIDE CALCULATIONS SHOWING COMPLIANCE WITH THE
 SIZE AND SPACING OF ATTIC VENTILATION SHOWN ON WALL
 SECTION TO COMPLY WITH THE VENTILATION REQUIREMENTS OF
 SEC. R806.
 (REPEAT COMMENT). CALCULATIONS SUBMITTED ARE INCORRECT.
 NEED TO PROVIDE CALCULATIONS FOR ENTIRE "ATTIC"
 VENTILATION, NOT JUST FOR THE "SOFFIT" VENTILATION.
 REVISE AS REQUIRED.
  
 6- SHEET #5:
 A) ENGINEER OF RECORD TO REVISE CONNECTORS SPECIFIED TO
 COMPLY WITH THE REQUIREMENTS SHOWN ON ITEM 3(B) ABOVE.
 (REPEAT COMMENT. NOT ADDRESSED). ENGINEER TO SPECIFY ON
 PLANS IF THE ROOF SHEATHING UPLIFT AND ROOF TO WALL
 UPLIFT LOADS WERE INCREASED BY 20% AS REQUIRED BY SEC.
 R301.2.1.4.3(2).
  
 B) AND, CLARIFY CONNECTOR SHOWN ON TRUSS LAYOUT FOR
 GABLE END TRUSSES. COORDINATE WITH ITEM #3(B) AND #5(A)
 ABOVE.
  
 C) TRUSS ENGINEER SHOWN ON THE TRUSS LAYOUT TO PROVIDE
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE.
 ***NOTE: TYPICALLLY THE TRUSS ENGINEER PROVIDES TRUSS
 LAYOUT AND INDIVIDUAL TRUSS ENGINEERING ON SEPARATE
 PACKAGE.
  
 7- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 ***NOTE: THIS MAY DE DONE LATER ON BEFORE PERMIT IS
 READY TO BE ISSUED.
  
 8- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 9- ENGINEER OF RECORD TO PROVIDE HIS LICENSE NUMBER AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE. (REPEAT
 COMMENT. DRAWINGS SUBMITTED ARE NOW MISSING THE
 ENGINEER OF RECORD INFORMATION (NAME, LICENSE #,
 ADDRESS, ETC) ON EACH DRAWING.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) HARDIPLANK SOFFIT AS SPECIFIED ON PLANS. NOTE: CHECK
 FRAMING MEMBERS SPACING REQUIRED ON THE PRODUCT
 APPROVAL AND FRAMING MEMBER SHOWN ON PLANS TO MAKE SURE
 INSTALLATION WILL BE DONE ACCORDING TO THE PRODUCT
 APPROVAL REQUIREMENTS. (REPEAT COMMENT, NOT ADDRESSED)
 ENGINEER TO CHECK SHEET 3/3 OF NOA 07-0418.04 SUBMITTED
 AND REVISE FRAMING MEMBERS SPACING AS REQUIRED.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. (REPEAT COMMENT. NOT ADDRESSED).
  
 C) MASTER BATH EXTERIOR DOOR AS SHOWN ON PLANS. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 D) CLARIFY WHICH ROOFING TYPE IS GOING TO BE INSTALLED.
 THREE DIFFERENT PRODUCT APPROVALS WHERE SUBMITTED: ROOF
 TILE, SHINGLES AND METAL ROOFING PANELS. WHICH ONE IS
 GOING TO BE INSTALLED?
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING THE ONES ALREADY SUBMITTED) AS REQUIRED BY
 SEC. 106.3.3 CITY AMENDMENTS TO FBC.
 ***SUBMITTAL RESPONSE: ENGINEER TO PROVIDE ALL HIS
 INFORMATION (NAME, LICENSE NUMBER, ADDRESS, ETC) ON
 LETTER SUBMITTED. AND, MAKE SURE MISSING PRODUCT
 APPROVALS ARE INCLUDED.
  
 12- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED
 TO COMPLY WITH SEC. R807.
 ***SUBMITTAL RESPONSE: REVISED FLOOR PLAN ON SHEET #2
 SHOWS NEW 22" X 56" PULL DOWN STAIRCASE. NEED TO
 PROVIDE OPENING FRAMING DETAILS. ACCORDING TO ROOF
 PLANS NEED TO CUT THE TRUSSES TO ALLOW FOR THE NEW
 OPENING. SEC. 106.1.2 CITY AMENDMENTS TO FBC.
  
 13- OWES $725.38. INCLUDES PERMIT FEE BALANCE, UPDATED
 VALUATION AND RADON FEES.
 ***THIS MAY BE PAID AT TIME OF PERMIT PICK UP.
  
 14- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY CHAPTER
 11 OF 2007 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT.
 NOT ADDRESSED).
  
 15- TRUSS PACKAGE: (REPEAT COMMENT. NOT ADDRESSED).
 A) TRUSS PACKAGE NEED TO BE RE-DESIGNED TO COMPLY WITH
 THE 20% UPLIFT INCREASE AS REQUIRED BY SEC.
 R301.2.1.4.3(2). SEE ITEM #3(C) ABOVE.
 B) NEED ORIGINAL TRUSS ENGINEER SEAL AND SIGNATURE ON
 BOTH COPIES SUBMITTED.
 C) REVISE TRUSS DRAWINGS TO SHOW THE ATTIC LIVE LOAD AS
 REQUIRED BY TABLE R301.5.
 D) TRUSS ENGINEER TO PROVIDE ALL THE INFORMATION ON THE
 COVER SHEET AS REQUIRED BY SEC. 61G15-31.003 OF FLORIDA
 ADMINISTRATIVE CODE IF SIGNING AND SEALING ONLY THE
 COVER PAGE INSTEAD OF SIGNING AND SEALING EACH
 INDIVIDUAL SHEET. IN ADDITION EACH INDIVIDUAL SHEET
 NEED TO HAVE THE TRUSS ENGINEER INFORMATION AS
 REQUESTED BY THIS SECTION ALSO.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-07-07 Cont ID  
Sent By jgomez Date 2010-07-07 Time 13:38 Rev Time 0.00
Received By jgomez Date 2010-07-07 Time 13:36 Sent To  
Notes
2010-07-07 13:48:22RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- A) PROPERTY IS LOCATED ON FLOOD ZONE A5. EXISTING
 HOUSE AND NEW ADDITION NEED TO HAVE A MINIMUM FINISHED
 FLOOR ELEVATION OF 7'-6" AS REQUIRED BY CITY ORDINANCE
 SEC. 94-546 (A)(B). SURVEY AND PROPOSED PLANS NEED TO
 SHOW THE NEW REQUIRED FINISHED FLOOR ELEVATION.
 B) CERTIFICATE ELEVATION WILL BE REQUIRED.
  
 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 3- ENGINEER OF RECORD TO REVISE THE DESIGN PARAMETERS
 ON SHEET #1:
 A) ACCORDING TO 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE SEC. R301.2.1.4.3 THIS BUILDING IS
 LOCATED ON EXPOSURE "C" NOT EXPOSURE "B".
 B) REVISE THE CALCULATED DOORS AND WINDOWS DESIGN
 PRESSURES.
 C) ENGINEER NEEDS TO INCREASE THE ROOF SHEATHING UPLIFT
 AND ROOF-TO-WALL UPLIFT LOADS BY 20% AS REQUIRED BY
 SEC. R301.2.1.4.3(2). SHOW COMPLIANCE WITH THIS
 SECTION.
 D) ONLY THE ROOF TOTAL DEAD LOAD WAS PROVIDED. SPECIFY
 ALL DEAD AND LIVE LOADS INCLUDING THE ATTIC LIVE LOAD
 AS REQUIRED BY TABLE R301.5
 E) DIMENSIONS SHOWN ON PLOT PLAN DON'T MATCH DIMENSIONS
 SHOWN ON SURVEY AND ON NEW FLOOR PLAN ON SHEET #2.
 REVISE AS REQUIRED TO MATCH.
  
 4- SHEET #2: PROVIDE DIMENSIONS FOR NEW SHOWER AND
 TOILET ROOM TO VERIFY COMPLIANCE WITH THE CLEARANCES
 REQUIRED BY FIGURE R307.1. NOTE: CHECK THE 21 IN.
 CLEARANCE REQUIRED IN FRONT OF THE TOILET.
  
 4- SHEET #3:
 A)REVISE WINDOW BUCKS AND DOORS BUCKS SPECIFICATIONS.
 THE PROPOSED CONSTRUCTION IS CONCRETE BLOCK NOT WOOD
 FRAMING.
 B) BEVELED BUCKS ARE NOT ALLOWED. BUCK SIZE NEED TO
 PROVIDE FULL SUPPORT TO THE WINDOW AND DOOR FRAME.
 REVISE AS REQUIRED SEE SEC. R613.6.
  
 5- SHEET #4:
 A) REVISE GABLE END DETAIL TO COMPLY WITH SEC. R609.4
 AND SEC. R601.2. NEED TO PROVIDE A CONTINUOUS LOAD PATH
 WALL AND ROOF. PROVIDE COMPLETE SPECIFICATIONS FOR ALL
 CONNECTORS. EG: SIZE AND SPACING. ALSO, COORDINATE
 INFORMATION WITH REQUIREMENTS OF ITEM 3(C) ABOVE.
 B) REVISE STUCCO THICKNESS ON GABLE END. 7/8" MIN.
 STUCCO THICKNESS IS REQUIRED BY TABLE R702.1(1).
 C) SPECIFY 2 LAYERS OF APPROVED WATER-RESISTANT BARRIER
 ON GABLE END AS REQUIRED BY SEC. R703.6.3.
 D) SPECIFY ROOF SHEATHING NAILING SIZE AND SPACING AS
 REQUIRED BY SEC. R803.2.3.1. NEED TO USE MIN. 8D RING
 SHANK NAILS AND SPACING TO BE 4"O.C. IN ROOF ZONE 3.
 E) PROVIDE CALCULATIONS SHOWING COMPLIANCE WITH THE
 SIZE AND SPACING OF ATTIC VENTILATION SHOWN ON WALL
 SECTION TO COMPLY WITH THE VENTILATION REQUIREMENTS OF
 SEC. R806.
  
 6- SHEET #5:
 A) REVISE CONNECTORS SPECIFIED TO COMPLY WITH THE
 REQUIREMENTS SHOWN ON ITEM 3(C) ABOVE.
 AND CLARIFY CONNECTOR SHOWN ON TRUSS LAYOUT FOR TRUSSES
 T-1G AND T-2G.
 B) REVISE THE BOTTOM CHORD LIVE LOAD TO COMPLY WITH
 TABLE R301.5. NEED TO SPECIFY THE LIVE LOAD IN THE
 ATTIC.
 C) TRUSS ENGINEER SHOWN ON THE TRUSS LAYOUT TO PROVIDE
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE.
  
 7- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 8- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4.
  
 9- ENGINEER OF RECORD TO PROVIDE HIS LICENSE NUMBER AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) GLASS BLOCK AS SPECIFIED ON PLANS.
 B) HARDIPLANK SOFFIT AS SPECIFIED ON PLANS. NOTE: CHECK
 FRAMING MEMBERS SPACING REQUIRED ON THE PRODUCT
 APPROVAL AND FRAMING MEMBER SHOWN ON PLANS TO MAKE SURE
 INSTALLATION WILL BE DONE ACCORDING TO THE PRODUCT
 APPROVAL REQUIREMENTS.
 C) ALL STRUCTURAL CONNECTORS SPECIFIED ON PLANS.
 D) MASTER BATH EXTERIOR DOOR.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING THE ONES ALREADY SUBMITTED) AS REQUIRED BY
 SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 12- PLANS NEED TO SPECIFY CARBON MONOXIDE ALARM AS
 REQUIRED BY SEC. R313.4.
  
 13- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED
 TO COMPLY WITH SEC. R807.
  
 14- OWES $725.38. INCLUDES PERMIT FEE BALANCE, UPDATED
 VALUATION AND RADON FEES.
  
 15- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY CHAPTER
 11 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 16- ENGINEER OF RECORD TO SPECIFY ALTERATION TYPE AS
 REQUIRED BY SEC. 401.4 OF 2007 FBC-EXISTING BUILDING
 CODE.
  
 17- SURVEY PROVIDED:
 A) NEW ADDITION DIMENSIONS DON'T MATCH DIMENSIONS SHOWN
 ON ENGINEER OF RECORD PLANS.
 B) SURVEYOR TO PROVIDE ORIGINAL SIGNATURE (NOT COPY) AS
 REQUIRED BY CHAPTER 472 FLORIDA STATUTE.
  
 18- TRUSS PACKAGE:
 A) TRUSS PACKAGE NEED TO BE RE-DESIGNED TO COMPLY WITH
 THE 20% UPLIFT INCREASE AS REQUIRED BY SEC.
 R301.2.1.4.3(2). SEE ITEM #3(C) ABOVE.
 B) NEED ORIGINAL TRUSS ENGINEER SEAL AND SIGNATURE ON
 BOTH COPIES SUBMITTED.
 C) REVISE TRUSS DRAWINGS TO SHOW THE ATTIC LIVE LOAD AS
 REQUIRED BY TABLE R301.5.
 D) TRUSS ENGINEER TO PROVIDE ALL THE INFORMATION ON THE
 COVER SHEET AS REQUIRED BY SEC. 61G15-31.003 OF FLORIDA
 ADMINISTRATIVE CODE IF SIGNING AND SEALING ONLY THE
 COVER PAGE INSTEAD OF SIGNING AND SEALING EACH
 INDIVIDUAL SHEET. IN ADDITION EACH INDIVIDUAL SHEET
 NEED TO HAVE THE TRUSS ENGINEER INFORMATION AS
 REQUESTED BY THIS SECTION ALSO.
  
 19- CLARIFY WHY THE OWNER LISTED ON THE PERMIT
 APPLICATION AND ON THE PROPERTY APPRAISAL WEBSITE IS
 DIFFERENT THAN THE OWNER LISTED ON THE DRAWINGS
 SUBMITTED. OWNER/BUILDER EXCEPTION APPLIES ONLY TO THE
 OWNER OF THE HOUSE. SEC. 489.103 FLORIDA STATUTE.
 REVISE PLANS ACCORDINGLY.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2011-02-04 Cont ID  
Sent By rmcdouga Date 2011-02-04 Time 13:10 Rev Time 0.00
Received By rmcdouga Date 2011-02-04 Time 13:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-11-10 Cont ID  
Sent By rmcdouga Date 2010-11-10 Time 09:23 Rev Time 0.00
Received By rmcdouga Date 2010-11-10 Time 09:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-06-29 Cont ID  
Sent By btrobaug Date 2010-06-29 Time 16:29 Rev Time 0.00
Received By btrobaug Date 2010-06-24 Time 16:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2011-01-26 Cont ID  
Sent By jgomez Date 2011-01-26 Time 11:35 Rev Time 0.00
Received By jgomez Date 2011-01-26 Time 11:35 Sent To  
Notes
2011-01-26 11:35:46SENT TO R4.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-11-04 Cont ID  
Sent By jgomez Date 2010-11-03 Time 13:05 Rev Time 0.00
Received By jgomez Date 2010-11-03 Time 13:09 Sent To  
Notes
2010-11-04 13:06:27SENT TO R9. NEED ELECTRICAL REVIEW OF NEW ELECTRICAL
 SHEET.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-14 Cont ID  
Sent By lmartine Date 2010-10-14 Time 15:10 Rev Time 0.00
Received By lmartine Date 2010-10-14 Time 15:10 Sent To  
Notes
2010-10-14 15:10:59IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-08 Cont ID  
Sent By jgomez Date 2010-07-08 Time 17:48 Rev Time 0.00
Received By jgomez Date 2010-06-16 Time 08:41 Sent To  
Notes
2010-06-16 08:41:28R-13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2011-02-11 Cont ID  
Sent By jgomez Date 2011-02-11 Time 16:56 Rev Time 0.00
Received By jgomez Date 2011-02-04 Time 13:28 Sent To PC
Notes
2011-02-04 13:28:49NO FEES DUE. MU-2011-2524.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2010-11-03 Cont ID  
Sent By jgomez Date 2010-11-03 Time 08:09 Rev Time 0.00
Received By jgomez Date 2010-11-03 Time 08:09 Sent To  
Notes
2010-11-03 08:09:37BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FESS ARE REQUIRED. BRING BACK STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-07-07 Cont ID  
Sent By jgomez Date 2010-07-07 Time 13:36 Rev Time 0.00
Received By jgomez Date 2010-07-07 Time 13:36 Sent To  
Notes
2010-07-07 13:38:28BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FESS ARE REQUIRED. BRING BACK STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2011-02-08 Cont ID  
Sent By rkussner Date 2011-02-08 Time 16:26 Rev Time 0.00
Received By rkussner Date 2011-02-08 Time 16:26 Sent To  
Notes
2011-02-08 16:42:18***LANDSCAPE PASSED WITH 'PROVISO'***
  
 LANDSCAPE PERMIT APPLICATION WITH TWO SETS OF PLANS
 MUST BE SUBMITTED AND APPROVED PRIOR TO FIRST
 INSPECTION---RAK

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-10-25 Cont ID  
Sent By eschneid Date 2010-10-25 Time 11:40 Rev Time 0.00
Received By eschneid Date 2010-10-25 Time 11:40 Sent To  
Notes
2010-10-25 11:41:12SEE ZONING REVIEW COMMENTS REGARDING THE ITEMS REQUIRED
 FOR LANDSCAPE COMPLIANCE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2011-02-04 Cont ID  
Sent By jgomez Date 2011-02-04 Time 11:46 Rev Time 0.00
Received By jgomez Date 2011-02-04 Time 11:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2010-11-04 Cont ID  
Sent By jgomez Date 2010-11-04 Time 11:12 Rev Time 0.00
Received By jgomez Date 2010-11-03 Time 15:53 Sent To  
Notes
2010-11-03 15:54:27RESIDENTIAL (R3) MECHANICAL REVIEW SECOND CHECKLIST.
 (REPEAT COMMENTS. NOT ADDRESSED).
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE COMPLETE DRAWINGS AND SPECIFICATIONS. NONE
 SUBMITTED.
  
 2- PROVIDE MANUAL J CALCULATIONS FOR EQUIPMENT SIZING.
 NONE SUBMITTED.
  
 3- PROVIDE MECHANICAL VENTILATION IN BATHROOM AS
 REQUIRED BY SEC. M1507 OF 2007 FLORIDA RESIDENTIAL
 CODE. OR PROVIDE COMPLIANCE WITH THE VENTILATION
 REQUIREMENTS OF SEC. R303.3
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-07-08 Cont ID  
Sent By jgomez Date 2010-07-08 Time 11:55 Rev Time 0.00
Received By jgomez Date 2010-07-08 Time 11:55 Sent To  
Notes
2010-07-08 12:31:33RESIDENTIAL (R3) MECHANICAL REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE COMPLETE DRAWINGS AND SPECIFICATIONS. NONE
 SUBMITTED.
  
 2- PROVIDE MANUAL J CALCULATIONS FOR EQUIPMENT SIZING.
 NONE SUBMITTED.
  
 3- PROVIDE MECHANICAL VENTILATION IN BATHROOM AS
 REQUIRED BY SEC. M1507 OF 2007 FLORIDA RESIDENTIAL
 CODE. OR PROVIDE COMPLIANCE WITH THE VENTILATION
 REQUIREMENTS OF SEC. R303.3
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 3 Status P Date 2011-02-04 Cont ID  
Sent By jgomez Date 2011-02-04 Time 11:47 Rev Time 0.00
Received By jgomez Date 2011-02-04 Time 11:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-11-04 Cont ID  
Sent By jgomez Date 2010-11-04 Time 11:12 Rev Time 0.00
Received By jgomez Date 2010-11-04 Time 11:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-07-08 Cont ID  
Sent By jgomez Date 2010-07-08 Time 17:06 Rev Time 0.00
Received By jgomez Date 2010-07-08 Time 12:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2011-02-09 Cont ID  
Sent By eschneid Date 2011-02-09 Time 15:08 Rev Time 0.75
Received By eschneid Date 2011-02-09 Time 15:08 Sent To  
Notes
2011-02-09 15:09:38PASSED W/PROVISO
  
 1) THE VALUE OF THE CONSTRUCTION ($47,407) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($75,667) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. STAFF HAS
 REVIEWED THE SUBMITTED LANDSCAPE PLAN AND MET WITH THE
 OWNER ON-SITE AND DETERMINED THAT THE SITE DOES NOT
 CONFORM TO ARTICLE XIV; THEREFORE, A SEPARATE LANDSCAPE
 PERMIT AND IRRIGATION PERMIT SHALL BE SUBMITTED TO
 INSTALL THE MATERIAL TO BRING THE SITE INTO CONFORMITY
 PRIOR TO THE FIRST INSPECTION FOR THIS PERMIT.
  
 2) THE LANDSCAPE WORK SHALL BE INSTALLED PRIOR TO THE
 FINAL CONSTRUCTION SERVICES INSPECTION FOR THE PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 3 Status F Date 2010-10-28 Cont ID  
Sent By eschneid Date 2010-10-28 Time 09:32 Rev Time 0.50
Received By eschneid Date 2010-10-28 Time 09:32 Sent To B
Notes
2010-10-28 09:38:38FAILED
  
 MET WITH RAY TERRY WHO DRAFTED THE PLANS TO DISCUSS THE
 SETBACK DISCERPANCIES LISTED IN THE 10/25/10 ZONING
 REVIEW. THE NORTH SIDE ADDITION DIMENSION IS FOR THE
 TOTAL ADDITION AND DOES NOT USE THE SAME MEASURE POINT
 AS THE SOUTH SIDE ADDITION DIMENSION, THEREFORE THE
 EAST SIDE SETBACK IS 7 FEET. COMMENTS HAVE BEEN UPDATED
 TO REFLECT THIS CLARIFICATION AND THE PLANS HAVE BEEN
 MARKED ACCORDINGLY. NOT COUNTED AS A ZONING
 RESUBMITTAL.
  
 1) THE VALUE OF THE PERMIT HAS INCREASED SINCE THE
 ORIGINAL ZONING REVIEW AND NOW THE VALUE OF THE
 CONSTRUCTION ($47,407) EXCEEDS 50% OF THE STRUCTURE'S
 VALUE ($75,667) ACCORDING TO THE P.B.C. PROPERTY
 APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION
 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING CONFORMANCE SHALL BE SUBMITTED WITH THE PERMIT.
 IF THE SITE DOES NOT CONFORM TO ARTICLE XIV, THEN A
 SEPARATE LANDSCAPE PERMIT AND IRRIGATION PERMIT SHALL
 BE SUBMITTED TO INSTALL THE MATERIAL TO BRING THE SITE
 INTO CONFORMITY PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT.
  
 2) THE AREA OF THE ON THE EAST PORTION OF THE FRONT OF
 THE PROPERTY (LOCATION SHOWN ON PLANS AS NEW DRIVEWAY)
 SHALL CONTAIN LANDSCAPE MATERIAL IN ACCORDANCE WITH THE
 CITY'S LANDSCAPE REGULATIONS - SECTION 94-442(B). NO
 PERMIT WAS APPROVED FOR A DRIVEWAY OR STORAGE AREA AT
 THIS LOCATION. ANY DISTURBED PARKWAY AREA BETWEEN THE
 SIDEWALK AND THE ROADWAY SHALL BE SODDED IN ACCORDANCE
 WITH SECTION 94-442(B). THIS APPEARS TO HAVE BEEN THE
 CONSTRUCTION ENTRANCE TO THE RECENT POOL INSTALLATION.
 IF THIS AREA IS NO LONGER IN A DISTURBED STATE, PLEASE
 PROVIDE PHOTOGRAPHIC VERIFICATION.
  
 3) NOTE THE A/C UNITS MAY ENCROACH NO FURTHER THAN FOUR
 (4) FEET INTO THE EAST SETBACK.
  
 4) NOTE THE STOOP MAY EXTEND NO CLOSER THAN TWO (2)
 FEET TO THE EASTERN PROPERTY LINE.
  
 5) ANY SHRUBS REMOVED BY THE CONSTRUCTION SHALL BE
 RELOCATED ON-SITE. THIS SHALL BE REFLECTED ON THE
 LANDSCAPE PLAN.
  
 6) ARE ANY TREES OR PALMS PROPOSED TO BE REMOVED AS
 PART OF THE CONSTRUCTION? IF THERE ARE, A TREE
 ALTERATION PERMIT FROM THE PLANNING AND ZONING
 DEPARTMENT IS REQUIRED PRIOR TO THE REMOVAL.
 APPROPRIATE ON-SITE RELOCATION OR REPLACEMENT WILL BE
 REQUIRED TO MITIGATE ANY TREE REMOVAL. THIS SHALL BE
 REFLECTED ON THE LANDSCAPE PLAN.
  
 7) THE DRIVEWAY EXPANSION REQUIRES A SEPARATE PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2010-10-25 Cont ID  
Sent By eschneid Date 2010-10-25 Time 11:38 Rev Time 1.50
Received By eschneid Date 2010-10-20 Time 09:58 Sent To B
Notes
2010-10-25 11:39:07FAILED
  
 1) THE DIMENSION LISTED FOR THE ADDITION???S PROJECTION
 TO THE EAST (INCLUDING THE EXISTING WALL) IS 14 FEET 2
 INCHES AT THE NORTH SIDE OF THE ADDITION AND 13 FEET 9
 INCHES ON THE SOUTH SIDE OF THE ADDITION. PLEASE
 RECTIFY THESE DIMENSIONS.
  
 2) THE SURVEY DATED OCTOBER 12, 2010 SHOWS THE WEST
 SETBACK FROM THE HOUSE TO THE PROPERTY LINE AS 8.0
 FEET. THIS REQUIRES A 7.0 FOOT SETBACK ON THE EAST SIDE
 OF THE HOUSE (TOTAL SETBACK IS REQUIRED TO BE AT LEAST
 15 FEET). THE PLANS SHOW THE ADDITION WITH A 6.5 FOOT
 SETBACK, WHICH IS NOT SUFFICIENT. IF THE ADDITION IS 13
 FEET 9 INCHES (AS DESCRIBED IN COMMENT #1) THEN THE
 SETBACK IS 7 FEET WHEN SUBTRACTED FROM THE 20 FOOT 1
 INCH SETBACK SHOWN ON THE SURVEY (SUBTRACTS 8 INCHES
 FOR THE EXISTING EXTERIOR WALL). IF THE ADDITION IS 14
 FEET 2 INCHES, THEN THERE IS INSUFFICIENT SETBACK. THE
 PLANS SHALL SHOW THE ACCURATE SETBACK TO THE PROPERTY
 LINES BASED ON THE SURVEY AND THE ACCURATE ADDITION.
 PLEASE NOTE: THE SURVEY INCLUDED IN THE ORIGINAL
 APPLICATION SHOWED A WESTERN SETBACK OF 8.8 FEET, WHICH
 WOULD ALLOW A 6.2 FOOT SETBACK ON THE EAST SIDE.
  
 3) THE VALUE OF THE PERMIT HAS INCREASED SINCE THE
 ORIGINAL ZONING REVIEW AND NOW THE VALUE OF THE
 CONSTRUCTION ($47,407) EXCEEDS 50% OF THE STRUCTURE'S
 VALUE ($75,667) ACCORDING TO THE P.B.C. PROPERTY
 APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION
 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING CONFORMANCE SHALL BE SUBMITTED WITH THE PERMIT.
 IF THE SITE DOES NOT CONFORM TO ARTICLE XIV, THEN A
 SEPARATE LANDSCAPE PERMIT AND IRRIGATION PERMIT SHALL
 BE SUBMITTED TO INSTALL THE MATERIAL TO BRING THE SITE
 INTO CONFORMITY PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT.
  
 4) THE AREA OF THE ON THE EAST PORTION OF THE FRONT OF
 THE PROPERTY (LOCATION SHOWN ON PLANS AS NEW DRIVEWAY)
 SHALL CONTAIN LANDSCAPE MATERIAL IN ACCORDANCE WITH THE
 CITY'S LANDSCAPE REGULATIONS - SECTION 94-442(B). NO
 PERMIT WAS APPROVED FOR A DRIVEWAY OR STORAGE AREA AT
 THIS LOCATION. ANY DISTURBED PARKWAY AREA BETWEEN THE
 SIDEWALK AND THE ROADWAY SHALL BE SODDED IN ACCORDANCE
 WITH SECTION 94-442(B). THIS APPEARS TO HAVE BEEN THE
 CONSTRUCTION ENTRANCE TO THE RECENT POOL INSTALLATION.
 IF THIS AREA IS NO LONGER IN A DISTURBED STATE, PLEASE
 PROVIDE PHOTOGRAPHIC VERIFICATION.
  
 5) NOTE THE A/C UNITS MAY ENCROACH NO FURTHER THAN FOUR
 (4) FEET INTO THE EAST SETBACK.
  
 6) NOTE THE STOOP MAY EXTEND NO CLOSER THAN TWO (2)
 FEET TO THE EASTERN PROPERTY LINE.
  
 7) ANY SHRUBS REMOVED BY THE CONSTRUCTION SHALL BE
 RELOCATED ON-SITE. THIS SHALL BE REFLECTED ON THE
 LANDSCAPE PLAN.
  
 8) ARE ANY TREES OR PALMS PROPOSED TO BE REMOVED AS
 PART OF THE CONSTRUCTION? IF THERE ARE, A TREE
 ALTERATION PERMIT FROM THE PLANNING AND ZONING
 DEPARTMENT IS REQUIRED PRIOR TO THE REMOVAL.
 APPROPRIATE ON-SITE RELOCATION OR REPLACEMENT WILL BE
 REQUIRED TO MITIGATE ANY TREE REMOVAL. THIS SHALL BE
 REFLECTED ON THE LANDSCAPE PLAN.
  
 9) THE DRIVEWAY EXPANSION REQUIRES A SEPARATE PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-06-30 Cont ID  
Sent By eschneid Date 2010-06-30 Time 10:49 Rev Time 1.00
Received By eschneid Date 2010-06-30 Time 10:49 Sent To  
Notes
2010-06-30 11:42:25FAILED
  
 1) PROVIDE A RECENT SURVEY, LESS THAN ONE YEAR OLD, FOR
 THE PROPERTY. THE SITE PLAN DOES NOT MATCH THE AERIAL -
 BUILDING FOOTPRINT AND THE EAST SIDE AND REAR YARD
 CONDITIONS.
  
 2) THE NEW DRIVEWAY MAY NOT BE INCLUDED AS PART OF THIS
 PERMIT. PLEASE NOTE THAT THIS PROPERTY IS ONLY ALLOWED
 TO HAVE ONE ACCESS POINT ONTO GREGORY ROAD. THE
 PROPOSED DRIVEWAY WOULD MAKE THE SECOND ACCESS POINT
 AND IS THUS NOT PERMITTED WITHOUT THE REMOVAL OF THE
 OTHER DRIVEWAY.
  
 3) THE AREA OF THE ON THE EAST PORTION OF THE FRONT OF
 THE PROPERTY (LOCATION SHOWN ON PLANS AS NEW DRIVEWAY)
 SHALL CONTAIN LANDSCAPE MATERIAL IN ACCORDANCE WITH THE
 CITY'S LANDSCAPE REGULATIONS - SECTION 94-442(B). NO
 PERMIT WAS APPROVED FOR A DRIVEWAY OR STORAGE AREA AT
 THIS LOCATION. ANY DISTURBED PARKWAY AREA BETWEEN THE
 SIDEWALK AND THE ROADWAY SHALL BE SODDED IN ACCORDANCE
 WITH SECTION 94-442(B). THIS APPEARS TO HAVE BEEN THE
 CONSTRUCTION ENTRANCE TO THE RECENT POOL INSTALLATION.
 IF THIS AREA IS NO LONGER IN A DISTURBED STATE, PLEASE
 PROVIDE PHOTOGRAPHIC VERIFICATION.
  
 4) THE A/C UNIT AND PAD SIZE, DIMENSION AND SETBACK
 FROM PROPERTY LINES SHALL BE SHOWN ON THE SITE PLAN.
 NOTE THE A/C UNITS MAY ENCROACH NO FURTHER THAN FOUR
 (4) FEET INTO THE EAST SETBACK.
  
 5) THE EAST DOORWAY STOOP SIZE, DIMENSION AND SETBACK
 FROM THE EAST PROPERTY LINE SHALL BE SHOWN ON THE SITE
 PLAN. NOTE THE STOOP MAY EXTEND NO CLOSER THAN TWO (2)
 FEET TO THE EASTERN PROPERTY LINE.
  
 6) THE SITE PLAN SHOWS THE NORTHERN DIMENSION LINE OF
 THE ADDITION AS 19.83 FEET, YET THE FLOOR PLAN SHOW THE
 DIMENSION AS 16 FEET 10 INCHES. ALL PLANS SHALL SHOW
 CONSISTENT CONDITIONS.
  
 7) ANY SHRUBS REMOVED BY THE CONSTRUCTION SHALL BE
 RELOCATED ON-SITE.
  
 8) ARE ANY TREES OR PALMS PROPOSED TO BE REMOVED AS
 PART OF THE CONSTRUCTION? IF THERE ARE, A TREE
 ALTERATION PERMIT FROM THE PLANNING AND ZONING
 DEPARTMENT IS REQUIRED PRIOR TO THE REMOVAL.
 APPROPRIATE ON-SITE RELOCATION OR REPLACEMENT WILL BE
 REQUIRED TO MITIGATE ANY TREE REMOVAL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  
  