Plan Review Details - Permit 10060255
Plan Review Stops For Permit 10060255
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-06-14 Cont ID  
Sent By jwitmer Date 2010-06-14 Time 14:27 Rev Time 0.77
Received By jwitmer Date 2010-06-14 Time 14:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-06-30 Cont ID  
Sent By btrobaug Date 2010-06-30 Time 07:05 Rev Time 0.00
Received By btrobaug Date 2010-06-30 Time 06:48 Sent To P
Notes
2010-06-30 07:10:38NEW PLUMBING SHEETS./WRT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-06-30 Cont ID  
Sent By btrobaug Date 2010-06-30 Time 06:45 Rev Time 0.00
Received By btrobaug Date 2010-06-16 Time 15:00 Sent To  
Notes
2010-06-16 15:25:26NEED CEILING PLAN FOR BOTH SPACES
  
 NEED ENERGY CALCULATION FOR LIGHTING
  
 ALL SWITCH GEAR IS SHOWN NEMA 1 OUTSIDE?????
  
 PLEASE REVISE PRIOR TO THE FINAL INSPECTION JL
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-06-17 Cont ID  
Sent By mawillia Date 2010-06-17 Time 14:46 Rev Time 0.00
Received By mawillia Date 2010-06-17 Time 14:26 Sent To  
Notes
2010-06-17 14:38:14*****APPROVED*****
  
  
 PLAN SHEETS A2.0, A3.0, AND E1.0 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-07-14 Cont ID  
Sent By vmolina Date 2010-07-14 Time 08:50 Rev Time 0.00
Received By vmolina Date 2010-07-14 Time 08:50 Sent To  
Notes
2010-07-14 08:50:37IN PLUMBING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-06-17 Time 14:46 Rev Time 0.00
Received By vmolina Date 2010-06-09 Time 12:17 Sent To  
Notes
2010-06-09 12:19:50B-22

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-06-17 Cont ID  
Sent By lwagner Date 2010-06-17 Time 10:44 Rev Time 0.00
Received By lwagner Date 2010-06-17 Time 10:17 Sent To  
Notes
2010-06-17 10:43:48****NOTE****
  
 MINIMUM 30" CENTER TO CENTER REQUIRED BETWEEN LAV AND
 HC WC 405.3.1

Review Stop Z ZONING
Rev No 1 Status N Date 2010-06-17 Cont ID  
Sent By kdfreema Date 2010-06-17 Time 08:33 Rev Time 0.00
Received By kdfreema Date 2010-06-17 Time 08:33 Sent To  
Notes
2010-06-17 08:34:24PROPOSED WORK DOES NOT EXCEED 50% OF STRUCTURE VALUE.