Plan Review Details - Permit 10060332
Plan Review Stops For Permit 10060332
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-06-23 Cont ID  
Sent By jgomez Date 2010-06-23 Time 09:15 Rev Time 0.00
Received By jgomez Date 2010-06-23 Time 09:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-06-17 Cont ID  
Sent By shill Date 2010-06-17 Time 17:34 Rev Time 0.00
Received By shill Date 2010-06-17 Time 17:34 Sent To  
Notes
2010-06-17 17:35:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE PROVIDE A SECOND COPY OF THE INSTALLATION
 SCHEDULE.
  
 2. REVISE EXPOSURE CATEGORY TO EXPOSURE C OR PROVIDE
 ENGINEERING WHICH DEMONSTRATES THAT THE PRESSURES FOR
 EXPOSURE B ARE APPLICABLE AS THIS PARCEL IS LOCATED IN
 A TRANSITION ZONE. FBC1609, FBC R301.2.1.4. NOTE THAT
 THE CODE CHANGED EFFECTIVE MARCH 1, 2009.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-06-17 Cont ID  
Sent By shill Date 2010-06-17 Time 17:35 Rev Time 0.00
Received By shill Date 2010-06-14 Time 08:08 Sent To  
Notes
2010-06-14 08:08:53IN MISC.1 BOX