| 2010-06-18 10:23:26 | PLAN REVIEWER: DEAN LAUDERMILK |
| | PHONE: 494-1083 |
| | FAX: 494-1116EMAIL: [email protected] |
| | PLAN STATUS: PASSED WITH PROVISOS: |
| | THE PLAN HAS BEEN PASSED TO ALLOW CONSTRUCTION TO |
| | START. THERE ARE ISSUES THAT MUST BE MET PRIOR TO |
| | COMPLETING THE WORK. THE PLAN SHEETS AND SHOP DRAWINGS |
| | WILL NEED TO BE RESUBMITTED FOR THE FOLLOWING ISSUES: |
| | SHEET E-1: |
| | 1) THE POLES ARE SHOWN OUTSIDE OF THE EASEMENT PROVIDED |
| | FOR BY THE PROPERTY OWNER. THE DOTTED LINE AT THE |
| | BOTTOM OF THE SHEET IS NOT AN EASEMENT LINE, IT WAS A |
| | PROPOSED CONSTRUCTION EASEMENT THAT WAS NOT GIVEN. THE |
| | POLES AND CONDUITS NEED TO BE INSTALLED IN THE |
| | SIDEWALK. THE USABLE SPACE OF THE EASEMENT HAS BEEN |
| | HIGHLIGHTED. |
| | SHEET E-2: |
| | 1) THE PROPERTY LINE ON THE NORTH SIDE OF THE ALLEY AND |
| | THE WEST SIDE OF SPENCER HAS BEEN HIGHLIGHTED TO SHOW |
| | THAT THE CONDUITS FROM THE FP&L POLE ARE SHOWN INSIDE |
| | PRIVATE PROPERTY, THEY CAN NOT BE LOCATED AS SHOWN, |
| | THEY NEED TO BE INSIDE THE ALLEY ROW. |
| | 2) THERE IS NO ROOM TO INSTALL THE ELECTRICAL METER AND |
| | BREAKER PANEL IN THE ALLEY ROW, IT WILL NEED TO BE |
| | INSTALLED IN THE SPENCER DRIVE ROW, FAR ENOUGH FROM THE |
| | ALLEY AS TO NOT BE WITHIN THE SITE LINES (SHOWN ON THE |
| | DRAWINGS) AND A HEDGE WILL NEED TO BE INSTALLED ON THE |
| | SOUTH SIDE TO BLOCK THE VIEW OF THE PANEL FROM THE |
| | ROAD. |
| | 3) TYPICAL ALL SHEETS; CHECK THE REST OF THE |
| | INTERSECTIONS, LIGHT POLES ARE NOT ALLOWED INSIDE THE |
| | SITE LINE TRIANGLE, WHICH MEASURES 20' ON EACH STREET. |
| | ONE POLE AT THIS ALLEY WILL NEED TO BE RELOCATED. |
| | SHEET E-5: |
| | 1) THE CITY IS LOOKING AT USING LED LIGHTS. PLEASE |
| | CONTACT THE ELECTRICAL ENGINEER AND SUPPLIER ON |
| | RESUBMITTING THE LIGHTS. |
| | |