Plan Review Details - Permit 10060335
Plan Review Stops For Permit 10060335
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-07-26 Cont ID  
Sent By shill Date 2010-07-26 Time 15:09 Rev Time 0.00
Received By shill Date 2010-07-26 Time 15:08 Sent To  
Notes
2010-07-26 15:09:12A101 REVISION 5 DATED 7/7/10
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-23 Cont ID  
Sent By shill Date 2010-06-23 Time 17:13 Rev Time 0.00
Received By shill Date 2010-06-23 Time 17:13 Sent To  
Notes
2010-06-23 18:02:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. IT IS NOT CLEAR HOW YOU HAVE OBTAINED FLOOR AREA.
  
 FOR INSTANCE:
 VESTIBULE/WAITING AREA APPEARS TO BE APPROXIMATELY 300
 SQUARE FEET, BUT LIFE SAFETY DATA ON SHEET A101 SHOWS
 204 SF.
 DINING AREA 1 IS APPROX. 8X26, 208SF, BUT LIFE SAFETY
 DATA FLOOR AREA IS 155 FOR THE TABLE/CHAIRS AREA.
  
 THIS COMMENT APPLIES TO OTHER AREAS. PLEASE EITHER
 REVISE THE LIFE SAFETY DATA, FLOOR AREA OR SHOW HOW THE
 FLOOR AREA HAS BEEN DETERMINED (PROVIDE CLEAR
 DIMENSIONS ON THE PLAN FOR EACH AREA).
  
 2. PLEASE EXPLAIN THE DIFFERENCE BETWEEN "MAXIMUM
 OCCUPANCY" AND "OCCUPANCY LOAD." SEE FBC1004.1.1, THE
 OCCUPANT LOAD CANNOT BE LESS THAN THE TABLE, BUT IF
 DESIGN OCCUPANT LOAD IS HIGHER, THAT NUMBER SHOULD BE
 USED. FOR INSTANCE, ENTRANCE, 204SF, 5SF PER PERSON,
 SHOULD HAVE AN OCCUPANT LOAD OF 41. LIFE SAETY DATA
 SHOWS 36 AND 22. SEE ALSO COMMENT #1 REGARDING FLOOR
 AREA. IF THE VESTIBULE/WAITING AREA IS 300SF, OCCUPANT
 LOAD SHOULD BE 60 BASED ON SQUARE FOOT AREA.
  
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS OR TO EMAIL
 EXPLANATORY INFORMATION.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2010-07-26 Cont ID  
Sent By mcarsill Date 2010-07-26 Time 09:56 Rev Time 0.00
Received By mcarsill Date 2010-07-26 Time 09:34 Sent To  
Notes
2010-07-26 09:56:221. THE FINAL APPROVED OCCUPANT LOAD OF 294 PERSONS IS
 NOT TO BE EXCEEDED FOR ANY REASON. MANAGEMENT PERSONNEL
 SHOULD BE AWARE OF THIS NUMBER AND ADDITIONAL
 MANAGEMENT STAFF WILL NEED TO COMPLETE THE CROWD
 MANAGEMENT TRAINING THAT CAN BE FOUND AT THE MARYLAND
 STATE FIRE MARSHALS WEB-SITE, CROWD MANAGEMENT TRAINING
 ICON.
  
 2. ALL EXITS ARE TO REMAIN CLEAR AND UNOBSTRUCTED WHEN
 THE FACILITY IS IN OPERATION.
  
 3. EXIT ACCESS AISLES ARE TO REMAIN CLEAR AND PASSABLE.
  
 4. ANY FUTURE CHANGES TO THE FLOOR PLAN MUST BE
 SUBMITTED TO THE BUREAU OF FIRE PREVENTION FOR
 APPROVAL.
  
 5. FINAL SEATING AND OCCUPANT LOAD IS TO BE APPROVED BY
 CONSTRUCTION SERVICES AND FIRE RESCUE PERSONNEL.
  
  
  
 APPROVED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-07-07 Cont ID  
Sent By mcarsill Date 2010-07-07 Time 11:43 Rev Time 0.00
Received By mcarsill Date 2010-07-07 Time 11:29 Sent To  
Notes
2010-07-07 11:43:472015 OKEECHOBEE BOULEVARD
 PERMIT NUMBER 10060335
  
  
 1. TWO DIFFERENT OCCUPANCY LOADS ARE NOTED ON THE LIFE
 SAFETY PLAN. ONE IS IDENTIFIED AS THE MAXIMUM OCCUPANCY
 LOAD ALLOWED AND THE OTHER IS THE PROPOSED OCCUPANCY
 LOAD. SINCE THIS DRAWING WHEN APPROVED WILL BECOME A
 PUBLIC RECORD, ONLY ONE OCCUPANT LOAD SHOULD BE ON THE
 DRAWING. THE OCCUPANT LOAD IS TO BE ESTABLISHED USING
 ALL CODE REQUIREMENTS. THE USEABLE AREA DVIDIED BY THE
 OCCUPANT LOAD FACTOR IS TO BE USED TO DETERMINE
 OCCUPANT LOADS. SOME SEATING CALCULATIONS FOR BOOTHS
 APPEAR TO BE ON THE LOW SIDE. ALL SEATS SHOULD BE
 NUMBERED AS TO THE OCCUPANT LOAD SO NO FURTHER
 CONFUSION OCCURS.
  
 2. A FINAL SEATING PLAN IS TO BE SUBMITTED AFTER THESE
 PLANS ARE APPROVED.
  
 3. THE OCCUPANT LOAD WILL BE ESTABLISHED AT TIME OF
 INSPECTION. ALL SEATING IS SUBJECT TO FIELD INSPECTION
 AND APPROVAL. THE FINAL OCCUPANT LOAD ESTABLISHED BY
 THIS OFFICE IS THE LEGAL MAXIMUM AMOUNT ALLOWED WITHIN
 THE ESTABLISHMENT. PRIOR TO THIS OCCURRING A SEATING
 PLAN IS TO BE SUBMITTED THAT IS READILY ABLE TO
 DETERMINE THE OCCUPANT LOAD.
  
 4. A MEETING IS NEEDED TO DISCUSS THE SEATING DIAGRAM
 AND OCCUPANT LOAD.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-06-18 Cont ID  
Sent By mawillia Date 2010-06-18 Time 15:11 Rev Time 0.00
Received By mawillia Date 2010-06-18 Time 12:53 Sent To  
Notes
2010-06-18 15:09:56*****DENIED*****
  
 1) THE ENTRANCE AREA OF 204 SQ.FT. DIVIDED BY 5 SQ.FT.
 PER PERSON EQUALS 41 PERSONS. THE OCCUPANT LOAD IS ONLY
 SHOWN AS 22 PERSONS.
  
 2) THE OCCUPANT LOAD ON THE PLANS SHOULD EITHER BE THE
 NUMBER OF FIXED SEATS OR THE FLOOR AREA DIVIDED BY THE
 OCCUPANT LOAD FACTOR, NOT BOTH. EXAMPLE: DINING AREA 3
 SHOWS "60 SEATS (LOAD 68 PERSONS)." ALSO THE LIFE
 SAFETY DATA CHART SHOWS 617 SQ.FT. FOR DINING AREA 3
 WITH 7SQ.FT. PER PERSON. 617SQ.FT. DIVIDED BY 7 SQ.FT.
 EQUALS 88 PERSONS NOT 28 PERSONS.
  
 3) THE FIXED BOOTH OCCUPANT CALCULATION SHOULD BE BASED
 UPON 18" PER PERSON NOT 24" PER PERSON. REFERENCE
 FLORIDA FIRE PREVENTION CODE (NFPA 101) TABLE 7.3.1.2.
  
 4) THE OCCUPANT LOAD FOR DINING AREA 2 DOES NOT INCLUDE
 THE FIVE WHEELCHAIR SPACES.
  
 5) WHY DOES THE FLOOR AREA PER OCCUPANT VARY BETWEEN
 THE DINING AREAS FROM 15 SQ.FT. PER PERSON TO 7 SQ.FT.
 PER PERSON?
  
  
 CAPT. MICHAEL A. WILLIAMS
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6722
 561-805-6730

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-07-26 Cont ID  
Sent By shill Date 2010-07-26 Time 15:09 Rev Time 0.00
Received By shill Date 2010-07-15 Time 15:01 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-29 Cont ID  
Sent By vmolina Date 2010-06-29 Time 09:05 Rev Time 0.00
Received By vmolina Date 2010-06-29 Time 09:05 Sent To  
Notes
2010-06-29 09:05:43IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-07-15 Cont ID  
Sent By wjolin Date 2010-07-15 Time 15:01 Rev Time 0.00
Received By wjolin Date 2010-06-14 Time 08:27 Sent To  
Notes
2010-06-14 08:42:30B-9