Plan Review Details - Permit 10060335
| Plan Review Stops For Permit 10060335 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2010-07-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-07-26 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-07-26 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2010-07-26 15:09:12 | A101 REVISION 5 DATED 7/7/10 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2010-06-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-06-23 |
Time |
17:13 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-06-23 |
Time |
17:13 |
Sent To |
|
|
| Notes |
| 2010-06-23 18:02:45 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. IT IS NOT CLEAR HOW YOU HAVE OBTAINED FLOOR AREA. | | | | | | FOR INSTANCE: | | | VESTIBULE/WAITING AREA APPEARS TO BE APPROXIMATELY 300 | | | SQUARE FEET, BUT LIFE SAFETY DATA ON SHEET A101 SHOWS | | | 204 SF. | | | DINING AREA 1 IS APPROX. 8X26, 208SF, BUT LIFE SAFETY | | | DATA FLOOR AREA IS 155 FOR THE TABLE/CHAIRS AREA. | | | | | | THIS COMMENT APPLIES TO OTHER AREAS. PLEASE EITHER | | | REVISE THE LIFE SAFETY DATA, FLOOR AREA OR SHOW HOW THE | | | FLOOR AREA HAS BEEN DETERMINED (PROVIDE CLEAR | | | DIMENSIONS ON THE PLAN FOR EACH AREA). | | | | | | 2. PLEASE EXPLAIN THE DIFFERENCE BETWEEN "MAXIMUM | | | OCCUPANCY" AND "OCCUPANCY LOAD." SEE FBC1004.1.1, THE | | | OCCUPANT LOAD CANNOT BE LESS THAN THE TABLE, BUT IF | | | DESIGN OCCUPANT LOAD IS HIGHER, THAT NUMBER SHOULD BE | | | USED. FOR INSTANCE, ENTRANCE, 204SF, 5SF PER PERSON, | | | SHOULD HAVE AN OCCUPANT LOAD OF 41. LIFE SAETY DATA | | | SHOWS 36 AND 22. SEE ALSO COMMENT #1 REGARDING FLOOR | | | AREA. IF THE VESTIBULE/WAITING AREA IS 300SF, OCCUPANT | | | LOAD SHOULD BE 60 BASED ON SQUARE FOOT AREA. | | | | | | PLEASE FEEL FREE TO CONTACT ME TO DISCUSS OR TO EMAIL | | | EXPLANATORY INFORMATION. | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2010-07-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-07-26 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-07-26 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2010-07-26 09:56:22 | 1. THE FINAL APPROVED OCCUPANT LOAD OF 294 PERSONS IS | | | NOT TO BE EXCEEDED FOR ANY REASON. MANAGEMENT PERSONNEL | | | SHOULD BE AWARE OF THIS NUMBER AND ADDITIONAL | | | MANAGEMENT STAFF WILL NEED TO COMPLETE THE CROWD | | | MANAGEMENT TRAINING THAT CAN BE FOUND AT THE MARYLAND | | | STATE FIRE MARSHALS WEB-SITE, CROWD MANAGEMENT TRAINING | | | ICON. | | | | | | 2. ALL EXITS ARE TO REMAIN CLEAR AND UNOBSTRUCTED WHEN | | | THE FACILITY IS IN OPERATION. | | | | | | 3. EXIT ACCESS AISLES ARE TO REMAIN CLEAR AND PASSABLE. | | | | | | 4. ANY FUTURE CHANGES TO THE FLOOR PLAN MUST BE | | | SUBMITTED TO THE BUREAU OF FIRE PREVENTION FOR | | | APPROVAL. | | | | | | 5. FINAL SEATING AND OCCUPANT LOAD IS TO BE APPROVED BY | | | CONSTRUCTION SERVICES AND FIRE RESCUE PERSONNEL. | | | | | | | | | | | | APPROVED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2010-07-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2010-07-07 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2010-07-07 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2010-07-07 11:43:47 | 2015 OKEECHOBEE BOULEVARD | | | PERMIT NUMBER 10060335 | | | | | | | | | 1. TWO DIFFERENT OCCUPANCY LOADS ARE NOTED ON THE LIFE | | | SAFETY PLAN. ONE IS IDENTIFIED AS THE MAXIMUM OCCUPANCY | | | LOAD ALLOWED AND THE OTHER IS THE PROPOSED OCCUPANCY | | | LOAD. SINCE THIS DRAWING WHEN APPROVED WILL BECOME A | | | PUBLIC RECORD, ONLY ONE OCCUPANT LOAD SHOULD BE ON THE | | | DRAWING. THE OCCUPANT LOAD IS TO BE ESTABLISHED USING | | | ALL CODE REQUIREMENTS. THE USEABLE AREA DVIDIED BY THE | | | OCCUPANT LOAD FACTOR IS TO BE USED TO DETERMINE | | | OCCUPANT LOADS. SOME SEATING CALCULATIONS FOR BOOTHS | | | APPEAR TO BE ON THE LOW SIDE. ALL SEATS SHOULD BE | | | NUMBERED AS TO THE OCCUPANT LOAD SO NO FURTHER | | | CONFUSION OCCURS. | | | | | | 2. A FINAL SEATING PLAN IS TO BE SUBMITTED AFTER THESE | | | PLANS ARE APPROVED. | | | | | | 3. THE OCCUPANT LOAD WILL BE ESTABLISHED AT TIME OF | | | INSPECTION. ALL SEATING IS SUBJECT TO FIELD INSPECTION | | | AND APPROVAL. THE FINAL OCCUPANT LOAD ESTABLISHED BY | | | THIS OFFICE IS THE LEGAL MAXIMUM AMOUNT ALLOWED WITHIN | | | THE ESTABLISHMENT. PRIOR TO THIS OCCURRING A SEATING | | | PLAN IS TO BE SUBMITTED THAT IS READILY ABLE TO | | | DETERMINE THE OCCUPANT LOAD. | | | | | | 4. A MEETING IS NEEDED TO DISCUSS THE SEATING DIAGRAM | | | AND OCCUPANT LOAD. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2010-06-18 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2010-06-18 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2010-06-18 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2010-06-18 15:09:56 | *****DENIED***** | | | | | | 1) THE ENTRANCE AREA OF 204 SQ.FT. DIVIDED BY 5 SQ.FT. | | | PER PERSON EQUALS 41 PERSONS. THE OCCUPANT LOAD IS ONLY | | | SHOWN AS 22 PERSONS. | | | | | | 2) THE OCCUPANT LOAD ON THE PLANS SHOULD EITHER BE THE | | | NUMBER OF FIXED SEATS OR THE FLOOR AREA DIVIDED BY THE | | | OCCUPANT LOAD FACTOR, NOT BOTH. EXAMPLE: DINING AREA 3 | | | SHOWS "60 SEATS (LOAD 68 PERSONS)." ALSO THE LIFE | | | SAFETY DATA CHART SHOWS 617 SQ.FT. FOR DINING AREA 3 | | | WITH 7SQ.FT. PER PERSON. 617SQ.FT. DIVIDED BY 7 SQ.FT. | | | EQUALS 88 PERSONS NOT 28 PERSONS. | | | | | | 3) THE FIXED BOOTH OCCUPANT CALCULATION SHOULD BE BASED | | | UPON 18" PER PERSON NOT 24" PER PERSON. REFERENCE | | | FLORIDA FIRE PREVENTION CODE (NFPA 101) TABLE 7.3.1.2. | | | | | | 4) THE OCCUPANT LOAD FOR DINING AREA 2 DOES NOT INCLUDE | | | THE FIVE WHEELCHAIR SPACES. | | | | | | 5) WHY DOES THE FLOOR AREA PER OCCUPANT VARY BETWEEN | | | THE DINING AREAS FROM 15 SQ.FT. PER PERSON TO 7 SQ.FT. | | | PER PERSON? | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | & WESLEY JOLIN | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | 561-805-6730 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2010-07-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-07-26 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-07-15 |
Time |
15:01 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2010-06-29 |
|
|
Cont ID |
|
| Sent By |
vmolina |
Date |
2010-06-29 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
vmolina |
Date |
2010-06-29 |
Time |
09:05 |
Sent To |
|
|
| Notes |
| 2010-06-29 09:05:43 | IN FIRE BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-07-15 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2010-07-15 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2010-06-14 |
Time |
08:27 |
Sent To |
|
|
| Notes |
|
|
|